............................................................................ ....................................................... ........................................................
........................................................ ............................................................................... ......................................................................................... .................................................................................. ................................................................................
1 1.1 - - - - - 1.2 Capacity (kW) Model Name 8 12 1.
2 2.1 - - - - - 2.
3 3.
- - - - 3.
4 - Outdoor unit capacity Capacity kW index 8 80 12 120 Sum of capacity indexes of connected indoor units (standard indoor units only) 40 to 104 60 to 156 Maximum number of connected indoor units 4 7 7
5 5.1 1.
5.
°C °C °C °C °C °C °C °C °C °C °C °C °C °C - - - - - - - Outdoor unit capacity Capacity kW index 8 80 12 10 - 120 Sum of capacity indexes of connected indoor units (standard indoor units only)
a) b) - CR Outdoor air temp. (°C DB) - - - Indoor air temp. (°C DB / °C WB) 25.8 / 18.0 TC PI kW kW Indoor air temp. (°C DB / °C WB) 25.8 / 18.0 TC PI kW kW CR Outdoor air temp. (°C DB) 120% 33 10.4 2.48 110% 33 10.2 2.
- - a) b) - CR Outdoor air temp. (°C DB) Indoor air temp. (°C DB / °C WB) 25.8 / 18.0 TC PI kW kW - Indoor air temp. (°C DB / °C WB) 25.8 / 18.0 TC PI kW kW CR Outdoor air temp. (°C DB) 100% 33 11.2 2.76 90% 33 10.1 2.
1 Sale Model Power supply Cooling Heating V-Ph-Hz Capacity kW Input kW EER kW/ KW Capacity kW Input kW COP kW/ kW Model Type 220-240V~50Hz 220-240V~50Hz - - KTM240D57UMT ATF400D64UMT Rotary Rotary Brand Compressor Capacity Btu/h 26349 41957 Input W 2085 3365 Rated current(RLA) A 9.45 6.
wire x 0.75 Ambient temp wire x 0.75 Cooling: -5 55, Heating: -15 27 1. 2. 3. 4.
2 - - 16 - -
- 3 - - - 17
- 4 - - 18
- 1. 2. - 3. 4. - 5.
Mini C Series VRF 50Hz 5 Wiring Diagrams Figure 2 5.1: 80 model wiring diagram 20 Component code Description Component code Description CH1 CH5 Magnetic ring RY1 Relay COMP.
Mini C Series VRF 50Hz Figure 2 5.2: 100/120 model wiring diagram FAN V W U Yellow/Green Orange Blue Part 2 - Outdoor Unit Engineering Data Green Green Yellow/Green ODU power supply Ammeter Centralized IDU controller or communication gateway Please use 3-core shielded cable, and the shield layer must be grounded Component code Description Component code Description BR Rectifier bridge stacking RL1 Relay CH1 CH6 Magnetic ring STF1 Four way valve COMP.
Mini C Series VRF 50Hz 6 Electrical Characteristics Table 2 6.1: Outdoor unit electrical characteristics Power Supply1 Model Min. Max. volts volts 220 240 198 220 240 198 Hz Volts 50Hz 50Hz Compressor OFM MCA2 TOCA3 MFA4 MSC5 RLA6 kW FLA 264 21.25 18.1A 25A Soft start 9.45 0.08 1.0 264 35 29A 40A Soft start 15.5 0.17 1.
