Original instructions SIRe Advanced Fan Heater - Water With quick guide SIReFA SIReFAWM SE .... 2 GB .... 22 DE .... 42 FR .... 62 ES .... 82 IT NL .... 123 NO .... 144 PL .... 164 RU .... 184 .... 103 For wiring diagram, please see last pages.
GB SIRe Advanced Fan Heater Water Quick guide/start up Wiring diagrams Check that all constituent parts are present (see section Constituent parts). The wiring diagrams are in a separate section at the end of this manual. When external PC board Base SIReB1X is used, wiring between the PC board base and the unit must be done. Please see separate manual for SIReB1X. Advice about location PC board HUB SIReA1X is installed close to the unit.
SIRe Advanced Fan Heater Water GB Start up Unit with mixing cabinet System supplied with power. At the first start up, the start-up wizard is run and the basic settings are made. Fan and heating steps are tested through the test program. Then a status window is displayed. At the first start up alarm and error codes can occur, these will usually be reset without actions. When a mixing cabinet is used the supplied Return temp. sensor SIReWTA must be installed.
GB SIRe Advanced Fan Heater Water Contents Quick guide/start up Advice about location Connect the system Wiring diagrams Enter ID/Operation without control unit Start up Unit with mixing cabinet Start up Jumper settings 22 22 22 22 23 23 23 23 Constituent parts SIReFA (without mixing cabinet) SIREFAWM (with mixing cabinet) 25 26 Operating modes Operating modes (without mixing cabinet) Operating modes (with mixing cabinet) 29 29 Control unit SIReUA1 Overview Statuswindow 30 30 Main menu Current set
GB SIRe Advanced Fan Heater Water Constituent parts SIReFA (without mixing cabinet) Integrated in fan heater X5 C2 SIReUA1, control unit Competent and Advanced Wall unit cover SIReOTX, outdoor temperature sensor SIReA1X, PC board HUB Advanced X4 C1 X3 ROOM ACTUATOR 230V PE N L SUPPLY 230V SIReIT, internal temperature sensor SIReB1/B2, integrated PC Board Base SIReCC, modular cable Dimensions constituent parts Type Description SIReUA1 SIReB1 SIReIT SIReA1X SIReOTX SIReCC603 SIReCC605 Contro
GB SIRe Advanced Fan Heater Water SIREFAWM (with mixing cabinet) X5 C2 SIReUA1, control unit Competent and Advanced X4 C1 X3 ROOM ACTUATOR 230V PE N L SUPPLY 230V SIReB1/B2, integrated PC Board Base Wall unit cover SIReIT, internal temperature sensor 0 90 90 0 60 30 SIReA1X, PC board HUB Advanced SIReOTX, outdoor temperature sensor 30 60 SMM24, damper motor SIReWTA, clamp-on sensor SIReCC, modular cable Dimensions constituent parts Type Description SIReUA1 SIReB1 SIReIT SIReA1X SIReOT
GB SIRe Advanced Fan Heater Water Option SIReRTX, external room temperature sensor SIReUR, kit for recessed installation SIReCJ6, SIReCJ4, joint piece joint piece SIReWTA, clamp-on sensor SIReCC, modular cable Type RSK-no. E-no.
GB SIRe Advanced Fan Heater Water Water control - valve kit SDM24 VMO TBVCM AV Water control - option VMOP SDM24 TBVCMP AV VAT, adjustment tool for valve package. VMT SDM24 TRVS Type RSK-no.
SIRe Advanced Fan Heater Water GB Operating modes Operating modes (with mixing cabinet) Operating modes (without mixing cabinet) The control is based on two operating modes: Control is based on the four operating modes: • Auto • Thermostat / Manual fan • Thermostat / Automatic fan • Manual Auto When the set point value is undercut by 0.5 K the fan starts at speed 1 and the valve motor starts to open stepless.
GB SIRe Advanced Fan Heater Water Control unit SIReUA1 Overview Statuswindow (Auto mode) IN 19.0 °C OUT -5 .0 °C Statuswindow Statuswindow (Manual mode) Forward arrow Back arrow IN 19.0 °C OUT -5.
GB SIRe Advanced Fan Heater Water Main menu System on/off Current settings Switch the whole unit off manually. In Off the display goes out; as soon as a button is pushed the display lights and shows System on/off. To activate the unit again select On. The unit’s safety functions are still active when the system is switched off, which means that the fan can continue to run for a moment after mode Off has been selected. Displays set room temp, high speed limit and week program status.
GB SIRe Advanced Fan Heater Water Installer menu To enter the Installer menu, code 1932 is entered. Select the digits using the rotary dial and confirm using the forward arrow. To check which days a certain program is active, select a week day by pressing the forward arrow, the program is marked and those days that the program is used will be underlined, switch between the programs for a particular day using the rotary wheel.
GB SIRe Advanced Fan Heater Water Week program is activated by selecting On, under Week program on/off. In On-mode, a sun, moon or Off in the Status window appears to indicate day, night respectively Off-function. >Installer menu>Week program >Installer menu>Week program Week program on/off New program step Check program • Week program on/off OFF Fan settings Make settings for fan mode (see also Operating modes section). Stepless fan control Settings for stepless fan control.
