IOM SYSPLIT WALL PRIME R32

Page 22
Indoor Unit
Installation
BEFORE PERFORMING ANY
ELECTRICAL WORK, READ THESE
REGULATIONS
1. All wiring must comply with local and national
electrical codes, regulations and must be
installed by a licensed electrician.
2. All electrical connections must be made
according to the Electrical Connection Diagram
located on the panels of the indoor and outdoor
units.
3.
If ther
e is a serious safety issue with the power
suppl
y, stop work immediately. Explain your
reasoning to the client, and r
efuse to install the
unit until the safety issue is p
roperly resolved.
4. Power voltage should be within 90-110% of
rated voltage. Insu
fficient power supply can
cause
malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, a surge
p
rotector and main power switch should be
installed.
6. If connecting power to fixed wiring, a switch
or circuit br
eaker that disconnects all poles and
has a contact separation of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The
qualified technician must use an approved
circuit breaker or switch.
7. Only connect the unit to an individual branch
ci
rcuit outlet. Do not connect another appliance
to
that outlet.
8.
Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose
wiring can cause the terminal to overheat,
r
esulting in
product malfunction and possible fire.
Do not let wires touch or rest against r
efrigerant
tubing, the comp
ressor
, or any moving parts
within the unit.
If the unit has an auxiliary electric heater, it must
be installed at least 1 meter (40in) away
fr
om
any
combustible materials.
To avoid getting an electric shock, never touch
the electrical components soon after the power
supply has been turned off. After turning off
the power, always wait 10 minutes or more
before you touch the electrical components.
10.
11.
12.
WARNING
BEFORE PERFORMING ANY ELECTRICAL
OR WIRING WORK, TURN OFF THE
MAIN POWER TO THE SYSTEM.
Step 6: Connect signal and power cables
The signal cable enables communication between
the indoor and outdoor units. You must first
choose the right cable size before preparing it for
connection.
Cable Types
Indoor Power Cable
(if applicable):
H05VV-F or H05V2V2-F
Outdoor Power Cable: H07RN-F or H05RN-F
Signal Cable: H07RN-F
(Not applicable for North America)
NOTE: In North America, choose the cable type
according to the local electrical codes and
regulations.
Minimum Cross-Sectional Area of
Power and Signal Cables (For reference)
Rated Current of
Appliance (A)
Nominal Cross-Sectional
Area (mm²)
> 3 and 6
0.75
> 6 and
10
1
> 10 and 16
1.5
> 16 and
25
2.5
> 25 and 32
4
> 32 and
40
6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal
cable, fuse, and switch needed is determined
by the maximum current of the unit. The
maximum current is indicated on the nameplate
located on the side panel of the unit. Refer to
this nameplate to choose the right cable, fuse,
or switch.
NOTE: In North America, please choose the
right cable size according to the Minimum
Circuit Ampacity indicated on the nameplate
of the unit.