Installation and owner’s manual SYSHP MINI SPLIT HYDRO 06-16 R32 Split Heat Pump Indoor unit Original instructions Thank you very much for purchasing our product. Before use, please carefully read this manual and keep it for future reference.
CONTENTS 1 SAFETY PRECAUTIONS 02 2 BEFORE INSTALLATION 08 3 INSTALLATION SITE 08 4 INSTALLATION PRECAUTIONS 10 4.1 4.2 4.3 4.4 4.5 Dimensions Installation requirements Servicing space requirements Mounting the indoor unit Refrigerant pipe connection 10 10 11 12 12 5 GENERAL INTRODUCTION 13 6 ACCESSORIES 14 7 TYPICAL APPLICATIONS 15 7.1 Application 1 7.2 Application 2 8 OVERVIEW OF THE UNIT 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.
11 MAINTENANCE AND SERVICE 57 12 TROUBLE SHOOTING 58 12.1 12.2 12.3 12.
Basic CN5 CN21 CN8 CN28 CN24 CN16 CN6 CN13 CN15 CN18 CN29 CN25 CN42 CN40 S1 S2 S4 CN4 CN35 EVU CN22 SG S3 CN31 CL COM HT DIS1 CN41 CN1 CN36 CN17 2 3 14 4 15 5 16 6 17 7 18 CN11 8 19 9 20 10 21 11 22 12 23 24 25 29 26 27 30 CN7 28 31 1 32 6 2 3 7 5 4 8 CN30 9 10 Electric Control Box CN5 CN21 CN8 CN28 CN24 CN16 CN6 CN13 CN15 CN18 CN29 CN25 CN42 CN40 S1 DIS1 S2 CN41 Terminal TerminalBlock Block S3 CN31 CL COM HT 13 S4 CN4 CN35 EVU CN22
1 SAFETY PRECAUTIONS The precautions listed here are divided into the following types.They are quite important, so be sure to follow them carefully.Read these instructions carefully before installation. Keep this manual in a handy for future preference. Meanings of DANGER, WARNING, CAUTION and NOTE symbols. DANGER Indicates an imminently hazardous situation which if not avoided, will result in death or serious injury.
Special requirements for R32 WARNING Do NOT have refrigerant leakage and open flame. Be aware that the R32 refrigerant does NOT contain an odour. WARNING The appliance shall be stored so as to prevent mechanical damage and in a well-ventilated room without continuously operating ignition sources (example:open flames,an operating gas appliance) and have a room size as specified below. NOTE Do NOT re-use joints which have been used already.
Input from installer: start 2 ▪ Area of adjacent room B (AroomB) (m ) Use table 2 in page5 to calculate the Input from installer: total ▪ Total refrigerant charge (mc)(kg) minimum floor 2 (A mintotal)(m )required 2 ▪ Area of room A (AroomA)(m ) for the area total refrigerant charge (mc) ≥ Use table 1 in page5 to calculate the maximum refrigerant charge(mmax)(kg) Amin total≤AroomA+AroomB? no allowed for room A.
Table 1-Maximum refrigerant charge allowed in a room:indoor unit Aroom(m2) Maximum refrigerant charge in a room(mmax)(kg) Aroom(m2) Maximum refrigerant charge in a room(mmax)(kg) H=1800mm H=1800mm 1.02 1 4 2.05 2 1.45 5 2.29 3 1.77 6 2.51 NOTE For wall mounted models, the value of “Installation height (H)” is considered 1800 mm to comply to IEC 60335-2-40:2013 A1 2016 Clause GG2. For intermediate Aroom values(i.e.
DANGER Before touching electric terminal parts, turn off power switch. When service panels are removed, live parts can be easily touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed. Do not touch water pipes during and immediately after operation as the pipes may be hot and could burn your hands. To avoid injury, give the piping time to return to normal temperature or be sure to wear protective gloves.
