DVG Installation and Operating Instructions for DVG-H DVG-V English original version DVG-H EC DVG-V EC
Previous issues: IMO_DVG_en_13_12_2016 Changes: Major revision The data stated in these operating instructions are merely for the purpose of describing the product. Information about a certain property or suitability for a certain purpose of use cannot be derived from our information. The information does not release the user from his own assessments and examinations. Please consider the fact that our products are subject to a natural wear and ageing process.
Contents 8.2 Safety elements........................................... 11 8.3 Commissioning ............................................ 11 1.1.1 Specific safety symbols ................................. 4 9 Operation ................................................. 12 1.1.2 List of instructions for action ........................ 5 9.1 Safety notes ................................................ 12 1.2 9.2 Operating conditions................................... 12 9.3 Operation/use .......
General information 1 General information 1.1 List of information DANGER Direct danger Failure to comply with this warning leads directly to death or to serious bodily harm. WARNING Possible danger Failure to comply with this warning potentially leads to death or to serious bodily harm. CAUTION Hazard with a low risk Failure to comply with this warning potentially leads to moderate injuries. ATTENTION Hazard with risk of property damage Failure to comply with this warning leads to property damage.
Important safety information 1.1.2 List of instructions for action Instruction for action Instruction for action with fixed order Carry out this action. Carry out this action. (if applicable, further action) Carry out this action. (if applicable, further action) 1.2 Notes on the documentation WARNING Hazard as a result of improper dealing with the fan These operating instructions describe safe use of the device.
Warranty 2.2.3 Personnel for operation/use, maintenance and cleaning Operation/use, maintenance and cleaning may only be carried out by trained and authorized personnel. The operating personnel must have appropriate knowledge about handling with the fan. In the case of a malfunction or an emergency, they must react correctly and adequately. 2.3 Intended use DVG fans are intended for installation in ventilation systems, outside buildings only (on roofs).
Transport, storage 4 Transport, storage 4.1 Transport Each fan leaves our plant in an electrically and mechanically proper condition. The fans are delivered in wooden crates or cardboard boxes. We recommend transporting the fans to the installation site in original packaging. WARNING Hazard of impact if the fan falls down! Load and unload the fan carefully in order to avoid possible damage. Pay attention to the weight and dimensions of the packaging.
Description 5 Description The casing is manufactured from seawater resistant aluminium. The base plate with nozzle consists of pre-galvanized steel. Impellers with backward-curved blades are welded and galvanized (sizes 355 and 450 have impellers made of pre-galvanized steel and tabbed). They are fastened together with hub and secured screw directly on to the motor shaft. Dynamically balanced to ISO 1940 T1, class G6,3.
Installation CAUTION Danger from cutting edges! At installation works wear protective working gloves. 6.2 Preconditions for installation DVG fans must be installed on roofs, outside fire zone (DVG/F for exhausting from fire zone). The fans must be mounted on a flat, horizontal roof base (<10 mm/m) with height of min. 250 mm over the rooftop (motor shaft vertical). The base shall be accordingly designed (load capacity, stiffness, insulation), if not proved Systemair accessories used.
Electrical connection 7 Electrical connection The wiring diagram is placed inside the cover of service switch (also in the test protocol). At DVG-EC the wiring diagram is placed in the connection box. The quality and installation of cables for electrical connection must ensure uninterrupted energy supply, even in case of fire. Inside fire zone use only certified cable. The electric cable must not be in contact with or be fastened to the casing of the fan (F400 only, high temperature!).
Commissioning 7.2 Connection of thermal protection (not applicable at DVG-EC) CAUTION Property damage as a result of motor overheating The motor can overheat and be destroyed if the PTC not been connected. PTC always connect to a motor protective device! 8 Commissioning 8.1 Preconditions Mounting and electrical connection have been correctly performed. Installation residuals and foreign objects have been removed from the fan and ducts. Inlet and outlet are free.
Operation 9 Operation 9.1 Safety notes WARNING Hazard from electrical voltage! The device may only be operated by persons - instructed in function and risks, - who have understood handling and can accordingly react. Ensure access only to persons, who can safe handle the device. 9.2 Operating conditions During operation, touching the impeller must not be possible. Safety components must not be bypassed or put out of function.
Maintenance/troubleshooting NOTE At single speed motors with nominal power from incl. 5,5 kW (D400V) we recommend “star – delta” starting. For this purpose all 7 wires are led to connection box/service switch. NOTE (DVG-EC ONLY) 0-10V speed control input. Modbus controllable. Fire mode to disable motor protection and controller protection in case of fire. 9.3 Operation/use Only use the fan in accordance with this operating instruction and the operating instructions of motor.
Maintenance/troubleshooting CAUTION Danger from hot surfaces! During maintenance/troubleshooting and cleaning wear protective working gloves to prevent contact with hot motor! 10.1 Malfunctions and troubleshooting (generally) The ventilator does not run Air volume is too low Thermal protection of the fan switches off Possible reasons Connection to the mains fault. Thermal protection triggers. Motor fault. Wrong direction of rotation. Too high pressure drop in system. Obstacles in duct.