Table 2 7.1: Combination (%) (Capacity index) 130% cooling capacity Outdoor temperature Indoor temperature(°C DB/WD) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 5 6.3 0.89 7.5 1.09 8.7 1.17 9.1 1.21 9.5 1.25 9.7 1.36 10.0 1.37 2 6.3 0.89 7.5 1.11 8.7 1.17 9.1 1.22 9.5 1.25 9.7 1.37 10.0 1.38 0 6.3 0.91 7.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) temperature DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 5.8 0.86 6.9 1.04 8.1 1.23 8.6 1.34 9.1 1.40 9.3 1.45 9.5 1.48 -2 5.8 0.87 6.9 1.05 8.1 1.25 8.6 1.35 9.1 1.42 9.3 1.46 9.5 1.49 0 5.8 0.88 6.9 1.06 8.1 1.26 8.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor DB:20.8,WB:14 DB:23.3,WB:16 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 5.3 0.75 6.4 0.94 7.4 1.12 7.9 1.20 8.4 1.29 9.1 1.34 9.3 1.38 -2 5.3 0.77 6.4 0.95 7.4 1.13 7.9 1.21 8.4 1.30 9.1 1.35 9.3 1.39 0 5.3 0.77 6.4 0.95 7.4 1.13 7.9 1.22 8.4 1.31 9.1 1.37 9.3 1.40 2 5.3 0.79 6.4 0.96 7.4 1.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) temperature DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 4.9 0.68 5.8 0.82 6.7 0.98 7.2 1.05 7.7 1.14 8.6 1.30 9.1 1.36 -2 4.9 0.69 5.8 0.83 6.7 0.99 7.2 1.07 7.7 1.16 8.6 1.31 9.1 1.36 0 4.9 0.70 5.8 0.84 6.7 1.00 7.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) temperature DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 4.4 0.61 5.2 0.73 6.1 0.86 6.5 0.94 6.9 0.99 7.7 1.14 8.6 1.31 -2 4.4 0.61 5.2 0.73 6.1 0.87 6.5 0.95 6.9 1.01 7.7 1.15 8.6 1.32 0 4.4 0.62 5.2 0.74 6.1 0.88 6.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) temperature DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 3.9 0.53 4.6 0.63 5.4 0.75 5.8 0.79 6.1 0.86 6.9 0.99 7.6 1.13 -2 3.9 0.54 4.6 0.64 5.4 0.75 5.8 0.81 6.1 0.86 6.9 1.00 7.6 1.14 0 3.9 0.55 4.6 0.65 5.4 0.76 5.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 3.4 0.48 4.1 0.56 4.7 0.63 5.0 0.68 5.4 0.72 6.0 0.83 6.7 0.95 -2 3.4 0.48 4.1 0.56 4.7 0.64 5.0 0.69 5.4 0.74 6.0 0.84 6.7 0.97 0 3.4 0.48 4.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 2.9 0.41 3.5 0.47 4.0 0.55 4.3 0.58 4.6 0.63 5.2 0.71 5.7 0.81 -2 2.9 0.41 3.5 0.48 4.0 0.56 4.3 0.59 4.6 0.64 5.2 0.72 5.7 0.82 0 2.9 0.41 3.
Table 2 7.1: cooling capacity (continued) Indoor temperature(°C DB/WD) Combinatio Outdoor DB:20.8,WB:1 DB:23.3,WB:1 DB:25.8,WB:1 DB:27,WB:1 DB:28.2,WB:2 DB:30.7,WB:2 DB:32,WB:2 temperatur 4 6 8 9 0 2 4 n (%) (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 2.4 0.35 2.9 0.41 3.4 0.47 3.6 0.49 3.8 0.52 4.3 0.59 4.8 0.63 -2 2.4 0.36 2.9 0.42 3.4 0.47 3.6 0.50 3.8 0.53 4.3 0.60 4.8 0.