CAUTION Install the power wire at least 3 feet (1 meter) away from televisions or radios to prevent interference or noise. (Depending on the radio waves, a distance of 3 feet (1 meter) may not be sufficient to eliminate the noise.) Do not wash the unit. This may cause electric shocks or fire. The appliance must be installed in accordance with national wiring regulations.
2 BEFORE INSTALLATION Before installation Be sure to confirm the model name and the serial number of the unit. CAUTION Frequency of Refrigerant Leakage Checks - For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more,but of less than 50 tonnes of CO2 equivalent,at least every 12 months, or where a leakage detection system is installed, at least every 24 months.
CAUTION The indoor unit should be installed in an indoor water proof place, or the safety of the unit and the operator cannot be ensured. The indoor unit is to be wall mounted in an indoor location that meets the following requirements: The installation location is frost-free. The space around the unit is adequate for serving, see figure 4-4. The space around the unit allows for sufficient air circulation. There is a provision for condensate drain and pressure relief valve blow-off.
4 INSTALLATION PRECAUTIONS 4.1 Dimensions Dimensions of the wall bracket: 158 158 40 3× 12 unit:mm Dimensions of the unit: Fig.4-1 50 40 151 49 82 158 158 721 824 790 68 149 53 60 216 152 5 4 1 23 Fig.4-2 unit:mm NAME NO. 1 Refrigerant gas connection connection5/8"-14UNF 5/8"-14UNF 2 Refrigerant liquid connection 1/4"(60) or 3/8"(100/160) -14UNF 3 Drainage 4 Water Inlet R1” 5 Water Outlet R1” 25 4.2 Installation requirements The indoor unit is packed in a box.
WARNING Do not grasp the control box or pipe to lift the unit! CN8 CN28 CN5 CN21 CN24 CN16 CN6 CN13 CN15 CN18 CN29 CN25 CN42 CN40 S1 CN41 S4 CN4 CN35 EVU CN22 SG S3 CN31 CL COM HT DIS1 S2 CN1 1 13 CN17 2 3 14 4 15 5 16 6 17 7 18 CN11 8 19 9 20 10 21 11 22 12 23 24 25 26 29 27 30 28 31 CN7 1 32 6 2 3 7 5 4 8 9 10 CN14 CN19 CN36 CN2 CN30 Fig.4-3 ≥200 4.3 Servicing space requirements ≥350 ≥500 ≥1150 ≥300 unit:mm 11 Fig.
4.4 Mounting the indoor unit Fix the wall mounting bracket to the wall using appropriate plugs and screws. Make sure the wall mounting bracket is horizontal level. Pay special attention to prevent overflow of the drain pan. Hang the indoor unit on the wall mounting bracket. two persons two persons two persons 1/4 1/4 5/8 5/8 Fig.4-5 4.5 Refrigerant pipe connection Outer diam. 6.35 9.52 16 Handle "A" Align the center of the pipes.
5 GENERAL INTRODUCTION These units are used for both heating and cooling applications and domestic hot water tanks.They can be combined with fan coil units, floor heating applications, low temperature high efficiency radiators, domestic hot water tanks (field supply) and solar kits (field supply). A wired controller is supplied with the unit . If you choose the built-in backup heater unit, the backup heater can increase the heating capacity during cold outdoor temperatures.
In cooling mode, the water flowing temperature (TW_out) range in different outdoor temperature (T4) is list below: 6 ACCESSORIES Installation Fittings Name Operation range by heat pump with possible limitation and protection.
7 TYPICAL APPLICATIONS The application examples given below are for illustration only. 7.1 Application 1 9.2 Indoor 9.1 2 2.2 2.4 2.9 2 2.5 23 24 2.6 Outdoor 3 F AHS 2.11 2.10 FHL1 2.1 2.1 2.3 2.8 2.7 17 FHL2 FHLn 13 17 15 16 1 12 4 5.1 21 5.3 19 6 9 14 5 18 11 5.2 19 10 16 14.2 14.1 16 Modbus 14.
