PTB01ATEX1016
30. Januar 2001
S U P P L E M E N T A R Y S H E E T 07
to EC TYPE-EXAMINATION CERTIFICATE PTB 01 ATEX 1016
Fitting of terminal boxes Type 8146/1061
Max. number of conductors
1)
depending on cross section and the permissible continuous current:
current / A cross section / mm
2
1,5 2,5 4 6 10 16 25 35
3
6
10 53
16 18 35 137 2)
20 7 20 39
25 9 22 43
35 6 17 42
50 2 13 35
63 4 16 57
80 6 18 64
100 7 17 4)
125 6
160 3)
92 92 66 34 24 19 11 9
max. number of terminals depending of the above mentioned enclosure size and
the cross section resp. max. permissible conductor cross section of the built-in
terminals
Notes
1) Each incoming conductor and each internal connection wire is counted as a conductor.
Bridges and earthing conductors are not counted.
2) additional conductors optional
3) to be specified by the manufacturer (including temperature rise test)
4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be
considered. Mixed equipment with circuits of different cross sections and currents is possible if
the various values of the table are applied proportionally:
Example: cross section / mm² current / A number of utilization
(general) conductors
2,5 16 10 (of 30) = 33 %
16 50 12 (of 48) = 25 %
25 63 36 (of 90) = 40 %
total = 98 % < 100 %