SYSHP MINI EVO P – Installation Operation Manual (IOM SYSHP MINI EVO P S 1GB)

48
11.1 Setting parameters
Order
number
Code State Default
1.1 DHW MODE Enable or disable the DHW mode:0=NON,1=YES 1
1.2 DISINFECT Enable or disable the disinfect mode:0=NON,1=YES 1
1.3 DHW PRIORITY Enable or disable the DHW priority mode:0=NON,1=YES 1
1.4 PUMP_D Enable or disable the DHW pump mode:0=NON,1=YES 0
1.5
DHW PRIORITY TIME SET
Enable or disable the DHW priority time set:0=NON,1=YES 0
1.6 dT5_ON The temperature diff erence for starting the hea
t pump 10
1.7 dT1S5
The difference value between Twout and T5 in DHW mode
10
1.8 T4DHWMAX
The maximum ambient temperature that the heat pump
can operate at for domestic water heating
43
1.9 T4DHWMIN
The minimum ambient temperature that the heat pump can
operate for domestic water heating
-10
1.10 t_INTERVAL_DHW The start time interval of the compressor in DHW mode. 5
1.11 T5S_DISINFECT 65
1.12 t_DI_HIGHTEMP 15
1.13 t_DI_MAX 210
1.14 t_DHWHP_RESTRICT 30
1.15 t_DHWHP_MAX 90
1.16 PUMP_D TIMER 1
1.17
PUMP_D RUNNING TIME
The certain time that the DHW pump will keep running. 5
1.18 PUMP_D DISINFECT 1
1.19 ACS FUNCTION 0
2.1 COOL MODE Enable or disable the cooling mode:0=NON,1=YES 1
2.
2 t_T4_FRESH_C The refresh time of climate related curves for cooling mode 0.5
2.3 T4CMAX
The highest ambient operation temperature for cooling mode
52
2.4 T4CMIN The lowest ambient operating temperature for cooling mode 10
2.5 dT1SC
5
2.6
dTSC 2
2.8 T1SetC1
The setting temperature 1 of climate related curves f or
cooling mode.
5
10
2.9 T1SetC2
The setting temperature 2 of climate related curves f or
cooling mode.
16
2.10 T4C1
The ambie
nt temperature 1 of climate related curves for
cooling mode.
35
2.11 T4C2
The ambient temperature 2 of climate related curves for
cooling mode.
25
2.12 ZONE1 C-EMISSION 0
2.13 ZONE2 C-EMISSION 0
The parameters related to this chapter are shown in the table below.
2.7 t_INTERVAL_C The start time interval of the compressor in cooling mode
3.1 HEAT MODE Enable or disable the heating mode 1
3.2 t_T4_FRESH_H The refresh time of climate related curves for heating mode
0.5
The target temperature of water in the domestic hot water
tank in the DISINFECT function.
The time that the highest temperature of water in the
domestic hot water tank in the DISINFECT function will last.
The maximum time that disinfection will last.
The operation time for the space heating/cooling operation.
The maximum running time of heat pump in DHW
PRIORITY mode.
Enable or disable the DHW pump run as timed and keeps
running for PUMP RUNNING TIME:0=NON,1=YES
Enable or disable the DHW pump operates when the unit
is in disinfect mode and T5≥T5S_DI-2:0=NON,1=YES
Enable or disable the second water tank control T5_2
0=NON,1=YES
Unit
/
/
/
/
/
MIN
MIN
MIN
/
MIN
/
/
/
hours
/
/
/
hours
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
The temperature difference between T1 and T1S(the set
water temperature) for starting the heat pump
The temperature difference between actual room
temperature Ta and the set room temperature Tas for
starting the heat pump.
The terminal type of zone 1 for cooling mode: 0=FCU(fan
coil unit), 1=RAD.(radiator), 2=FHL(floor heating loop)
The terminal type of zone 2 for cooling mode: 0=FCU(fan
coil unit), 1=RAD.(radiator), 2=FHL(floor heating loop)
min
°C