Space heating The ON/OFF signal and operation mode and temperature setting are set on the user interface. P_o(6) keeps running as long as the unit is ON for space heating, SV1(4) keeps OFF. Domestic water heating The ON/OFF signal and target tank water temperature (T5S) are set on the user interface. P_o(6) stops running as long as the unit is ON for domestic water heating, SV1(4) keeps ON. AHS (auxiliary heat source) control The AHS function is set on the indoor unit (See 9.
7.2 Application 2 ROOM THERMOSTAT Control for Space heating or cooling need to be set on the user interface. It can be set in three ways: MODE SET/ONE ZONE/DOUBLE ZONE. The indoor unit can be connected to a high voltage room thermostat and a low voltage room thermostat. A thermostat transfer board can also be connected. Another six thermostats can be connected to the thermostat transfer board. Please refer to 8.8.6/6) “For room thermostat” for wiring. (see 9.5.6 "ROOM THERMOSTAT") 7.2.
7.2.2 Mode set control Indoor 2 RT2 RT3 2.4 2.2 2.9 RT4 2.5 25 RT5 2.6 Outdoor 3 24 RT6 7 RT8 FCU1 FCU2 23 FCUn M F 2.11 23 RT7 2.1 2.1 2.3 2.10 2.8 RT1 2.7 17 13 17 15 FHL1 FHL2 5.1 1 6 19 18 5 5.
7.2.3 Double zone control Indoor RT2 2 2.2 RT4 2.4 2.9 25 2.5 RT5 2.6 Outdoor RT7 3 2.10 RT6 RAD.1 RT8 F 2.11 RT3 2.1 2.1 2.3 2.8 RAD.2 RT1 2.7 13 17 17 ZONE1 RAD.n 15 5.1 1 19 18 6 8 23 Tw2 ZONE2 8.1 8.2 5 5.
The floor heating loops require a lower water temperature in heating mode compared to radiators or fan coil units. To achieve these two set points, a mixing station is used to adapt the water temperature according to requirements of the floor heating loops. The radiators are directly connected to the unit water circuit and the floor heating loops are after the mixing station. The mixing station is controlled by the unit.
8 OVERVIEW OF THE UNIT 8.1 Disassembling the unit The indoor unit cover can be removed by removing the 2 screws and unhitching the cover. CAUTION Make sure to fix the cover with the screws and nylon washers when installing the cover (screws are delivered as accessory) .Parts inside the unit can be hot. To gain access to the control box components – e.g. to connect the field wiring – the control box service panel can be removed. Thereto, loosen the front screws and unhitch the control box service panel.
1 8 1 14.2 5.3 5.1 10 14.1 2 8 5.3 14.2 5.1 15 14.1 2 10 5.4 7 5.2 9 13 3 11 4 5.4 7 9 13 11 12 3 6 4 12 6 Basic Customized Assembly unit Code 5.2 Explaination Remaining air in the water circuit will be automatically removed via the automatic air purge valve.
8.
8.3.
8.4 Refrigerant pipework For all guidelines, instructions and specifications regarding refrigerant pipework between the indoor unit and outdoor unit, please refer to "Installation and owner’s manual (M-thermal split outdoor unit)". CAUTION When connecting the refrigerant pipes, always use two wrenches/spanners for tightening or loosening nuts! Failure to do so can result in damaged piping connections and leaks. NOTE The appliance contains fluorinated greenhouse gases.
8.5.1 Check the water circuit The unit is equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by a licensed technician and must comply with local laws and regulations. The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping. Example: Indoor 2 2.2 2.4 2.9 2.5 2.6 F Outdoor 2.11 2.10 3 2.1 2.1 2.3 2.8 2.7 17 13 17 15 5.1 1 23 6 24 19 5 18 19 5.