Table 2 7.3: cooling capacity Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 10.7 1.77 12.8 2.16 14.8 2.31 15.4 2.40 16.1 2.47 16.5 2.69 16.9 2.71 -2 10.7 1.77 12.8 2.20 14.8 2.31 15.4 2.42 16.1 2.47 16.5 2.72 16.9 2.73 0 10.7 1.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 9.9 1.71 11.8 2.07 13.7 2.44 14.6 2.66 15.3 2.78 15.7 2.87 16.0 2.94 -2 9.9 1.72 11.8 2.09 13.7 2.47 14.6 2.68 15.3 2.81 15.7 2.89 16.0 2.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 9.1 1.49 10.8 1.85 12.5 2.21 13.4 2.37 14.3 2.56 15.4 2.65 15.7 2.74 -2 9.1 1.52 10.8 1.88 12.5 2.23 13.4 2.40 14.3 2.58 15.4 2.68 15.7 2.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 8.2 1.36 9.8 1.63 11.4 1.94 12.2 2.08 13.0 2.26 14.6 2.57 15.4 2.69 -2 8.2 1.37 9.8 1.65 11.4 1.97 12.2 2.12 13.0 2.29 14.6 2.60 15.4 2.70 0 8.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 7.4 1.20 8.8 1.44 10.3 1.70 11.0 1.85 11.7 1.97 13.1 2.27 14.6 2.60 -2 7.4 1.21 8.8 1.45 10.3 1.72 11.0 1.88 11.7 1.99 13.1 2.29 14.6 2.62 0 7.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 6.6 1.06 7.8 1.25 9.1 1.48 9.8 1.57 10.4 1.69 11.7 1.96 12.9 2.24 -2 6.6 1.07 7.8 1.27 9.1 1.49 9.8 1.60 10.4 1.71 11.7 1.98 12.9 2.26 0 6.6 1.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 5.8 0.94 6.9 1.11 8.0 1.25 8.5 1.34 9.1 1.43 10.2 1.64 11.3 1.89 -2 5.8 0.95 6.9 1.11 8.0 1.26 8.5 1.37 9.1 1.46 10.2 1.67 11.3 1.91 0 5.8 0.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 4.9 0.80 5.9 0.93 6.8 1.09 7.3 1.16 7.8 1.25 8.8 1.41 9.7 1.61 -2 4.9 0.81 5.9 0.95 6.8 1.11 7.3 1.18 7.8 1.26 8.8 1.43 9.7 1.62 0 4.9 0.82 5.
Table 2 7.3: cooling capacity (continued) Indoor temperature(°C DB/WD) Combination Outdoor (%) DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 temperature (Capacity TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 4.1 0.70 4.9 0.81 5.7 0.93 6.1 0.97 6.5 1.03 7.3 1.17 8.1 1.26 -2 4.1 0.70 4.9 0.82 5.7 0.94 6.1 0.99 6.5 1.04 7.3 1.18 8.1 1.27 0 4.1 0.72 4.
Table 2 7.6: heating capacity Indoor temperature(°C WD) Outdoor Combination (%) (Capacity index) 130% 120% temperature (°C 16.00 18.00 20.00 21.00 22.00 24.00 DB) TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 6.13 1.65 6.11 1.69 6.09 1.76 6.09 1.81 6.06 1.86 6.04 1.88 -11.8 -13 6.22 1.68 6.20 1.72 6.18 1.80 6.18 1.84 6.15 1.89 6.15 1.91 -9.8 -11 6.31 1.70 6.29 1.75 6.27 1.82 6.27 1.
Table 2 7.6: heating capacity (continued) Indoor temperature(°C WD) Outdoor Combination (%) Temperature (°C 100% 18.00 20.00 21.00 22.00 24.00 DB) TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 6.10 1.82 6.08 1.86 6.06 1.90 6.06 1.86 6.06 1.89 6.03 1.94 -11.8 -13 6.19 1.85 6.17 1.89 6.17 1.93 6.15 1.88 6.15 1.92 6.13 1.96 -9.8 -11 6.29 1.85 6.26 1.89 6.26 1.93 6.24 1.91 6.24 1.94 6.
Table 2 7.6: heating capacity (continued) Indoor temperature(°C WD) Outdoor Combination (%) (Capacity index) 90% 80% Temperature (°C 16.00 18.00 20.00 21.00 22.00 24.00 DB) TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 6.06 2.21 6.03 2.23 6.03 2.25 6.01 2.26 5.99 2.17 5.49 1.95 -11.8 -13 6.15 2.21 6.13 2.23 6.13 2.26 6.10 2.23 5.99 2.13 5.49 1.92 -9.8 -11 6.24 2.21 6.24 2.24 6.22 2.
Table 2 7.6: heating capacity (continued) Indoor temperature(°C WD) Outdoor Combination (%) (Capacity index) 70% 60% Temperature (°C 16.00 18.00 20.00 21.00 22.00 24.00 DB) TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 5.81 2.10 5.42 1.93 5.05 1.90 4.85 1.86 4.66 1.83 4.27 1.76 -11.8 -13 5.81 2.05 5.42 1.89 5.05 1.87 4.85 1.83 4.66 1.80 4.27 1.73 -9.8 -11 5.81 2.02 5.42 1.86 5.05 1.