Maintenance/troubleshooting Maintenance and check points of fans similarly to VDMA 24186-1 (type, scope and maintenance intervals to be specified in dependence of use and operating conditions). VDMA 24186-1 Description Maintenance interval Monthly Fan and electric motor of the fan Check the drainage for function Check to dirt, damage, corrosion and fastening Functional cleaning Check the terminals for tightness Test the fan for function und operational readiness (test run app. 15 min.
Uninstalling/dismounting 11 Uninstalling/dismounting WARNING Hazard from electrical voltage! Disconnection and uninstalling only by a trained electrician or trained and instructed qualified personnel! Observe 5 safety rules for the electrical expert! - disconnect from the power supply (all-pole), - prevent switching on again, - test absence of voltage, - earthing and short-circuiting, - protect adjacent live parts by covers and barriers and fit a suitable warning notice.
Appendix 1: Mounting of service switch / Mounting of vertical outlets at DVG-V Properly mounted service switch, See IMO, Section 7 cable protected inside tube DVG 30.03.
Appendix 2: Wiring diagrams Single speed motor up to inclusive 4 kW output power, 4 pole, 6 pole, 8 pole Single speed motor, DVG-H/V 400D4V/F400 – it can be voltage controlled 18 DVG 30.03.
2 speed motor in Dahlander connection, 4-8 pole Y400V…low speed, YY400V…high speed Single speed motor with star – delta starting (motors with output power more than 4 kW) Starting in Y, operation in D Warning: it is not 2 speed motor! 2 speed motor with separated windings, 4-6, 6-8 pole 1U, 1V, 1W…low speed 2U, 2V, 2W…high speed DVG 30.03.
Appendix 3: Wiring diagrams DVG-EC 1~ Symbol Description G1 Fan DVG-EC G2 EC controller - terminals prewired with connection box on the casing G3 Service switch ON-OFF, 6 pole + 1xNC F1 Fault relay F2 Analog input for set value / speed setting F3 Potentiometer for speed setting F4 External sensor F5 Speed output F6 FIRE mode (open = FIRE) F7 Start/Stop switch (open = stop) F8 Modbus E1 Power supply - connection in G3 Max.
DVG 355-EC, DVG 450-EC – Wiring 1~, 230V, 50/60Hz……..27.11.2013 Terminals 4 to 23 (lower markings in the connection box) are led from controller out to outer connection box. 3 bridges are factory inserted to allow test of fan without connecting control cables. In case of using the fan for smoke and heat extraction, remove the red bridge 16-17 (fire mode) and connect controller to fire central up to wiring scheme.
Appendix 4: Wiring diagrams DVG-EC 3~ Symbol Description G1 Fan DVG-EC G2 EC controller - terminals prewired with connection box on the casing G3 Service switch ON-OFF, 6 pole + 1xNC F1 Fault relay F2 Speed output F3 Potentiometer for speed setting F4 Analog input for set value/speed setting F5 External sensor F6 FIRE mode (open = FIRE) F7 Start /Stop switch (open = stop) F8 Modbus E1 Power supply - connection in G3 Max.
DVG 560-EC, DVG 630-EC, DVG 800-EC – Wiring 3~, 400V, 50/60Hz……..27.11.2013 Terminals 1 to 17 (lower markings in the connection box) are led from controller out to outer connection box. 3 bridges are factory inserted to allow test of fan without connecting control cables. In case of using the fan for smoke and heat extraction, remove the red bridge 10-11 (fire mode) and connect controller to fire central up to wiring scheme).
Appendix 5: Accessories DVG-H - mounting DVG-H DVG-H SSG/F VKG/F SSG/F ASG/F VKG/F ASG/F ASSG/F ASSG/F DVG-H DVG-H VKG/F VKG/F ESDG SSGE/F (FDGE/F) FDG/F ASG/F ASSG/F 24 DVG 30.03.
Appendix 6: Accessories DVG-V - mounting DVG-V DVG-V SSG/F VKG/F SSG/F ASG/F VKG/F ASG/F ASSG/F ASSG/F DVG-V DVG-V VKG/F VKG/F ESDG SSGE/F (FDGE/F) FDG/F ASG/F ASSG/F DVG 30.03.
Appendix 7: Sealing of cable glands (DVG-EC only) no wire 1x blind plug D8 1x wire up to D5,3 mm 1x multiwire sealing insert 2x blind plug D5 2x wire up to D5,3 mm 1x multiwire sealing insert 1x blind plug D5 3x wire up to D5,3 mm 1x multiwire sealing insert no blind plug All cable glands for control cables seal with multiwire sealing inserts and blind plugs to prevent moisture/dust ingress! Tighten the cable glands to obtain tightness! Attached: 2 multiwire cable inserts, 4 blind plugs D5 26 DVG 30.