Before continuing installation of the unit, check the following: The maximum water pressure ≤ 3 bar. The maximum water temperature ≤ 70°C according to safety device setting. Always use materials that are compatible with the water used in the system and with the materials used in the unit. Ensure that components installed in the field piping can withstand the water pressure and temperature.
8.5.3 Water circuit connection Water connections must be made correctly in accordance with labels on the indoor unit, with respect to the water inlet and water outlet. CAUTION Be careful not to deform the unit’s piping by using excessive force when connecting the piping. Deforming the piping can cause the unit to malfunction. If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit: Use clean pipes only.
Water may enter into the flow switch and cannot be drained out and may freeze when the temperature is low enough. The flow switch should be removed and dried, then can be reinstalled in the unit. 1 2 There need drying NOTE 1.Counterclockwise rotation, remove the flow switch. 2.Drying the flow switch completely. 8.6 Filling water Connect the water supply to the filling valves and open the valve. Make sure all the automatic air purge valves are open (at least 2 turns).
8.7 Water piping insulation The complete water circuit including all piping, water piping must be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity as well as prevention of freezing of the outside water piping during winter. The insulation material should at least of B1 fire resistance rating and complies with all applicable legislation. The thickness of the sealing materials must be at least 13 mm with thermal conductivity 0.
8 3 4 1 2 5 6 7 9 10 11 12 � C 1ON SL1 SL2 H � 1OFF2ON 2OFF P_c P_o � P_d � � P_s 25 26 27 28 ����� HT ���� R2 AHS1 AHS2 29 30 31 32 ��N R1 DFT2 DFT1 13 14 15 16 17 18 19 20 21 22 23 24 TBH IBH1 L1 N N N 3ON 3OFF N N N N CN11 1 A 6 2 B 3 X 4 Y 5 E 6 7 8 9 10 E H1 H2 P Q CN7 CN30 3 9 5 8 1 7 B 4 M 25 T H D M F 2 CC 2.
Description Item AC/DC Required number of conductors Maximum running current 1 Solar energy kit signal cable AC 2 200mA 2 User interface cable AC 5 200mA 3 Room thermostat cable AC 2 200mA(a) 4 Solar pump control cable AC 2 200mA(a) 5 Outside circulation pump control cable AC 2 200mA(a) 6 DHW pump control cable AC 2 200mA(a) 7 SV2: 3-way valve control cable AC 3 200mA(a) 8 SV1: 3-way valve control cable AC 3 200mA(a) 9 Booster heater control cable AC 2 200mA(
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent appropriate tightening. Over-tightening the terminal screws can damage the screws. Attach a ground fault circuit interrupter and fuse to the power supply line. In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so that outside force cannot affect the terminals. 8.8.4 Safety device requirements 1.
XT1 XT1 XT1 FUSE FUSE FUSE L1 L2 L3 LPS LPS LPS L N L N L1 L2 L3 N INDOOR UNIT POWER SUPPLY 1-phase 3KW backup heater INDOOR UNIT POWER SUPPLY (Basic) Unit 2 Wiring size(mm) N Basic 3KW-1PH 3KW-3PH 1.5 4.0 2.5 INDOOR UNIT POWER SUPPLY 3-phase 3/6/9KW backup heater 6KW-3PH 9KW-3PH 4.0 4.0 Stated values are maximum values (see electrical data for exact values).
8.8.
1) For solar energy input signal 1 2 3 4 5 6 7 8 9 10 � 12 � � 11 13 14 15 16 17 18 19 20 21 22 23 24 ���� 1 2 3 4 5 30 CN7 CN11 Type 1 1 2 26 � � � 6 7 8 9 10 CN30 220-240VAC 0.2 Maximum running current(A) Wiring size(mm ) 0.
