SYSHP MINI EVO P Engineering Data Manual (EDM SYSHP MINI EVO P S 1GB)

78
1.20 HMI ADDRESS SET
MENU > FOR SERVICEMAN > HMI ADDRESS SET
HMI ADDRESS SET
HMI SET sets the wired controller is master or slave. (0=MASTER, 1=SLAVE)
When HMI SET is set to SLAVE, the controller can only switch the operation mode, turn on or off, set the temperature, and
cannot set other parameters and functions.
HMI ADDRESS FOR BMS sets the HMI address code for BMS.(only valid for master controller)
STOP BIT set upper computer stop bit(1: STOP BIT1; 2:STOP BIT2)
1.21 COMMON SET
MENU > FOR SERVICEMAN > COMMON SET
t_DELAY PUMP sets the delay time for the pump to turn off after the compressor stops.
t1_ANTILOCK PUMP sets the interval time that the pump runs in order to antilock
t2_ANTILOCK PUMP RUN sets the running time for pump antilock operation
t1_ANTILOCK SV sets the interval time that the valve works in order to antilock
t2_ANTILOCK SV RUN sets the running time for valve antilock operation
Ta-adj is an correction value for Ta which is inside the wired controller.
F-PIPE LENGTH select the total length in the liquid pipe (0=F-PIPE LENGTH<10m, 1=F-PIPE LENGTH>=10m)
PUMP_I_SLIENT OUTPUT can decrease water pump maximum output in order to decrease the noise of heat pump.
17 HMI ADDRESS SET
MASTER
1
17.1 HMI SET
17.2 HMI ADDRESS FOR BMS
ADJUST
17.3 STOP BIT
1
18 COMMON SET
2,0MIN
24h
60s
24h
30s
18.1 t_DELAY_PUMP
18.2 t1_ANTILOCK PUMP
18.3 t2_ANTILOCK PUMP RUN
18.4 t1_ANTILOCK SV
18.5 t2_ANTILOCK SV RUN
1/2
ADJUST
18 COMMON SET
-2° C
<10m
100%
18.6 Ta_adj.
18.7 F-PIPE LENGTH
18.8 PUMP_I_SILENT OUTPUT
2/2
ADJUST