Impedance Information
(Applicable to some countries of Middle East Area only)
To be in compliance with EN61000-3-11, the product MTI-48HWN1-R shall be connected
only to a supply of the system impedance: Zsys = 0.267802236 Ω or less. Before connecting
the product to public power network, please consult your local power supply authority to
ensure the power network meet above requirement.
To be in compliance with EN61000-3-11, the product MTIT4-36CWN1-QC5 (Indoor Unit:
MTIT4-36CWN1-QC5 , Outdoor Unit:MOT4DU-36CN1-QC5)shall be connected
only to a supply of the system impedance: Zsys = 0.021893 Ω or less. Before connecting
the product to public power network, please consult your local power supply authority to
ensure the power network meet above requirement.
To be in compliance with EN61000-3-11, the product MTIT4-36CWN1-QC5 (Indoor Unit:
MTIT4-36CWN1-QC5 , Outdoor Unit:MOT4V-36CN1-QC5 )shall be connected
only to a supply of the system impedance: Zsys = 0.024 Ω or less. Before connecting
the product to public power network, please consult your local power supply authority to
ensure the power network meet above requirement.
To be in compliance with EN61000-3-11, the product MTI-60HWN1-R shall be connected
only to a supply of the system impedance: Zsys = 0.214 Ω or less. Before connecting
the product to public power network, please consult your local power supply authority to
ensure the power network meet above requirement.
To be in compliance with EN61000-3-11, the product MTIT-32CWN1-QC5 shall be connected
only to a supply of the system impedance: Zsys = 0.083964 Ω or less. Before connecting
the product to public power network, please consult your local power supply authority to
ensure the power network meet above requirement.