4) For remote shut down: CN21 CN8 CN28 CN5 CN24 CN16 CN6 CN32 CN13 CN15 CN18 CN29 CN25 CN40 � � 25 26 27 28 1 2 3 4 5 29 30 31 32 17 6 7 8 9 10 CN7 S2 CN41 S3 CN30 S4 CN31 CN4 CN22 CN35 M1 M2 EVU CN11 S1 DIS1 CL COM HT � SG 7 8 CN1 CN36 SW9 CN2 1 13 CN17 2 3 14 4 15 5 16 6 17 8 7 18 19 9 20 10 21 11 22 25 12 23 24 26 29 30 CN11 7 27 28 31 1 32 6 2 3 7 CN7 CN30 8 17 CLOSE: SHUT DOWN 5) For Pumpc and DHW pipe pump : SV2 9 � 25 26 27 28 � 2
CN5 Voltage 220-240VAC Maximum running current(A) 0.2 Wiring size(mm ) 0.75 2 Control port signal type 3 4 ���� Type 2 25 26 27 28 � � 29 30 31 32 15 CN11 1 2 3 4 5 6 7 8 9 10 CN7 CN30 S1 a) Procedure Connect the cable to the appropriate terminals as shown in the picture. Fix the cable reliably. CN4 6) For room thermostat: Room thermostat type 1(High voltage): "POWER IN" provide the working voltage to the RT, doesn’t provide the voltage to the RT connector directly.
Room thermostat type2 (Low voltage): CN21 CN32 CN13 CN32 CN29 CN15 CN18 CN29 CN25 CN42 CN40 CN41 CN31 S4 S4 CN4 CN22 13 5 4 14 15 6 16 17 8 7 18 9 19 10 20 21 11 22 25 12 26 27 29 23 24 30 CN11 HT 28 31 1 32 2 6 3 7 5 4 8 10 9 CN7 CN30 COM CL CN36 1 CN17 2 13 3 14 5 4 15 16 6 17 8 7 18 19 9 20 10 21 11 22 12 23 24 25 Method A 29 CN8 CN24 CN16 CN6 CN13 CN29 CN15 CN18 CN25 S1 S2 S4 CN4 CN35 EVU CN22 SG S3 CN31 CL COM HT
C.2 When unit detect voltage is 12VDC between CL and COM, zone2 turn on according to climate temp curve. When unit detect voltage is 0V between CL and COM, zone2 turn off. 8) For additional heat source control: C.3 When HT-COM and CL-COM are detected as 0VDC, unit turn off. C.4 when HT-COM and CL-COM are detected as 12VDC, both zone1 and zone2 turn on.
Voltage 220-240VAC Maximum running current(A) 0.2 Wiring size(mm ) 0.
1. when EVU signal is on, the unit operate as below: DHW mode turn on, the setting temperature will be changed to 70℃ automatically, and the TBH operate as below:T5<69. the TBH is on, T5 ≥ 70, the TBH is off. The unit operate in cooling/heating mode 2. When EVU signal is off, and SG signal is on, the unit operate normally. 3. When EVU signal is off, SG signal is off, the DHW mode is off, and the TBH is invalid, disinfect function is invalid.
9.2 Initial start-up at low outdoor ambient temperature During initial start-up and when water temperature is low, it is important that the water is heated gradually. Failure to do so may result in concrete floors cracking due to rapid temperature change. Please contact the responsible cast concrete building contractor for further details. To do so, the lowest water flow set temperature can be decreased to a value between 25°C and 35°C by adjusting the FOR SERVICEMAN. Refer to SPECIAL FUNCTION. 9.
9.4 Setting the pump The pump is contolled via a digital low-voltage pulse-width modulation signal which means that the speed of rotation depends on the input signal.The speed changes as a function of the input profile. The relationships between the head and the water flow rated,the PMW Return and the water flow rated are shown in the graph below.
Failure diagnosis at first installation If nothing is displayed on the user interface, it is necessary to check for any of the following abnormalities before diagnosing possible error codes. -Disconnection or wiring error (between power supply and unit and between unit and user interface). -The fuse on the PCB may be broken. If the user interface shows "E8" or "E0" as an error code, there is a possibility that there is air in the system, or the water level in the system is less than the required minimum.
