EDM SYSHP MINI SPLIT 06 16
Table Of Contents
- CONTENTS
- CONTENTS
- 1.1 System Schematic
- 1.2 System Configurations
- 2 Unit Capacities
- 2.1 Outdoor unit
- 3 Nomenclature
- 3.1 Outdoor unit
- 3.2 Hydronic box
- 4 System Design and Unit Selection
- 4.1 Selection procedure
- 4.2 M thermal Leaving Water Temperature (LWT) Selection
- 5 Typical Applications
- 5.1 Space Heating Only
- 5.2 Space Heating and Domestic Hot Water
- 5.3 Space Heating, Space Cooling and Domestic Hot Water
- 5.4 Space Heating and Domestic Hot Water (Bivalent)
- 5.4.2 Auxiliary heat source provides space heating and domestic hot water
- 5.5 Space Heating Through Floor Heating Loops and Radiators
- 5.6 Space Heating, Space Cooling and Domestic Hot Water Compatible with Solar Water Heater
- Part 2 Engineering Data
- 1.1 Outdoor Unit
- 1.2 Hydronic Box
- 2 Dimensions and Center of Gravity
- 2.1 Outdoor Unit
- 2.2 Hydronic Box
- 3.1 Outdoor Unit
- 4 Wiring Diagrams
- 4.1 Outdoor Unit
- 4.2 Hydronic Box
- 5 Capactiy Tables
- 5.2 Cooling Capacity Tables (Test standard:EN14511)
- 7 Hydronic Performance
- 8.1 Overall
- 8.2 Octave Band Levels
- 9.1 Outdoor Unit
- 1.1 Notes for Installers Boxes
- 2 Installation
- 2.1 Acceptance and Unpacking
- 2.3 Outdoor unit
- 1
- 1.1
- 1.2
- 1.3
- 1.4
- 1.5
- 2.4 Hydronic box
- 3 Refrigerant Pipework
- 3.1 Permitted Piping Length and Level Difference
- 3.3 Procedure and Principles
- 3.4 Storing Copper Piping
- 3.8 Pipe Flushing
- 3.9 Gastightness Test
- 4 Water Pipework
- 4.1 Water Circuit Checks
- 4.2 Water volume and sizing expansion vessels
- 4.3 Water Circuit Connection
- 4.4 Water Circuit Anti-freeze Protection
- 5.1 General
- 5.4 Wiring Overview
- 8.1 Introduction
- 8.2 Menu Structure
- 8.11 HOLIDAY AWAY SETTING Menu
- 8.14 TEST RUN
- 8.15 SPECIAL FUNCTION
- 8.16 AUTO RESTART
- 8.20 HMI ADDRESS SET
- 9 Operation parameter
- 10 Network Configuration Guidelines
- 10.1 Install APP
- 10.2 Sign in
- 10.3 Add device and login to home Wi-Fi
- 10.4 Wired Controller Setting
- 10.4.2 Finishing up
- 11 USB Function Guidelines
- 11.1 Parameters setting transfer between wired controllers
- 11.2 Convenient program upgrade for unit
- 12 Climate Related Curves
- 13 Error Code Table
- Part 1 General Information
- Part 2 Engineering Data
- Part 3
- Installation and Field Settings
- 1 Air-to-Water HP Split System
- 2 Unit Capacities
- 3 Nomenclature
- 4 System Design and Unit Selection
- 5 Typical Applications
- 1 Specifications
- 3 Piping Diagrams
- 4 Wiring Diagrams
- 5 Capactiy Tables
- 6 Operating Limits
- 7 Hydronic Performance
- 8 Sound Levels
- 9 Accessories
- 1 Preface to Part 3
- 3 Refrigerant Pipework
- 4 Water Pipework
- 6 DIP Switch Settings
- 7 Internal Circulation Pump
- 8 User Interface Field Settings
- 9 Operation parameter
- 10 Network Configuration Guidelines
- 11 USB Function Guidelines
- 12 Climate Related Curves
- 13 Error Code Table
94
If set DOUBLE ZONE to YES and set ROOM TEMP. to NON, meanwhile set WATER FLOW TEMP. to YES or NON, the following pages
will be displayed. In this case, the seng value of zone 1 is T1S, the seng value of zone 2 is T1S2.
If set DOUBLE ZONE and ROOM TEMP. to YES, meanwhile set WATER FLOW TEMP. to YES or NON, the following page will be
displayed. In this case, the seng value of zone 1 is T1S, the seng value of zone 2 is T1S2. (The corresponding TIS2 is calculated
according to the climate related curves.)
Homepage (zone 1) Addion page (zone 2)
(Double zone is eecve)
Figure 3-8.23: Set DOUBLE ZONE to YES and set ROOM TEMP. to NON; Set WATER FLOW TEMP. to YES or NON
Figure 3-8.24: Set DOUBLE ZONE and ROOM TEMP. to YES; Set WATER FLOW TEMP. to YES or NON
Homepage (zone 1) Addion page (zone 2)
8.9 ROOM THERMOSTAT Menu
MENU > FOR SERVICEMAN > ROOM THERMOSTAT
As an alternave to controlling space heang/cooling modes according to the
Heat Pump Split unit’s leaving water temperature and/or the room temperature
detected by the temperature sensor in the Heat Pump Split user interface,
separate room thermostat can be installed and used to control space heang/
cooling modes.
In ROOM THERMOSTAT the following parameters should be set.
ROOM THERMOSTAT sets whether or not room thermostats are installed. For installaons with room thermostats, select YES. For
installaons without room thermostats, select NON.
ROOM THERMOSTAT = NON: No room thermostat.
ROOM THERMOSTAT = MODE SET: Room thermostat can control heang and cooling individually.
ROOM THERMOSTAT=ONE ZONE: Room thermostat provides the switch signal to unit.
ROOM THERMOSTAT=DOUBLE ZONE: Indoor unit is connected with two room thermostat.
Figure 3-8.25: ROOM THERMOSTAT menu