SYSVRF2 CASSETTE 1W GB One-way Cassette Type INSTALLATION MANUAL
CONTENTS PAGE INSTALLATION PRECAUTION.................................................................. 1 ACCESSORIES........................................................................................ 1 UNIT STRUCTURE INTRODUCTION......................................................... 2 INSTALLATION SPACE............................................................................ 2 INTDOOR UNIT INSTALLATION .............................................................. 2 DRAINPIPE INSTALLATION.....
. Unit structure introduction 01 02 4. INSTALLATION SPACE Unit Please avoid installing in the following places A place with flammable gas or material. A saline place such as a seashore vicinity A place with sulphur gas. A place with oil gas, such as kitchen. A place with high-humidity air. An unbearable place. A place where high-frequency waves are generated. The appliance shall not be installed in the laundry.
No. Model Unit mm Steel roof beam structure Install the supporting angle steel. Hanging screw bolt Hanging bolts Please accord to the follow figure’s requirements to design the length of the suspender bolt. Supporting angle steel Fig.5-5 Hoisting the indoor unit take 18-36 as an example, operation method of 45-71are the same.
Install the panel component, and wiring (take 18-36 as an example, operation method of 45-71 are the same.) Two buckles on the panel component are used for assisting the panel installation, the installing method of the buckle as Fig.5.10 display. Panel component wiring: open the electric control panel, connect the wiring terminal of the control display box and the motor connecting terminal of the air leading bar as the figure display to the main control panel.
. DRAINPIPE INSTALLATION Install the screw Before installation please check the connecting cable etween panel and air conditioner whether has clamped, if clamped, the panel will be unfairness after fastening the screws and When connecting the pipe, please use the sealing material and pipe glove. damage the wires. CAUTION The drain pipe of indoor unit must be heat insulated, or it will condense dew, as well as the connections of the indoor unit. Make sure the connections is no leakage.
Please according to the tube hardness to choose proper support density, do not appear obvious dropping and deformation situation. Dropping part will save the water and lead to poor drainage and abnormal noise. 7. INSTALL THE CONNECTING PIPE The connective length of indoor and outdoor piping and those height difference requirements. Connect to different outdoor units with different connective length and height difference requirements. Please refer to Indoor Unit Installation Manual for detail.
Fig.7-1 A _ 90+4 45+_2 Use frozen oil Fig.8-2 Table.8-1 Bend the pipe with thumb A(mm) Outside diameter Fig.7-2 Make the ends straight Fig.7-3 Max Min 8.7 8.3 12.4 12.0 15.8 15.4 19.0 18.6 Fasten the nut Locate The Pipe Drill a hole in the wall (suitable just for the size of the wall conduit, 90mm in general), then set on the fittings such as the wall conduit and its cover. Bind the connecting pipe and the cables together tightly with binding tapes.
. WIRING CHART Air Purging Attaching wiring Use a vacuum pump, to vacuum from the gas side refrigerant adding mouth of the outdoor unit. The air conditioner should use separate power supply with rated voltage. Don’t use the refrigerant of the outdoor unit to do the vacuum. (A certain volume of refrigerant had been added into the outdoor unit in factory.) The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor and outdoor unit.
To wired To outdoor/ indoor controller POWER INPUT units COMM. BUS COMM.
Outdoor power supply RCCB Wire slot Grounding line Indoor unit Grounding line Indoor power supply RCCB Signal wire for communicate indoor unit and outdoor unit Fig.
10. CONTROL OPERATION Network address set Network address is set by communication of indoor and is no need to set separately. F 01 2 BC 3 4 56 DE Horsepower set 7 A ON ON ON ON ON ON ON POWER_S CN17 CN20 SW6 SW5 SW4 SW3 SW2 SW1 SW7 ENC1 CN3 CN13 main control panel CN24 CN55 CN4 J1 CN30 CN25 CN6 CN11 J2 CN16 CN7 89 CN5 CN8 CN9 CN15 CN31 CN21 CN14 Fig.10-1 Base on different purposes to setting the switch cords on PC panel of indoor electrical control box.
Main board Code designation Guide for main control panel dial code SW 1 ● 0 means cooling mode temperature ON ON compensation is 0°C (default) ● 1 means cooling mode temperature compensation is 2°C 12 SW1 ● 0 means EXV positions 96 (steps) in 12 SW2 ON 12 SW 2 ON ON 12 SW3 ON 12 SW 3 ON standby heating mode (default) ● 1 means EXV positions 72 (steps) in standby heating mode Reserved (Default 0) 12 ON S W6 12 Reserved (Default 0) ● 0 means auto addressing mode (default) O N ● 1 means clea
11. TEST OPERATION The test operation must be carried out after the entire installation has been completed. CAUTION A protection feature prevents the air conditioner from being activated for approximately 3 minutes when it is restarted immediately after shut off . Please confirm the following points before the test operation: The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed. The refrigerant pipe system is leakage-checked. The drainage is unimpeded.
MD17I-021B 16126000002928