About FOR SERVICEMAN FOR SERVICEMAN "FOR SERVICEMAN" is designed for the installer to set the parameters. Setting the composition of equipment. Setting the parameters. OK ENTER How to go to FOR SERVICEMAN Go to MENU> FOR SERVICEMAN. Press OK: Press ▼ ▲ to scroll and use "OK" to enter submenu. FOR SERVICEMAN 9.5.1 DHW MODE SETTING Please input the password: DHW = domestic hot water Go to MENU> FOR SERVICEMAN> 1.DHW MODE SETTING. Press OK.
9.5.3 HEAT MODE SETTING 4/5 1 DHW MODE SETTING 1.16 t_DI_MAX 1.17 t_DHWHP_RESTRICT 1.18 t_DHWHP_MAX 1.19 DHWPUMP TIME RUN 1.20 PUMP RUNNING TIME Go to MENU>FOR SERVICEMAN> 3.HEAT MODE SETTING. Press OK. The following pages will be displayed: 210 MIN 30 MIN 120 MIN YES 5 MIN 3 HEAT MODE SETTING 3.1 HEAT MODE 3.2 t_T4_FRESH_H 3.3 T4HMAX 3.4 T4HMIN 3.5 dT1SH ADJUST 1/3 YES 2.0HRS 16°C -15°C 5°C ADJUST 1 DHW MODE SETTING 5/5 1.21 DHW PUMP DI RUN NON 3 HEAT MODE SETTING 3.6 dTSH 3.7 t_INTERVAL_H 3.
9.5.5 TEMP. TYPE SETTING About TEMP. TYPE SETTING ◄ ◄ The TEMP. TYPE SETTING is used for selecting whether the water flow temperature or room temperature is used to control the ON/OFF of the heat pump. 2 When ROOM TEMP. is enabled, the target water flow temperature will be calculated from climate-related curves . Go to MENU> FOR SERVICEMAN> 5.TEMP. TYPE SETTING. Press OK. The following page will be displayed: 5 TEMP. TYPE SETTING 5.1 WATER FLOW TEMP. 5.2 ROOM TEMP. 5.
9.5.7 Other HEATING SOURCE In this case, the setting value of zone 1 is T1S,the setting value of zone 2 is T1S2. The OTHER HEATING SOURCE is used to set the parameters of the backup heater, additional heating sources and solar energy kit. If you set DOUBLE ZONE and ROOM TEMP. to YES, meanwhile set WATER FLOW TEMP. to YES or NON,the following page will be displayed. Go to MENU> FOR SERVICEMAN> 7.OTHER HEATING SOURCE, Press OK. The following page will be dispayed: ◄ ◄ 7 OTHER HEATING SOURCE 1/2 7.
9 SERVICE CALL PHONE NO. *************** MOBILE NO. ****************** OK CONFIRM If YES is selected, the following pages will be displayed: 11 TEST RUN 11.1 POINT CHECK 11.2 AIR PURGE 11.3 CIRCULATED PUMP RUNNING 11.4 COOL MODE RUNNING 11.5 HEAT MODE RUNNING ADJUST The number displayed on the user interface is the phone number of your local dealer. OK ENTER 9.5.10 RESTORE FACTORY SETTINGS 11 TEST RUN 11.
When in air purge mode, SV1 will open, SV2 will close. 60s later the pump in the unit (PUMPI) will operate for 10min during which the flow switch will not work. After the pump stops, the SV1 will close and the SV2 will open. 60s later both the PUMPI and PUMPO will operate until the next command is received. During HEAT MODE test running, the default target outlet water temperature is 35°C. The IBH (internal backup heater) will turn on after the compressor runs for 10 min.
