SYSPLIT CEILING R32 INSTALLATION MANUAL
Page 6 Page 6
Amount of refrigerant
to be charged (kg)
maximum installation
height (m)
Minimum room
area (m²)
≤2.048 1.8m 4
≤2.048 0.6m 35
2.048-3.0 1.8m 8
2.048-3.0 0.6m 80
>3.0 1.8m 9
>3.0
Model
(Btu/h)
≤30000
≤30000
30000-48000
30000-48000
>48000
>48000 0.6m 80
WARNING
• Appliance shall be installed, operated and stored in a room with a oor area larger than X m²,
installation of pipe-work shall be kept to a minimum X m²(Please see the following form ).
The appliance shall not be installed in an unventilated space, if that space is smaller than X m²
(Please see the following form ).Spaces where refrigerant pipes shall be compliance with
national gas regulations.
•
Any person who is involved with working on or breaking into a refrigerant circuit should hold a
current valid certicate from an industry-accredited assessment authority, which authorises their
competence to handle refrigerants safely in accordance with an industry recognised assessment
specication.
•
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out
under the supervision of the person competent in the use of ammable refrigerants.
•
Appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specied for operation.
•
Appliance shall be stored in a room without continuously operating open ames (for example
an operating gas appliance) and ignition sources (for example an operating electric heater).
• The appliance shall be stored in a room without continuously operating ignition sources
(for example: open ames, an operating gas appliance or an operating electric heater).
• Do not pierce or burn.
•
The appliance shall be stored so as to prevent mechanical damage from occurring.
•
•
Be aware that the refrigerants may not contain an odour.
• Keep ventilation openings clear of obstruction.
Compliance with national gas regulations shall be observed.
• A warning that the appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specied for operation.