GB SIRe Advanced Fan Heater Electric Quick guide/start up Enter ID/Operation without control unit Check that all constituent parts are present (see section Constituent parts). The control system can control one or more units in parallel (max 9). Each unit must get a unique ID number (1-9) which is set in the ID selector of the PC board. E.g. Unit 1: ID=1, unit 2: ID=3 If the external control for some reason has not been installed the unit can still be run temporarily.
GB SIRe Advanced Fan Heater Electric Start up System supplied with power. At the first start up, the start-up wizard is run and the basic settings are made. Fan and heating steps are tested through the test program. Then a status window is displayed. At the first start up alarm and error codes can occur, these will usually be reset without actions. Start up Select mixing cabinet On in the start-up wizard.
GB SIRe Advanced Fan Heater Electric Contents Quick guide/start up Advice about location Connect the system Wiring diagrams Enter ID/Operation without control unit Start up Unit with mixing cabinet Start up 22 22 22 22 23 23 23 Constituent parts 25 SIReFAX (without mixing cabinet) SIReFAEMX (with mixing cabinet) 26 Option 27 Operating modes Operating modes (without mixing cabinet) Operating modes (with mixing cabinet) 28 28 Control unit SIReUA1 Overview 29 Statuswindow 29 Main menu Curren
GB SIRe Advanced Fan Heater Electric Constituent parts SIReFAX (without mixing cabinet) SIReUA1, control unit Competent and Advanced SIReA1X, PC board HUB Advanced Wall unit cover SIReB1X, External PC board Basic SIReOTX, outdoor temperature sensor SIReIT02, internal temperature sensor 2m SIReCC, modular cable Dimensions constituent parts Type Description SIReUA1 SIReB1X SIReIT02 SIReA1X SIReOTX SIReCC603 SIReCC605 Control unit Competent and Advanced External PC Board Base Internal temperature
GB SIRe Advanced Fan Heater Electric SIReFAEMX (with mixing cabinet) SIReUA1, control unit Competent and Advanced Wall unit cover SIReB1X, External PC board Basic SIReIT02, internal temperature sensor 2 m 0 90 90 0 60 30 SIReA1X, PC board HUB Advanced SIReOTX, outdoor temperature sensor 30 60 PSM01, damper motor SIReCC, modular cable Dimensions constituent parts Type Description SIReUA1 SIReB1X SIReIT02 SIReA1X SIReOTX PSM01 SIReCC603 SIReCC605 Control unit Competent and Advanced External
GB SIRe Advanced Fan Heater Electric Option SIReRTX, external room temperature sensor SIReUR, kit for recessed installation SIReCJ4, joint piece SIReCJ6, joint piece SIReCC, modular cable Type RSK-no. E-no.
GB SIRe Advanced Fan Heater Electric Operating modes Operating modes (with mixing cabinet) Operating modes (without mixing cabinet) The control is based on two operating modes: Control is based on the three operating modes: • Thermostat / Manual fan • Thermostat / Automatic fan • Manual Thermostat / Manual fan The thermostat just controls the heating and the fan runs continually. The fan speed is set manually.
GB SIRe Advanced Fan Heater Electric Control unit SIReUA1 Overview Statuswindow Back arrow IN 19.0 °C OUT -5.0 °C Fan speed step Forward arrow Heating step Rotary dial Meny Week program Day Week program Night Alarm Red led Run signal Green led OFF Week program Out of operation Explanations Statuswindow The display shows prevailing room temperature, outdoor temperature, fan and heating step and day, night mode, or Off when week program is used.
GB SIRe Advanced Fan Heater Electric Main menu System on/off Current settings Displays set room temp, high speed limit and week program status. Main menu Current settings Current settings Temperature settings Fan control Room temp. day Room temp. night High speed limit Week program 20°C 18°C Step 5 No program Temperature settings Set the desired room temperatures to apply for day respectively night mode (room temperature night is used for week program/ night reduction).
GB SIRe Advanced Fan Heater Electric Installer menu To enter the Installer menu, code 1932 is entered. Select the digits using the rotary dial and confirm using the forward arrow. Main menu Main menu>Installer menu Fan control System on/off Enter password Check program 0 0 0 0 (See manual) Installer menu Installer status screen Check the settings. The installer status screen consists of three pages with settings, scroll using the rotary dial.
GB SIRe Advanced Fan Heater Electric Week program is activated by selecting On, under Week program on/off. In On-mode, a sun, moon or Off in the Status window appears to indicate day, night respectively Off-function. >Installer menu>Week program >Installer menu>Week program Week program on/off New program step Check program Week program on/off OFF • Fan settings Make settings for fan mode (see also Operating modes section). Heating settings Make settings for heating.
GB SIRe Advanced Fan Heater Electric Temperature control without mixing cabinet (fan mode Thermostat /Automatic fan): Comfort 1. Fan starts at set setpoint value. 2. Heating on at set setpoint value – 0.5K Eco Fan starts at set setpoint value - 1K. Heating on at set setpoint value – 2K. Heating off at set setpoint value. Temperature control (Outlet temp. limit) with mixing cabinet (fan mode Thermostat/ Automatic fan): Comfort 1. Increases heating step. 2. Gradually closes damper to night mode. Eco 1.
GB SIRe Advanced Fan Heater Electric Filter guard settings Filter alarm alarms when the set fixed run time has been exceeded. >Installer menu Heating settings Filter guard settings External control Filter timer setting Under Filter timer setting, set the desired run time to between 50 and 9950 hours. Last filter change To check the number of run time hours since the last filter replacement, select Last filter change. The time is reset when the filter alarm is reset.