Go to MENU> FOR SERVICEMAN> 12.SPECIAL FUNCTION. During preheating for floor, all the buttons except OK are invalid. If you want to turn off the preheating for floor, please press OK. Before floor heating, if a large amount of water remains on the floor, the floor may be warped or even rupture during floor heating operation, in order to protect the floor, floor drying is necessary, during which the temperature of the floor should be increased gradually. The following page will be displayed: 12.
The AUTO RESTART function reapplies the user interface settings at the time of the power supply failure. If this function is disabled, when power returns after a power supply failure, the unit won’t auto restart. During floor drying, all the buttons except OK are invalid. When the heat pump malfunctions, the floor drying mode will turn off when the backup heater and additional heating source is unavailable. If you want to turn off floor drying up, please press OK. The following page will be displayed: 9.
9.5.16 Setting parameters The parameters related to this chapter are shown in the table below. Order number Code State Default Minumum Maximum Setting interval Unit 1.1 DHW MODE Enable or disable the DHW mode:0=NON,1=YES 1 0 1 1 / 1.2 DISINFECT Enable or disable the disinfect mode:0=NON,1=YES 1 0 1 1 / 1.3 DHW PRIORITY Enable or disable the DHW priority mode:0=NON,1=YES 1 0 1 1 / 1.4 DHW PUMP Enable or disable the DHW pump mode:0=NON,1=YES 0 0 1 1 / 1.
3.1 HEAT MODE Enable or disable the heating mode The refresh time of climate related curves for heating mode The maximum ambient operating temperature for heating mode The minimum ambient operating temperature for heating mode 1 0 1 1 / 0.5 0.5 6 0.5 hours 25 20 35 1 ℃ -15 -25 15 1 ℃ 1 ℃ 3.2 t_T4_FRESH_H 3.3 T4HMAX 3.4 T4HMIN 3.5 dT1SH The temperature difference for starting the unit (T1) 5 2 10 3.
12.4 t_DRYUP 12.5 t_HIGHPEAK 12.6 t_DRYD 12.7 T_DRYPEAK 12.8 12.9 13.1 13.2 14.1 15.1 15.2 15.3 15.4 15.5 15.6 15.7 15.8 15.9 15.
10 TEST RUN AND FINAL CHECKS The following checks must be performed at least once a year by qualified person. Water pressure Check the water pressure, if it is below 1 bar,fill water to the system. The installer is obliged to verify correct operation of unit after installation. 10.1 Final checks Before switching recommendations: on the unit, read Water filter Clean the water filter.
12 TROUBLE SHOOTING This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit. This troubleshooting and related corrective actions may only be carried out by your local technician. 12.1 General guidelines Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.
Symptom 3: Pump is making noise (cavitation) POSSIBLE CAUSES CORRECTIVE ACTION There is air in the system. Purge air. Water pressure at pump inlet is too low. • Check on the manometer that there is sufficient water pressure. The water pressure must be > 1 bar (water is cold). • Check that the manometer is not broken. • Check that the expansion vessel is not broken. • Check that the setting of the pre- pressure of the expansion vessel is correct (refer to "8.5.
Symptom 8: DHW mode can’t change to Heat mode immediately POSSIBLE CAUSES CORRECTIVE ACTION Heat exchanger for space heating not big enough • Set "t_DHWHP_MAX" to minimum value, the suggested value is 60min. • If circulating pump out of unit is not controlled by unit, try to connect it to the unit. • Add 3-way valve at the inlet of fan coil to ensure enough water flow.
OPERATION PARAMETER FAN SPEED #00 600R/MIN IDU TARGET FREQUENCY 46Hz FREQUENCY LIMITED TYPE 5 OPERATION PARAMETER #00 OPERATION PARAMETER #00 TW_O PLATE W-OUTLET TEMP. 35°C T3 OUTDOOR EXCHARGE TEMP. 5°C TW_I PLATE W-INLET TEMP. 30°C T4 OUTDOOR AIR TEMP. T2 PLATE F-OUT TEMP. 35°C TF MODULE TEMP. 35°C P1 COMP. PRESSURE 5°C 55°C SUPPLY VOLTAGE 230V T2B PLATE F-IN TEMP. DC GENERATRIX VOLTAGE 420V Th COMP. SUCTION TEMP.
