SYSVRF2 CASSETTE 1W IM
Fig.10-1
Table.10-1
10. CONTROL OPERATION
Base on different purposes to setting the switch cords on PC panel
of indoor electrical control box. Once finish the setting, please cut off
the main power, and then input power again, otherwise, setting
function could not work.
Network address is set by communication of indoor and
is no need to set separately.
There are maximum 64 indoor units in one refrigerant
system,and each of them should occupy one unique
address, from 0 to 63. Repeated indoor address will result
in error.
Please switch off the power before configuring settings,or an
error may occur.
CAUTION
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Horsepower set
Network address set
11
installation manual
ENC1
SW1 SW7SW2SW3SW4SW5
SW6
ONON
POWER_S
CN20
CN17
CN9
CN15
CN21
CN14
ONONONONON
CN8CN7
CN16
J2
CN5
CN25
J1
CN30
CN11CN6CN4CN55
CN24
CN13
CN3
CN31
main control panel
HP set switch ENC1 definition list
Code
Indoor unit capacity value
0
0
1
2
3
4
5
1800W(0.6HP)
2200W(0.8HP)
2800W(1.0HP)
3600W(1.2HP)
4500W(1.7HP)
5600W(2.0HP)
7100W(2.5HP)