Original instructions SWX H SE ... 7 FR ... 28 GB ... 11 NO ... 15 DE ... 19 ES ... 24 IT NL ... 36 PL ... 41 RU ... 45 ...
SWX H SWX A min 150 ØI E G B F C H D [mm] SWXH13 SWXH23 A 550 705 B 530 655 C 380 430 D 630 700 Electrical installation 230V~ Terminal box 0,85 m cable 2 E ø22 ø28 F 250 270 G 330 420 H 410 505 ØI 10 10
SWX H Accessories HxWxD Type SWXHFT1 SWXHFT2 SWXH13 SWXH23 [mm] 455x525x15 595x650x15 SWXHFT Controls SWX H Type RSK-nr (SE) NRF-nr (NO) SWXRT70 HxWxD [mm] 175x150x100 SWXRT70 Water regulation SWX H Type SD20* TVV20* TVV25* RSK-nr (SE) 672 70 37 672 70 35 672 70 36 NRF-nr (NO) 85 021 57 85 021 47 85 021 48 + TVV20/25 SD20 *) Note: Only for mounting outside hot environments >50 °C.
SWX H Wiring diagrams SWX H Internal SWXH -13 -23 SWX CE/CS -12, -22 SWXD -13, -23 M ~ 10 11 BK BU WT RD L N Control by thermostat only SWXH -13, -23 SWXH -13, -23 M ~ M ~ SD20* SD20* TVV20/25* TVV20/25* 10 11 BK BU WT RD L N *) Note! Only for mounting outside hot environments >50 °C.
SWX H SWX H Typ Heat output*1 [kW] SWXH13 12 SWXH23 23 Air flow [m³/h] 1830 3870 Air flow [m³/s] 0,5 1,1 Sound level*2 [dB(A)] 57 68 ∆t*1,3 [°C] 21 20 Air throw [m] 6 9 Water volume*4 [l] 2,2 3,8 Voltage Amperage Weight [V] 230V~ 230V~ [A] 0,5 1,35 [kg] 28 46 *1) Applicable at water temperature 80/60 °C, air temperature, in +40 °C. *2) Conditions: Distance to the unit 5 metres. *3) ∆t = temperature rise of passing air at maximum heat output. *4) Water volume inside battery.
SWXH13 SWXH23 Type SWXH13 SWXH23 Type SWXH13 SWXH23 Type 43,0 53,4 0,53 Air temp. in = +20 °C Output Air Water temp. flow out [kW] [°C] [l/s] 21,8 55,9 0,27 7,5 23,1 59,6 0,28 Air temp. in = +40 °C Pressure Output Air Water drop temp. flow out [kPa] [kW] [°C] [l/s] 5,9 11,8 61,2 0,14 Incoming / outgoing water temperature 98/85 °C Air temp. in = +20 °C Air temp. in = +40 °C Airflow Output Air Water Pressure Output Air Water temp. flow drop temp.
SWX H GB Installation and operating instructions General Instructions Read these instructions carefully before installation and use. Keep this manual for future reference. The product may only be used as set out in the assembly and operating instructions. The guarantee is only valid if the product is used in the manner intended and in accordance with the instructions. Application SWX is a range of fan heaters suitable for environments with strict demands on materials and safety.
GB SWX H Fitting the wall brackets 1. Remove the eight screws indicated by the arrows in picture A. A 3. The fan heater may be mounted with the connection pipes facing left or right, as seen from the front. In rooms with high ceilings, the fan heater should be installed in a low position, but not so low that it intrudes on the working space. Make sure that the wall is able to support the weight of the fan heater. 2. Install the brackets with the holes toward the fan motor, as shown in picture B. B 4.
SWX H Connection of heating coil The installation must be carried out by an authorised installer. By turning the fan heater, pipe connections are possible on both sides. Connect the water supply pipe to the lower pipe on the heater and connect the outlet pipe to the upper pipe, as shown by the arrows in picture E. Ø22 connection on SWXH13 and ø28 connection on SWXH23. If compression fittings are installed, check that they can withstand the pressure and temperature of the heating medium.
GB SWX H Cleaning The interval between each cleaning depends on the environment the fan heater is used in. Dust on the fan protective grille and on the water coil’s aluminum fins impedes the airflow and reduces its heat exchanging performance. The water coil must therefore be kept clean. The fan cooling flanges also need to be kept clean, to obtain the lowest possible motor operating temperature.
Tel: +46 31 336 86 00 mailbox@frico.se www.frico.net For latest updated information and information about your local contact: www.frico.net.