QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
24
| Quick configuration guides
5.10.4 Operation settings
Adjust the start/stop point for the digital output: Cooling start (SEQ-C) in the Data & Settings > Temperature
control > Cooling menu.
Overview:
Data & Settings > Temperature control > Cooling
24 Jun 10:31
Digital start output start point 10 %
Digital start output stop point 1 %
PID-delay after DX-compressor start
30 s
Data & Settings > Temperature control > Supply air
controller
24 Jun 10:31
Min limit supply air
14 °C
Max limit supply air
30 °C
Reduction of min limit supply air if active DX-cooling
5 °C
Min setpoint deviation to allow start of DX-cooling
2 °C
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Temperature control
3. Select Cooling
4. Set the desired output % to activate the digital output as Digital start output start point
5. Set the desired output % to deactivate the digital output as Digital start output stop point
6. Set the desired time delay in PID-delay after DX-compressor start.
7. Go back to Temperature control (use the navigation path Data & Settings > Temperature control)
8. Select Supply air controller
9. Adjust the min. allowed supply air temperature when DX-Cooling is active as Reduction of min limit supply
air if active DX-cooling.
10.Set the desired value in Min setpoint deviation to allow start of DX-cooling.
157618 | A008