Table 2 7.6: heating capacity (continued) Indoor temperature(°C WD) Outdoor Combination (%) (Capacity index) 50% Temperature (°C 16.00 18.00 20.00 21.00 22.00 24.00 DB) TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 4.16 1.54 3.89 1.46 3.61 1.41 3.45 1.35 3.31 1.31 3.04 1.20 -11.8 -13 4.16 1.49 3.89 1.41 3.61 1.35 3.45 1.30 3.31 1.25 3.04 1.15 -9.8 -11 4.16 1.44 3.89 1.36 3.61 1.29 3.
Table 2 7.8: heating capacity 16.00 Combination (%) (Capacity index) 130% 120% 18.00 20.00 21.00 22.00 24.00 TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 11.92 2.87 11.88 2.95 11.83 3.07 11.83 3.15 11.79 3.23 11.75 3.28 -11.8 -13 12.10 2.92 12.06 3.00 12.01 3.13 12.01 3.21 11.97 3.29 11.97 3.33 -9.8 -11 12.28 2.97 12.23 3.05 12.19 3.16 12.19 3.24 12.19 3.32 12.14 3.33 -9.5 -10 12.
Table 2 7.8: heating capacity (continued) 16.00 Combination (%) (Capacity index) 110% 100% 18.00 20.00 21.00 22.00 24.00 TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 11.87 3.18 11.82 3.25 11.78 3.32 11.78 3.24 11.78 3.30 11.73 3.38 -11.8 -13 12.04 3.22 12.00 3.29 12.00 3.36 11.96 3.27 11.96 3.34 11.91 3.42 -9.8 -11 12.22 3.23 12.18 3.30 12.18 3.37 12.13 3.33 12.13 3.38 12.09 3.
Table 2 7.8: heating capacity (continued) 16.00 Combination (%) (Capacity index) 90% 80% 18.00 20.00 21.00 22.00 24.00 TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 11.78 3.84 11.73 3.88 11.73 3.92 11.69 3.94 11.64 3.78 10.67 3.40 -11.8 -13 11.96 3.85 11.91 3.89 11.91 3.93 11.87 3.89 11.64 3.70 10.67 3.34 -9.8 -11 12.13 3.85 12.13 3.90 12.09 3.93 12.09 3.81 11.64 3.63 10.67 3.28 -9.
Table 2 7.8: heating capacity (continued) 16.00 Combination (%) (Capacity index) 70% 60% 18.00 20.00 21.00 22.00 24.00 TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 11.29 3.65 10.53 3.36 9.82 3.31 9.42 3.24 9.07 3.19 8.31 3.06 -11.8 -13 11.29 3.58 10.53 3.30 9.82 3.25 9.42 3.18 9.07 3.14 8.31 3.01 -9.8 -11 11.29 3.51 10.53 3.23 9.82 3.19 9.42 3.12 9.07 3.08 8.31 2.95 -9.5 -10 11.
Table 2 7.8: heating capacity (continued) 16.00 Combination (%) (Capacity index) 50% 18.00 20.00 21.00 22.00 24.00 TC PI TC PI TC PI TC PI TC PI TC PI °C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW -13.7 -15 8.09 2.69 7.56 2.55 7.02 2.45 6.71 2.35 6.44 2.27 5.91 2.10 -11.8 -13 8.09 2.59 7.56 2.46 7.02 2.35 6.71 2.27 6.44 2.18 5.91 2.00 -9.8 -11 8.09 2.51 7.56 2.37 7.02 2.24 6.71 2.17 6.44 2.09 5.91 1.93 -9.5 -10 8.09 2.42 7.
Figure 2 7.1: 80 model rate of change in cooling capacity Figure 2 7.3: 100 120 model rate of change in cooling capacity Figure 2 7.2: 80 model rate of change in heating capacity Figure 2 7.4: 100 120 model rate of change in heating capacity Notes: 1. The horizontal axis shows equivalent length of piping between farthest indoor unit and first outdoor branch joint; the vertical axis shows the largest level difference between indoor unit and outdoor unit.