GB SIRe Advanced Fan Heater Water Control with mixing cabinet, with falling outlet temp Comfort: 1. Opens the valve gradually to fully open valve. 2. Gradually closes damper to night mode 3. Slows down the fan. Eco: 1. Gradually closes damper to night mode 2. Opens the valve gradually to full heating. 3. Slows down the fan. Max. outlet temp. limit +32°C. >Installer menu>Heating settings When the temperature falls below the set point value the fan speed increases (the high speed limit is position 4).
GB SIRe Advanced Fan Heater Water Control range limit External filter guard The maximum room temperature that a user can select is limited to between 5 – 35°C. If an external filter guard, e.g. a pressure switch, is used, it is activated under External filter guard, select On. >Installer menu>Heating settings >Installer menu>Heating settings Return water temp.
GB SIRe Advanced Fan Heater Water External control (BMS) Day damper pos. Desired current damper position daytime. >Installer menu>Mixing cabinet Min outlet temp. Day damper pos. Night damper pos. >Installer menu>Mixing cabinet Day damper pos. 100 % Factory setting Day damper pos.: 100% (0 – 100%) Night damper pos. >Installer menu Desired current damper position nighttime. >Installer menu>Mixing cabinet Min outlet temp. Day damper pos. BMS functions can be activated under External control.
SIRe Advanced Fan Heater Water GB 8,4 5 7,0 4 5,6 3 4,2 2 2,8 1 1 7,4 6,0 4,6 3,2 2 8,8 3 4 5 6 7 8 9 10 11 [V] 7,2 3 5,0 2 7,6 2,8 1 5,4 Diagram: Fan step at incoming 0-10V DC voltage level, 5 step 3,2 1 2 3 4 5 6 7 8 9 10 11 General settings Possibility of making general settings that are also in the Start-up wizard and execute user reset. >Installer menu [V] Function test To test the fan and heating steps, run the function test.
GB SIRe Advanced Fan Heater Water Alarm and error codes Power failure SIRe has different alarms and error codes for safe and problem free operation. If alarms or error codes have been indicated these must be reset in order to return to normal operation, for example activating the heating again. Fan mode is active even when, for example, the over heating alarm has been indicated.
SIRe Advanced Fan Heater Water GB Table - Alarm Alarm Cause Action A1 Motor alarm Thermal switch has deployed. One or several motors have overheated. (Only units with withdrawn thermal switches.) Check that nothing is obstructing the unit’s air intake and exhaust. When the overheated motor has cooled the thermal switch shuts again and the alarm can be reset. At repeated alarms, check the motors, replace damaged motors.
GB SIRe Advanced Fan Heater Water Table - Error codes Error code Cause Action E1 Communication SIReB1(X) has no contact with SIReA1X. Check connection between the boards. Replace any modular cables. E2 ID Error Two or more SIReB1(X) have the same ID-number. Interrupt the current and select different ID numbers for all SIReB1(X) in the system. E3 ID Error One or more SIReB1(X) do not have programs. Contact Frico for support.
GB SIRe Advanced Fan Heater Water Connecting external control - including BMS functions SIReA1X 0-10V DC OUT (max 5 mA) Signal from SIRe indicates fan control, corresponds to 0-100% fan control. Always active. Operation indication OUT (BMS) 5 6 7 8 9 10 (potential free contact) max 3A, 230V) Outgoing operation indication. Always active. 21 22 Operation indication OUT (BMS) External rpm control 0-10V DC 1112 + - Control fan control 0-100%.
C2 Pot. X5 Unit ID C1 X4 ROOM X3 ~ N L L SIReST23024 PE N L ACTUATOR SUPPLY COM 2 111213 1415 161718 + - + - ROOM BUS (not in use) 1 2 3 4 5 6 7 8 9 10 + - COM 1 SIReA1X SIReSDM24 SIReWTA (optional) Black Grey Red RPM INDICATION 0-10V DC out (max 5 mA) SIReB1 EXTERNAL SETBACK TEMP.
C2 Pot. X5 Unit ID C1 X4 ~ N L L ST23024 PE N L ACTUATOR SUPPLY ROOM X3 24V SDM24 1 2 3 4 + SMM24 COM 2 111213 1415 161718 + - + - ROOM BUS (not in use) 1 2 3 4 5 6 7 8 9 10 + - COM 1 SIReWTA (Return water temp. sensor) SIReA1X EXTERNAL SETBACK TEMP.
206 ~ ROOM X3 ACTUATOR SUPPLY N L L PE N L ~ ACTUATOR SUPPLY N L L PE N L SIReWTA (optional) ST23024 SDM24 SDM24 SDM24 Black Grey Red C1 X4 ROOM X3 ~ ACTUATOR SUPPLY N L L PE N L PE N L SUPPLY 230V ACTUATOR 230V COM 2 BUS 1 2 3 4 5 6 7 8 9 10 + - COM 1 SIReA1X 111213 1415 161718 + - + - ROOM 21 22 BMS INDICATION OUT (potential free contact max 3A, 230V) 19 20 ALARM OUT (BMS) (potential free contact, max 3A, 230V) C2 Pot.
Tel: +46 31 336 86 00 Fax: +46 31 26 28 25 mailbox@frico.se www.frico.se For latest updated information and information about your local contact: www.frico.