Argus RC C
2
RC-C
RC-C
RC-C
Control states
Argus-RC-C can be configured for different control
states/
control sequences:
• Heating
• Heating or cooling via the change-over function
• Heating/Heating
• Heating/Cooling
• Heating/Cooling with VAV-control and forced
supply air function
• Heating/Cooling with VAV-control
• Cooling
• Cooling/Cooling
Operating modes
There are five different operating modes: Off,
Unoccupied, Stand-by, Occupied and Bypass. Occupied is
the preset operating mode. It can be changed to Stand-by
with a dipswitch. The operating modes can be activated
via a central command or an occupancy detector.
Off: Heating and cooling are disconnected. However,
the temperature must not drop below the set minimum
temperature (Factory setting (FS)=8°C). Operating mode
Off is activated on open window.
Unoccupied: The room where the controller is placed
is not used for an extended period, for example during
holidays or long weekends. Both heating and cooling
are disconnected within a temperature interval with
configurable min/max temperatures (FS min=15°C,
max=30°C).
Stand-by: The room is in an energy save mode and is
not used at the moment. This can for example be during
nights, weekends, evenings etc. The controller is prepared
to change operating mode to Occupied if someone enters
the room. Both heating and cooling are disconnected
within a temperature interval around the applicable
setpoint (FS heating setpoint value=-3°C, cooling
setpoint=+3°C).
Occupied: The room is in use and is therefore in a
comfort mode. The controller regulates the temperature
around a heating setpoint (FS=22°C) and a cooling
setpoint (FS=24°C).
Bypass: The temperature in the room is controlled in the
same way as in operating mode Occupied. The output
for forced ventilation is also active. Bypass is useful for
example in conference rooms, where many people are
present at the same time for a certain period of time.
After 10 minutes absence, the controller will
automatically return to the preset operating mode
(Occupied or Stand-by).
Occupancy detector
By connecting an occupancy detector, Argus-RC-C
can switch between Bypass and the preset operating
mode (Occupied or Stand-by). The temperature is then
controlled according to requirement, which saves energy
and keeps the temperature at a comfortable level.
Change-over function
Argus-RC-C has an input for change-over that
automatically resets output UO1 to operate with heating
or cooling function. The input can be connected to
sensors of type PT1000 and have the sensor mounted so
that it senses the temperature on the supply pipe to the
coil.
When the temperature exceeds 22°C, the output function
is set to heating and when the temperature drops below
18°C, the output is set to cooling.
As an alternative, a potential-free contact can be used.
When the contact is open the controller works with the
heating function and when it is closed, with the cooling
function.
To ensure satisfactory functioning using sensor, the system
must have continuous primary circuit circulation. When
the change-over function is not used, the input must be
left disconnected.
Setpoint
In Occupied mode, the controller operates from a heating
setpoint (FS=22°C) or a cooling setpoint (FS=24°C) that
can be changed centrally or locally using dipswitches.
The setpoint can be adjusted up and down
(FS=±3°C) with the knob on the front of the controller.
Switching between heating and cooling setpoints is done
automatically in the controller depending on the heating
and cooling requirement.
Built-in safety functions
Argus-RC-C has an input for a condensation detector
which prevents condensation. The controller also has frost
protection. It prevents frost damages by ensuring that the
room temperature does not drop below 8°C when the
controller is in Off-mode.
Indications
The controller has an LED shaped like a thermometer on
the front. A red indication is shown when heating control
is functional and a blue indication when cooling control is
active. No LED indication shows that neither heating nor
cooling control is active.
Actuator exercise
All actuators are exercised. The exercise takes place at
set intervals in hours (FS=23 hours interval). An opening
signal is sent to the actuator for as long time as the run
time has been configured. Then a closing signal is sent for
as long time and the exercise is finished.