GB SIRe Advanced Fan Heater Electric Night damper pos. Desired current damper position nighttime. >Installer menu>Mixing cabinet >Installer menu>Mixing cabinet Min outlet temp. Day damper pos. Night damper pos. • 0% Night damper pos. External control (BMS) BMS functions can be activated under External control. Activate External on/off (5-30V AC/DC from BMS) or 0-10V fan control by selecting On under the respective one. See diagram on next page and Connecting external control.
GB SIRe Advanced Fan Heater Electric 7,8 4 6,1 3 4,4 2 2,8 1 8,3 6,6 4,9 3,2 [V] 1 2 3 4 5 6 7 8 9 10 11 Diagram: Fan step at incoming 0-10V DC voltage level, 4 step 6,8 2 2,8 1 7,2 1 2 3,2 3 4 5 6 7 8 9 10 11 [V] Diagram: Fan step at incoming 0-10V DC voltage level, 2 step 7,2 3 5,0 2 2,8 1 1 2 7,6 5,4 3 3,2 4 5 6 7 8 9 10 11 [V] Diagram: Heating step for incoming 0-10V DC voltage level, 3-step.
SIRe Advanced Fan Heater Electric General settings Possibility of making general settings that are also in the Start-up wizard and execute user reset. Function test To test the fan and heating steps, run the function test. >Installer menu >Installer menu>General settings External control General settings Support menu Function test Start test Skip test Change the date, time, language and temperature unit.
GB SIRe Advanced Fan Heater Electric Alarm and error codes SIRe has different alarms and error codes for safe and problem free operation. If alarms or error codes have been indicated these must be reset in order to return to normal operation, for example activating the heating again. Fan mode is active even when, for example, the over heating alarm has been indicated. Displaying alarm and error codes In event of alarm or error the alarm/error code is shown in the status window.
SIRe Advanced Fan Heater Electric GB Table - Alarm Alarm Cause Action A1 Motor alarm Thermal switch has deployed. One or several motors have overheated. (Only units with withdrawn thermal switches.) Check that nothing is obstructing the unit’s air intake and exhaust. When the overheated motor has cooled the thermal switch shuts again and the alarm can be reset. At repeated alarms, check the motors, replace damaged motors.
GB SIRe Advanced Fan Heater Electric Table - Error codes Error code Cause Action E1 Communication SIReB1X has no contact with SIReA1X. Check connection between the boards. Replace any modular cables. E2 ID Error Two or more SIReB1 X have the same ID number. Interrupt the current and select different ID numbers for all SIReB1X in the system. E3 ID Error One or several SIReB1X does not have a program. Contact Frico for support.
GB SIRe Advanced Fan Heater Electric Connecting external control - including BMS functions SIReA1X 19 20 Operation indication OUT (BMS) 21 22 RPM indication Ext. Heating control 0-10V DC IN Heating indication External on/off 5-30V AC/DC 3 4 + - 0-10V DC OUT (max 5 mA) Signal from SIRe indicates connected heating step. Always active. (obligatory) SIReOTX 5 6 7 8 External alarm IN Outgoing alarm indication. Always active.
SIRe Advanced Fan Heater Electric Connections between SIReB1X and Panther SE06, SE09, SE12 and SE15.
SIRe Advanced Fan Heater Electric Connections between SIReB1X and Panther SE20 L L~ N SIReB1X SE20 203
SIRe Advanced Fan Heater Electric Connections between SIReB1X and Panther SE30 L L~ N SIReB1X SE30 204
SIRe Advanced Fan Heater Electric 21 22 111213 1415 161718 + - + 1 2 3 4 5 6 7 8 9 10 + - + - ROOM BUS COM 2 EXTERNAL ON/OFF, 5-30V AC/DC EXTERNAL HEAT 0-10V DC IN EXTERNAL RPM 0-10V DC IN EXTERNAL ALARM IN (potential free contact) EXTERNAL SETBACK TEMP. on/off (potential free contact) HEAT INDICATION 0-10V DC out (max 5 mA) RPM INDICATION 0-10V DC out (max 5 mA) 230V~ COM 1 SIReA1X N L~ L PE N L ALARM OUT (BMS) (potential free contact, max 3A, 230V) C2 Pot.
SIRe Advanced Fan Heater Electric 21 22 EXTERNAL ON/OFF 5-30V AC/DC EXTERNAL HEAT 0-10V DC IN EXTERNAL RPM 0-10V DC IN EXTERNAL ALARM IN (potential free contact) EXTERNAL SETBACK TEMP. on/off (potential free contact) 206 230V~ PE N L N L~ L ACTUATOR SUPPLY C2 Pot.
SIRe Advanced Fan Heater Electric 21 22 EXTERNAL ON/OFF, 5-30V AC/DC EXTERNAL HEAT 0-10V DC IN EXTERNAL RPM 0-10V DC IN EXTERNAL ALARM IN (potential free contact) EXTERNAL SETBACK TEMP. on/off (potential free contact) COM 1 COM 2 BUS 1 2 3 4 5 6 7 8 9 10 + - + - ROOM 111213 1415 161718 + - + - ALARM OUT (BMS) (potential free contact, max 3A, 230V) HEAT INDICATION 0-10V DC out (max 5 mA) RPM INDICATION 0-10V DC out (max 5 mA) 230V~ L PE N C2 Pot.