OM SYSHP MINI SPLIT

t_DI_max
t_DI_hightemp
t_interval_C
dT1SC
dTSC
T4cmax
T4cmin
t_interval_H
dT1SH
dTSH
T4hmax
T4hmin
T4_IBH_on
dT1_IBH_on
t_IBH_delay
T4_AHS_on
dT1_AHS_on
t_AHS_delay
221 (PLC: 40222)
222 (PLC: 40223)
223 (PLC: 40224)
224 (PLC: 40225)
225 (PLC: 40226)
226 (PLC: 40227)
227 (PLC: 40228)
228 (PLC: 40229)
229 (PLC: 40230)
230 (PLC: 40231)
231 (PLC: 40232)
232 (PLC: 40233)
233 (PLC: 40234)
234 (PLC: 40235)
235 (PLC: 40236)
237 (PLC: 40238)
238 (PLC: 40239)
240 (PLC: 40241)
Maximum disinfection duration, range: 90~300 min, default setting: 210 min
Disinfection high temperature duration, range: 5~60 min, default setting: 15 min
Time interval of compressor start-up in cooling mode; range: 5~30 min,
default setting: 5 min
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 43°C, range: 35~46°C, setting interval: 1°C
Default setting: 10°C, range: -5~25°C, setting interval: 1°C
Time interval of compressor start-up in the heating mode; range: 5~60 min,
default setting: 5 min
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 25°C, range: 20~35°C, setting interval: 1°C
Default setting: -15°C, range: -25~5°C, setting interval: 1°C
Ambient temperature for enabling the hydraulic module auxiliary electric
heating IBH, range: -15~10°C; default setting: -5°C
Temperature return difference for enabling the hydraulic module auxiliary
electric heating IBH, range: 2~10°C; default setting: 5°C
Delay time of enabling the hydraulic module auxiliary electric heating IBH,
range: 15~120 min; default setting: 30 min
Ambient temperature for enabling the external heater AHS,
range: -15~10°C, setting interval: -5°C
Temperature return difference for enabling the external heater AHS,
range: 2~10°C; default setting: 5°C
Delay time for enabling the external heater AHS, range: 5~120 min;
default setting: 30 min
56