MONOLIT EC AC INSTALLATION INSTRUCTIONS

A B C D E F
MONOLIT EC
N.B. Damper adjustment or speed changes must be carried out by a qualified professional.
Setting the damper: The air flow is adjusted with the aid of the damper.
The damper can be accessed for adjustment by removing the filter.
Changing the voltage: The output voltage for speeds can be changed by reprogramming
via the control panel.
Start programming: Press and hold buttons B and C for 6 seconds.
Press one of the buttons B to E once to see the set value.
The value is indicated by the flashes on the button’s LED.
Press and hold button where speed is to be changed.
Release the button when the set value has been obtained (see table).
Set values for the speeds can be controlled by pressing button A once.
Press any button to cancel.
Save the changes by pressing and holding buttons B and C for 3 seconds.
Indication/ Button/
Flashes Function
B C D E
Standard
mode Speed 1 Speed 2 Speed 3
Factory settings 2 V 3 V 5 V 10 V
x1 1,5 V 1,5 V 3,5 V 7 V
x2 2 V 2 V 4 V 7,5 V
x3 2,5 V 2,5 V 4,5 V 8 V
x4 3 V 3 V 5 V 8,5 V
x5 3,5 V 3,5 V 5,5 V 9 V
x6 4 V 4 V 6 V 9,5 V
x7 4,5 V 4,5 V 6,5 V 10 V