13 Error Code Table
Table 3-13.1: Error code table
Table connued on next page …
Error code Content
C7 Transducer module temperature too high protecon
E0 Water ow failure (E8 appears 3 mes)
E1 Phase sequence error (for 3 phase models)
E2 Communicaon error between the main control board of hydraulic module and user interface
E3 Backup electric heater exchanger water outlet temperature sensor T1 error
E4 Domesc hot water tank temperature sensor T5 error
E5 Air side heat exchanger refrigerant outlet temperature sensor T3 error
E6 Outdoor ambient temperature sensor T4 error
E7 Balance tank sensor Tbt1 error
E8 Water ow failure within 3 mes
E9 Sucon pipe temperature sensor Th error
EA Discharge pipe temperature sensor Tp error
Eb Solar board sensor Tsolar error
Ec Balance tank sensor Tbt2 error
Ed Water side heat exchanger water inlet temperature sensor Twin error
EE. Hydronic box EEPROM error
F1 DC generatrix voltage is too low
H0 Communicaon error between outdoor unit main control chip and hydronic box main control chip
H1 Communicaon error between outdoor unit main control chip and inverter driver chip
H2 Water side heat exchanger refrigerant outlet (liquid pipe) temperature sensor T2 error
H3 Water side heat exchanger refrigerant inlet (gas pipe) temperature sensor T2B error
H4 Inverter module protecon (L0/L1 appear 3 mes in one hour)
H5 Room temperature sensor Ta error
H6 DC fan error
H7 Abnormal main circuit voltage
H8 Pressure sensor error
H9 Zone 2 water outlet temperature sensor Tw2 error
HA Water side heat exchanger water outlet temperature sensor error
Hb PP protecon appears three mes in a row and Twout<7℃
H.F. Invert module EEPROM error
HH H6 appears 10 mes in 120min
HP Low pressure protecon (pressure < 0.6MPa for 3 mes in one hour)
P0 Low pressure protecon
P1 High pressure protecon
P3 Compressor current protecon
P4 Discharge temperature sensor Tp protecon
P5 High temperature dierence between water side heat exchanger water inlet and water outlet temperatures protecon
P6 Inverter module protecon
L0 Inverter module protecon
L1 DC bus low voltage protecon
L2 DC bus high voltage protecon