Fig. 6: Wet installation of PKI-C in exible wall
Fig. 7: Cross-section of Wet installation in exible wall
EI60S/EI90S/EI120S - Flexible Wall
Installation into the End of a Duct Fitted with Valve
1 Fire damper PKI-C
2 Connected metal ductwork
3 Plaster/mortar/concrete lling
4 Flexible duct coupling TVK-PKIC-DN/return plastic valve (e.g. BALANCE-E)
Legend (Fig. 4 up to Fig. 7)
IMPORTANT: Make sure the valve, when inserted, is not protruding in the blade area of PKI-C damper.
1
2
3
4
45 max.
60 max.
13 2
4
≥100 (EI60S)
≥125 (EI90S)
≥150 (EI120S)
20
12,5 (EI60S, EI90S)
15 (EI120S)
≥40 (EI60S, EI90S)
≥60 (EI120S)
DN
DN + 60
DN + 100