Figure 2 8.1: Operating limits Table 2 8.1: Operating limits 5 55 17 32 15 27 0 30 5 55 12 32 Notes: 1. If the unit is running outside the above condition, protective device will start, and even then the units take place abnormality running. 2. These figures base on the operation conditions between indoor units and outdoor units: Equivalent pipe length is 5m, and height difference is 0m. Precaution: 1. The indoor relative humidity should be lower than 80%.
Table 2 9.1: Sound pressure level 54 1.2 56 1.2 Notes: 1. Sound pressure level is measured at a position 1m in front of the unit and Hm above the floor in a semi anechoic chamber. During in situ operation, sound pressure levels may be higher as a result of ambient noise. Figure 2 9.1: Sound pressure level measurement (unit: m) H 1m Figure 2 9.2 80 model octave band level Figure 2 9.
Figure 2 9.4 120 model octave band level Table 2 10.
................................................................................... .......................................................... .................................................................... ............................................................. ........................................................................................ ............................................................................................ ........................................................
- 1 1.1 Notes for installers boxes contain important information which may primarily be of use during field installation, rather than during desk-based system design. 1.2 1.
2 2.1 2.1.1 Placement of outdoor units should take account of the following considerations: Air conditioners should not be exposed to direct radiation from a high-temperature heat source. Air conditioners should not be installed in positions where dust or dirt may affect heat exchangers. nditioners should not be installed in locations where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.
- 2.1.3 Outdoor unit base structure design should take account of the following considerations: prevents Outdoor unit bases should be constructed on solid ground or on structures weight. Bases should be at least 200mm high to provide sufficient access for installation of piping. - typical concrete specification is 1 part cement, 2 parts sand and 6 parts crushed stone . To ensure that all contact points are equally secure, bases should be completely level.
2.1.5 When units are delivered check whether any damage occurred during shipment. If there is damage to the surface or outside of a unit, submit a written report to the shipping company. Check that the model, specifications and quantity of the units delivered are as ordered. Check that all accessories ordered have been included. Retain the Owner's Manual for future reference. 2.1.6 Do not remove any packaging before hoisting.
2.2 2.2.1 Placement of indoor units should take account of the following considerations: Sufficient space for drain piping and for access during servicing and maintenance should be allowed. To ensure a good cooling/heating effect, short-circuit ventilation (where outlet air returns quickly to a unit s air inlet) should be avoided. To prevent excessive noise or vibration during operation, suspension rods or other weight-bearing fixings should typically be able to bear twice the unit s weight.
3 3.1 Refrigerant piping design should take account of the following considerations: The amount of brazing required should be kept to a minimum. On the two inside sides of the first indoor branch joint ( A in Figures 3-3.4 and - ) the system should, as far as possible, be equal in terms of number of units, total capacities and total piping lengths. 3.2 Only seamless phosphorus-deoxidized copper piping that complies with all applicable legislation should be used.
Figure 3-3.
3.4 - - - Figure 3-3.3: Selecting piping diameters - 1. - - - 1. 2. 3. 4.
3.5 Figure 3-3.4: Refrigerant piping selection example - - - - - - - - - - - 3.6 Branch joint design should take account of the following: To ensure even of refrigerant - - 107 - Indoor units N1~ N5 are of capacity 2.8kW, N6 is 2.2kW. Refer to Table 3-3.6.
- Table 3-3.8: Indoor branch joint dimensions (unit: mm) - - 3.7 R410A refrigerant is not flammable in air at temperatures up to 100°C at atmospheric pressure and is generally considered a safe substance to use in air conditioning systems. Nevertheless, precautions should be taken to avoid danger to life in the unlikely event of a major refrigerant leakage. Precautions should be taken in accordance with all applicable legislation.
- - 109
4 4.1 4.1.1 Pipe flushing should be performed once the brazed connections have been completed with the exception of the final connections to the indoor units. That is, flushing should be performed once the outdoor unit have been connected but before the indoor units are connected. 4.1.2 Vacuum drying4 Pipe manipulation5 techniques Gas tightness test6 1. 2. 3. 4. 5. 6.
