EDM SYSHP MINI SPLIT 06 16

Table Of Contents
93
8.8 TEMP. TYPE SETTING Menu
MENU > FOR SERVICEMAN > TEMP. TYPE SETTING
The TEMP. TYPE SETTING is used for selecng whether the water ow temperature
or room temperature is used to control the ON/OFF of the heat pump.
When ROOM TEMP. is enabled, the target water ow temperature will be calculated
from climate-related curves (refer to “9.1 Climate related curves ”).
For installaons without room thermostats, space heang and cooling modes can be
controlled in one of two dierent ways:
according to the Heat Pump leaving water temperature alone
according to the room temperature detected by the Heat Pump Split user
interface’s built-in temperature sensor alone
WATER FLOW TEMP. sets whether space heang/cooling modes are controlled
according to the Heat Pump leaving water temperature. If YES is selected, the user is
able to set the Heat Pump Split units leaving water temperature set temperature on
the user interface’s main screen.
ROOM TEMP. sets whether space heang/cooling modes are controlled according to
the room temperature detected by the temperature sensor in the Heat Pump Split
user interface. If YES is selected, the user is able to set the room temperature set
temperature on the user interface’s main screen, no maer what is the seng of
WATER FLOW TEMP.
DOUBLE ZONE sets whether there are two zones.
If set WATER FLOW TEMP. and ROOM TEMP. to YES, meanwhile set DOUBLE ZONE to
NON or YES, the following pages will be displayed. In this case, the seng value of
zone 1 is T1S, the seng value of zone 2 is T1S2 (The corresponding TIS2 is calculated
according to the climate related curves.)
Figure 3-8.19: TEMP. TYPE SETTING menu
Figure 3-8.20: Only set WATER FLOW TEMP to YES
Figure 3-8.21: Only set ROOM TEMP to YES
Figure 3-8.22: Set WATER FLOW TEMP. and ROOM TEMP. to YES; Set DOUBLE ZONE to NON or YES
Homepage (zone 1)
Addion page (zone 2)
(Double zone is eecve)