OM SYSHP MINI SPLIT

t_DHWHP_max
t_DHWHP_restrict
T4autocmin
T4autohmax
T1S_H. A_H
T5S_H. A_DHW
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
Reserved, wrong address is reported when this register is queried
t_DRYUP
t_HIGHPEAK
t_DRYD
T_DRYPEAK
t_firstFH
241 (PLC: 40242)
242 (PLC: 40243)
243 (PLC: 40244)
244 (PLC: 40245)
245 (PLC: 40246)
246 (PLC: 40247)
247 (PLC: 40248)
248 (PLC: 40249)
249 (PLC: 40250)
250 (P LC:40251)
251 (PLC: 40252)
252 (P LC:40253)
253 (PLC: 40254)
254 (P LC:40255)
255 (PLC: 40256)
256 (PLC: 40257)
257 (PLC: 40258)
258 (PLC: 40259)
259 (PLC: 40260)
260 (PLC: 40261)
ECO parameter
ECO parameter
ECO parameter
ECO parameter
Comfort parameter
Comfort parameter
Comfort parameter
Comfort parameter
T1S (first floor heating)
Longest duration of water heating by the heat pump, range:
10~600 min, default setting: 120 min;
Duration of limited water heating by the heat pump, range:
10~600 min, default setting: 30 min;
Default setting: 25°C, range: 20~29°C, setting interval: 1°C
Default setting: 17°C, range: 10~17°C, setting interval:
1°C
In the holiday mode, setting of T1 in the heating mode, range:
20~25°C, default setting: 25°C
In the holiday mode, setting of T1 in the water heating mode,
range: 20~25°C, default setting: 25°C
Temperature rise day number, range: 4~15 days, default setting: 8 days
Drying day number, range: 3~7 days, default setting: 5 days
Temperature drop day number, range: 4~15 days, default setting: 5 days
Highest drying temperature, range: 30~55°C, default setting: 45°C
Running time of floor heating for the first time, default setting: 72 hrs,
range: 48-96 hrs
T1S of floor heating for the first time, range: 25~35°C, default setting: 25°C
57