4.2 4.2.1 Ensure that piping does not get bent or deformed during delivery or whilst stored. On construction sites store piping in a designated location. To prevent dust or moisture entering, piping should be kept sealed whilst in storage and until it is about to be connected. If piping is to be used soon, seal the openings with plugs or adhesive tape. If piping is to be stored for a long time, charge the piping with nitrogen at 0.2-0.5MPa and seal the openings by brazing.
4.3.3 Insert the expanding head of the pipe expander into the pipe. After completing pipe expansion, rotate the copper pipe a few degrees to rectify the straight line mark left by the expanding head. Ensure that the section of piping is smooth and even. Remove any burrs that remain after cutting. - 4.3.4 Flared joints should be used where a screw thread connection is required. Before flaring 1/2H (half hard) piping, anneal the end of the pipe to be flared.
4.3.5 - - - - 4.4 When the air conditioner is running, the refrigerant piping will deform (shrink, expand, droop). To avoid damage to piping, hangers or supports should be spaced as per the criteria in the Table 3-4.2. In general, the gas and liquid pipes should be suspended in parallel and the interval between support points should be selected according to the diameter of the gas pipe. Table 3-4.
4.5 Warning Never flow oxygen through piping as doing so aids oxidation and could easily lead to explosion and as such is extremely dangerous. Take appropriate safety precautions such as having a fire extinguisher to hand whilst brazing. Flowing nitrogen during brazing Use a pressure reducing valve to flow nitrogen through copper piping at 0.02-0.03MPa during brazing.
box continued from previous page Piping orientation during brazing Brazing should be conducted downwards or horizontally to avoid filler leakage. - Piping overlap during brazing - - - - 1.
4.6 - Figure 3-4.8: Branch joint orientation - To ensure even of refrigerant 4.7 4.7.1 To remove dust, other particles and moisture, which could cause compressor malfunction if not flushed out before the system is run, the refrigerant piping should be flushed using nitrogen. As described in Part 3, 4.1.1 Installation procedure , pipe flushing should be performed once the piping connections have been completed with the exception of the final connections to the indoor units.
4.7.2 Only use nitrogen for flushing. Using carbon dioxide risks leaving condensation in the piping. Procedure 1. 2. 3. 4. - - 5. 6. 7. a) b) c) 8. 9. - - 1.
4.8 4.8.1 faults 4.8.
4.8.3 1. 2. 3. 4. a) b) c) d) 4.9 4.9.
4.9.2 During vacuum drying, a vacuum pump is used to lower the pressure in the piping to the extent that any moisture present evaporates. At 5mmHg (755mmHg below typical atmospheric pressure) the boiling point of water is 0°C. Therefore a vacuum pump capable of maintaining a pressure of -756mmHg or lower should be used. Using a vacuum pump with a discharge in excess of 4L/s and a precision level of 0.02mmHg is recommended.
5 5.1 Drain piping design should take account of the following considerations: Indoor unit condensate drain piping needs to be of sufficient diameter to carry the volume of condensate produced at the indoor units and installed at a slope sufficient to allow drainage. Discharge as close as possible to the indoor units is usually preferable.
installed too close to indoor unit lift pumps. - Air conditioner drain piping should be installed separately from waste, rainwater and other drain piping and should not come into direct contact with the ground. Drain piping diameter should ing connection. To allow inspection and maintenance, the piping clamps shipped with units should be used to attach drain piping to indoor units adhesive should not be used. Thermal insulation should be added to drain piping to prevent condensation forming.
PVC piping PVC25 PVC32 PVC40 PVC50 PVC63 PVC75 PVC90 Nominal diameter (mm) 25 32 40 50 63 75 90 Capacity (L/h) 220 410 730 1440 2760 5710 8280 Remarks Branch piping only Branch or main piping 5.4 Drain piping for units with lift pumps should take account of the following additional considerations: A downward sloping section should immediately follow the vertically rising section adjacent to the unit, otherwise a water pump error will occur. Refer to Figure 3-5.7.
5.6 Once installation of a drainage piping system is compete, water tightness and water flow tests should be performed. Water tightness test Fill the piping with water and test for leakages over a 24-hour period. Water flow test (natural drainage test) Slowly fill the drainage pan of each indoor unit with at least 600ml of water through the inspection port and check that the water is discharged through the outlet of the drain piping.
