Hawair HAW007 HAW009 HAW018 HAW022
capacities
Total cooling capacity (1) - LS W 1340 1490 1710 2790
Total cooling capacity (1) - MS W 1540 1680 2160 3210
Total cooling capacity (1) W 1710 1870 2400 3570
Total cooling capacity (1) - HS W 1730 2180 2810 3780
Total cooling capacity (1) W 1920 2420 3120 4200
Sensible capacity - LS W 1000 1100 1190 1970
Sensible capacity - MS W 1210 1320 1670 2260
Sensible capacity W 1370 1500 1900 2570
Sensible capacity- HS W 1280 1710 2110 2710
Sensible capacity W 1450 1940 2400 3080
Water pressure drop - LS kPa 14.4 23.3 51.6 50.9
Water pressure drop - MS kPa 16.3 26.1 57.4 58.5
Water pressure drop - HS kPa 18.8 35 66.3 70
Heating capacity (2) - LS W 1780 1840 2130 3350
Heating capacity (2) - MS W 2030 2180 2980 3860
Heating capacity (2) W 2390 2570 3510 4540
Heating capacity (2) - HS W 2150 2710 3500 4710
Heating capacity (2) W 2530 3190 4120 5540
sound levels
Sound power level - LS dB(A) 45 47 53 56
Sound power level - MS dB(A) 49 52 56 59
Sound power level - HS dB(A) 51 57 59 63
Sound pressure level (3) - LS dB(A) 37 39 45 48
Sound pressure level (3) - MS dB(A) 41 44 48 51
Sound pressure level (3) - HS dB(A) 43 49 51 55
NR (3) - LS dB(A) 32 34 40 43
NR (3) - MS dB(A) 36 39 43 46
NR (3) - HS dB(A) 38 44 46 50
ventilation
Number 1 1 1 1
Air flow - LS rpm / m
3
/h 750 / 252 800 / 243 900 / 450 1000 / 531
Air flow - MS rpm / m
3
/h 850 / 288 900 / 369 1000 / 522 1150 / 612
Air flow - HS rpm / m
3
/h 950 / 306 1200 / 459 1150 / 581 1380 / 729
electrical characteristics
Power supply V/Ph/Hz 230V / 1~ / 50Hz
Consumption - LS W 39 45 46.2 51
Consumption - MS W 42 47 52.8 59
Consumption - HS W 59 59 65 71
FCEER - Energy class E E E E
FCCOP - Energy class E E E E
water connection
Type Gas female
Coupling inch 1/2"
dimensions
Length x Width x Height mm 845 x 275 x 180 845 x 275 x 180 940 x 298 x 200 940 x 298 x 200
weight
Weight kg 11 11 13 13
(1) According to Eurovent : Air = 27 °C dry bulb / 19 °C wet bulb - Water = 7 °C / 12 °C.
(2) According to Eurovent : Air = 20 °C, same ow as in cooling mode.
(3) Sound pressure levels considering a room having a volume of 100 m3, with a reverberation time of 0.5 seconds and a distance of 1 meter.