12.4 Error codes When a safety device is activated, an error code will be displayed on the user interface. A list of all errors and corrective actions can be found in the table below. Reset the safety by turning the unit OFF and back ON. In case this procedure for resetting the safety is not successful, contact your local dealer. ERROR CODE MALFUNCTION OR PROTECTION Water flow falut(after 3 times E8) FAILURE CAUSE AND CORRECTIVE ACTION 1.The wire circuit is short connected or open.
ERROR CODE MALFUNCTION OR PROTECTION FAILURE CAUSE AND CORRECTIVE ACTION 1. The EEprom parameter is error, rewrite the EEprom data. Indoor unit EEprom failure 2. EEprom chip part is broken, change a new EEprom chip part. 3. main control board of indoor unit is broken, change a new PCB. 1.wire doesn’t connect between outdoor unit and main control board of indoor unit. connect the wire. Communication fault between indoor unit and outdoor unit Refrigerant liquid temp.sensor(T2) fault 2.
ERROR CODE MALFUNCTION OR PROTECTION Three times “PP” protection and Tw_out< 7℃ FAILURE CAUSE AND CORRECTIVE ACTION The same to "PP". 1.Check the resistance of the sensor. Buffer tank up temp.sensor(Tbt1) fault 2.The Tbt1 sensor connector is loosen,reconnect it. 3.The Tbt1 sensor connector is wet or there is water in,remove the water ,make the connector dry.Add waterproof adhesive. 4.The Tbt1 sensor failure,change a new sensor." 1.Check the resistance of the sensor. 2.
13 TECHNICAL SPECIFICATIONS Indoor unit model 60 100 160 220-240V~ 50Hz Power supply Rated input 95W 95W 95W Rated Current 0.4A 0.4A 0.4A Refer to the technical data Norminal capacity Dimensions (W×H×D)[mm] 420x790x270 Packing (W×H×D)[mm] 525x1050x360 Plate heat exchanger Heat exchanger / Electric heater Internal water volume 5.0L Rated water pressure 0.3MPa 60 Filter mesh 6L/min Min. water flow (flow switch) 10L/min Pump DC inverter Type 9m Max.
Indoor unit model 60 (3kW Heater) Rated Current 160 (3kW Heater) 60 (9kW Heater) 220-240V~ 50Hz Power supply Rated input 100 (3kW Heater) 160 (9kW Heater) 380~415V 3N~ 50Hz 3095W 3095W 3095W 9095W 9095W 9095W 13.5A 13.5A 13.5A 13.3A 13.3A 13.
14 INFORMATION SERVICING 1) Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minmised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. 2) Work procedure Works shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.
10) Repairs to sealed components a) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete(if not already). Extreme care shall be taken not to overfill the refrigeration system.
ANNEX A: Refrigerant cycle 7 Basic 4 Customized Item Description Item 1 Water Side Heat Exchanger (Plate Heat Exchange) 8 2 Flow switch 9 Circulating pump 3 Refrigerant liquid line temperature sensor 10 Manometer 4 Refrigerant gas line temperature sensor 11 Pressure relief valve 5 Water outlet temperature sensor 12 Internal backup heater 6 Water inlet temperature sensor 13 Total outlet temperature sensor 7 Automatic air purge valve 70 Description Expansion vessel
NOTE 71
NOTE 72
Tel. +39 0362 680 1 Fax +39 0362 680 693 www.systemair.com As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Dans un souci d’amélioration constante, nos produits peuvent être modifiés sans préavis. Photos non contractuelles. In dem Bemühen um ständige Verbesserung können unsere Erzeugnisse ohne vorherige Ankündigung geändert werden. Fotos nicht vertraglich bindend.