6 6.1 6.1.1 During operation, the temperature of the refrigerant piping varies. Insulation is required to ensure unit performance and compressor lifespan. During cooling, the gas pipe temperature can be very low. Insulation prevents condensation forming on the piping. During heating, the gas pipe temperature can rise to as high as 100°C. Insulation serves as necessary protection from burns. 6.1.
Figure 3-6.1: Installation of joint insulation (unit: mm) 6.2 Use rubber/plastic insulating tube with a B1 fire resistance rating. The insulation should typically be in excess of 10mm thick. For drain piping installed inside a wall, insulation is not required. Use suitable adhesive to seal seams and joints in the insulation and then bind with cloth reinforced tape of width not less than 50mm. Ensure tape is fixed firmly to avoid condensation.
7 7.1 - - 6.35 9.53 12.7 15.9 7.2 Only charge refrigerant after performing a gas tightness test and vacuum drying. Never charge more refrigerant than required as doing so can lead to liquid hammering. Only use refrigerant R410A - charging with an unsuitable substance may cause explosions or accidents. Use tools and equipment designed for use with R410A to ensure required pressure resistance and to prevent foreign materials from entering the system.
box continued from previous page - - - Pressure gauge 128
8 8.1 - Caution All installation and wiring must be carried out by and in accordance with all applicable legislation. Electrical systems should be grounded in accordance with all applicable legislation. Overcurrent circuit breakers and residual-current circuit breakers (ground fault circuit interrupters) should be used in accordance with all applicable legislation.
- - - 8.3 r communication wiring. Using other types of cable can lead to interference and malfunction. Indoor communication wiring: The P Q E communication wires should be connected one unit after another in a daisy chain from the outdoor unit to the final indoor unit. At the final indoor unit, a 120 resistor should be connected between the P and Q terminals.
Mini C Series VRF 50Hz Notes for installers The communication wires should be connected to the outdoor unit terminals indicated in Figure 3 8.3 and Table 3 8.2. Caution Communication wiring has polarity. Care should be taken to connect the poles correctly. Only the dedicated meter of can be used on the unit. For the wiring method of the meter, please consult Mideas professional service personnel. The arrangement of OAE, XYE and PQE depends on the unit. Figure 3 8.
8.
9 9.1 Do not install outdoor units where they could be directly exposed to sea air. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. Outdoor units installed in seaside locations should be placed such as to avoid direct exposure to the sea air and additional anticorrosion treatment options should be selected, otherwise the service life of the outdoor units will be seriously affected.
10 10.1 - ach independent refrigeration system (i.e. each system of one outdoor unit and its connected indoor units) should be given a test run independently, before the multiple systems that make up a project are run simultaneously. 10.2 - 1. All indoor and outdoor refrigeration piping and communication wiring has been connected to the correct refrigeration system and the system to which each indoor and outdoor unit belongs is clearly marked on each unit or recorded in some other suitable place. 2.
the CHECK button on the outdoor unit s main PCB and complete the cooling mode columns of one Sheet D and one Sheet E of the system commissioning report for the outdoor unit. c) Run the system in heating mode with the following settings: temperature 30°C; fan speed high.
11 136
SYSTEM INFORMATION Project name and location Customer company System name Installation company Commissioning date Agent company Outdoor ambient temp. Commissioning engineer Model Serial no. Power supply (V) Outdoor unit information INDOOR UNITS (S Room Address Set temp. Inlet temp. Outlet temp. Drainage Abnormal noise/ (°C) (°C) (°C) OK? vibration? - no.
SYSTEM INFORMATION Project name and location Customer company System name Installation company Commissioning date Agent company Outdoor ambient temp. Commissioning engineer Model Serial no. Power supply (V) Outdoor unit information INDOOR UNITS (S Room no. 138 Model Address Set temp. Inlet temp. Outlet temp.
Project name and location System name RECORD OF ISSUES SEEN DURING COMMISSIONING No. Description of observed issue Suspected cause Troubleshooting undertaken Serial no.
Project name and location System name ------------------------- -- - 140