SYSHP MINI EVO P – Installation Operation Manual (IOM SYSHP MINI EVO P S 1GB)

8.2.2 Mode set control
Operation mode and ON/OFF of the unit are set via the room thermostat, water temperature is set on the user interface.
1) When “CL” of the thermostat keep closing for 15s, the system will run according to the priority mode set on the user interface.
2) When “CL” of the thermostat keep opening for 15s and “HT” close , the system will run according to the non-priority mode set
on the user interface.
3) When “HT” of the thermostat keep opening for 15s and “CL” open , the system will turn off.
4) When “CL” of the thermostat keep opening for 15s and “HT” open , the system will turn off.
Space heating
The circulation pump and valve operation
1When the system is in cooling mode, SV2 keeps OFF, P_o starts running.
2When the system is in heating mode, SV2 keeps ON, P_o starts running.
4
4.2
4.1
10
Outdoor
1
FCU1 FCUnFCU2
FHL1 FHL2 FHLn
19
19
20
5
22
M
RT
2
17
15
16
14
12
14
16
Code
Assembly unit
Code
Assembly unit
1
Main unit
2
User interface
16
4
Buffer tank
(Field supply
)
19
4.1
Automatic air purge valve
20
4.2
Drainage valve
5
P_o: Outside circulation pump
(Field
supply)
RT
22
10
Expansion vessel
(Field supply
)
FHL 1…n
12 Filter (Accessory) FCU 1...n
14
Shut-off valve
15
Filling valve (Field supply)
(Field supply
)
Collector/distributor
Low
voltage
room
thermostat
SV2: 3
-
-way valve (Field supply
Drainage valve (Field
supply
)
Bypass valve (Field
supply)
Floor heating loop (Field
supply)
Fan coil unit (Field supply)
16