IMO PRF, PRF EX 009 312436

12
| Electrical connection
10.1 Installation positions
The installation is possible in any mounting position.
10.2 Lightning protection device
If the risk assessment shows that there is the risk of an atmospheric discharge, lightning protection measures must
be taken. For reasons of operational safety, provide for a suitable lightning protection system according to country
specific directives (e.g. DIN VDE 0185).
11 Electrical connection
Safety information
Danger
Risk of ignition of a potentially explosive gas/air atmosphere!
If the wire ends which have not been connected are fitted to the external current circuits within an area
with a potentially explosive atmosphere,
a connection box (with its own certification and explosion-protection identification) which has been
selected as suitable for this area must be used.
the electrical data, information on temperature monitoring and on admissible operation with part voltage,
if applicable, can be found on the relevant data sheet.
Electronic accessories without explosion-protection (e.g. RTRD control device and UEK motor protection)
must be installed outside the explosion capable area.
Speed control by frequency converter is only admissible for devices with the „Pressure-proof
encapsulation Ex d“ ignition protection class.
The types #33985 PRF-EX 180D4 and #34532 PRF-EX 125D2 are not speed controllable by frequency
converter.
Protection against explosions in general:
Earth at the planned earthing point.
In hazardous areas connect conductive components to a potential equalisation system.
Warning: Danger from electrical voltage!
Observe the 5 rules of electrical safety, see 3.3 5 rules of electrical safety, page 3.
Prevent the ingress of water into the connection box.
Electrical connection may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page
3.
Connection
Check if the data on the nameplate matches the
connection data.
Complete the electrical connection according to the
circuit diagram.
Use all of the locking screws.
Insert the screws by hand to avoid damaging the
thread.
Tighten all glands well in order to guarantee
protection class IP.
Screw the lid of the terminal box/inspection switch
evenly tight.
Connect the cable end in a dry environment.
Install a circuit breaker in the permanent electrical
installation, with a contact opening of at least 3 mm
at each pole.
Potentially, the fans may become charged with static
electricity. If this represents a risk, please contact
Systemair.
Protective grounding wire
The protective grounding must have a cross-section equal to or greater than that of the phase conductor.
Residual current circuit breaker
All-current-sensitive residual current circuit breakers are required for use in alternating-current systems with 50/60
Hz, in combination with electronic devices such as EC motors, frequency converters or uninterruptible power supplies
(UPS).
| 009