Installation Manual

2
B
A
A horizontally incline angle
should not larger than 10°.
Vertical
≤ ±10°
Direction A
≤ ±10°
Direction B
≤ ±10°
>0.5m
>0.5m
>0.5m
Installation Precaution
Pay attention to the distance of straight horizontal pipe.
a.The straight horizontal pipe’s distance between two adjacent branch
pipes should ≥0.5m.
b.Distance between two adjacent branches should ≥0.5m.
c.The straight horizontal pipe’s distance which outdoor unit connecting
behind the branch pipe should ≥0.5m.
Indoor unit
Indoor unit
Indoor unit
Installation Notices
1) Select the branch pipes’
2) According to the actual piping size and cut off the needless parts with special tools such as cutter, take the
model according to the Model Selection Guide and the downstream indoor unit capacity.
JOINT IN 01 gas0 side for example and the operating steps as follow:
a.When selecting model JOINT IN 01, the actual object as display in Fig.1, and then suppose that the present
using pipe isΦ15.9 , then as display in Fig.2, cut the welded pipe of the branch pipe component.
b.As display in Fig.2, cut the standalone connecting pipe.
c.As display in Fig.3, weld the branch pipe components with the field pipes.
3) Particularly notice the followings:
a.When the actual pipe size matches with the un-welded side of U-shape three direct links, weld the pipe with the
U-shape three direct links directly.
b.For the separate un-welded connecting pipe of JOINT IN06, as display in Fig. 3, please cut in the bottom of the
necking side if the flaring side is needed to be used, and vice versa.
Fig.1
Fig.2 Fig.3
Cut here
Cut here
Cut here
Cut here
Horizontally Placing Branch Pipe
Heat insulation
1) Example of connected branch.
2) Use the supplied heat insulation material
to insulate the branches against heat.
3) Apply the heat insulation material and
seal all connections with tape.
Be sure to insulate the brahches
against heat
heat insulation material(supplied)
Field pipe
Field pipe
Branch (supplied)
Field pipe
Tape
Field piping heat
insulation material
Adhesive paper(tear off before pasting)