SYSHP MINI EVO P – Installation Operation Manual (IOM SYSHP MINI EVO P S 1GB)

44
CAUTION
Do not place the wired remote controller near
the lamps, to avoid the remote signal of the
controller to be disturbed. (refer to the right
figure)
10.4.2.3 Note for installation of wired controller:
1) This installation manual contains information about the
procedure of installing Wired Remote Controller. Please refer to
Indoor Unit Installation Manual for connection between Wired
Remote Controller and Indoor Unit.
2) Circuit of Wired Remote Controller is low voltage circuit. Never
connect it with a standard 220V/380V circuit or put it into a same
Wiring Tube with the circuit.
3) The shielded cable must be connected stable to the ground, or
transmission may fail.
4) Do not attempt to extend the shielded cable by cutting, if it is
necessary, use Terminal Connection Block to connect.
5) After finishing connection, do not use Megger to have the
insulation check for the signal wire.
6Cut off the power supply when installing the wired controller.
10.4.3 Installation procedure and matching setting of
wired controller
10.4.3.1 Structure size figure
19mm84mm
44mm
46mm
60mm
120mm
20mm
120mm
Figure A
10.4.2 Other Precautions
10.4.2.1. Installation location
Do not install the unit in a place with much oil, steam, sulfide gas.
Otherwise, the product may deform and fail.
10.4.2.2 Preparation before installation
1) Check whether the following assemblies are complete.
1
3
2
1
2
For Mounting on the Wall
Name
Qty.
Remarks
Wired Controller
Installation and Owner's Manual
Plastic bolt
3
For mounting on the Wall
Plastic expansion pipe
Cross round head wood
mounting screw
Cross round head
mounting screw
For Mounting on the
Electrical Switch Box
This accessory is used when
install the centralized control
inside the electric cabinet
1
2
3
4
5
6
No.
10.4.3.3 Back cover installation
Buckling position
Back cover
Straight head
screwdriver
Front cover
Screw hole installed on the
three M4X20
18V DCInput Voltage(HA/HB)
Wiring size
Wiring type
Wiring length
0.75mm
2
2-core shielded twisted pair cable
L1<50m
10.4.3.2 Wiring
H2H1
EA+ B-
Modlous
D2
D1
X1/HB
E
X2/HA
Wired Controller
Hydraulic module
A B
X/HA
E
Y/HB
P Q E1 H1 H2
L1