IOM SYSHP MINI SPLIT 06 16 ODU

Table Of Contents
09
6.1 Dimensions
6 INSTALLATION PRECAUTIONS
Model A B C D E F G H I
4/6kW
8/10/12/14/16kW
1008
1118
375
456
426
523
663
656
134
191
110
110
170
170
712
865
160
230
4/6 kW (unit: mm)
8/10/12/14/16 kW (unit: mm)
Check the strength and level of the installation ground so that the unit may not cause any vibrations or noise during the
operation.
In accordance with the foundation drawing in the figure, fix the unit securely by means of foundation bolts. (Prepare four sets
each of Φ10 Expansion bolts, nuts and washers which are readily available in the market.)
Screw in the foundation bolts until their length is 20 mm from the foundation surface.
6.2 Installation requirements
(unit: mm)
Concrete
basement
h100mm
Rubber
shocking
proof mat
100
80
Φ10 Expansion
bolt
Solid
ground
or roofing
H
B
Fig: 6-3
Fig: 6-1
Fig: 6-2
Fig: 6-4
F
G
I
A
B
C
E D
C
A
E D
H
F
G
I
Please remove the noise insulation cover of the compressor first.
Please make sure the transportation support had be removed.
It will cause heat pump abnormal vibration and noise if running with transportation support for compressor installed.
Please wear gloves when doing the above operation to prevent hand scratches.
Please restore the noise insulation cover after removing the transportation support.