NOVA-H Perforated Panel Grille Handbook
/30 | NOVA-H Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions & Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ordering Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
/30 | NOVA-H Description NOVA-H is a diffusion grille with perforated panel. The product is mainly intended for air extract and can be used for air supply as well. The product is installed into rectangular ducts or into walls. For a balanced distribution it is recommended to use the R1-NOVA damper or a plenum box. The field of application is industrial and commercial premises.
/30 | NOVA-H Product Parts NOVA- H-2... A2 A1 P1.2 P1.1 P1 Legend P1 NOVA-H P1.1 Grille frame P1.
/30 | NOVA-H Dimensions & Weights NOVA- H-2... 5 W+30 (H-20) (W-20) (H-3) (W-3) H W H+30 26 46 (mm) (mm) H W H+30 NOVA-H-2...
/30 | NOVA-H W H mm 200 300 400 500 600 800 1000 1200 AV = 46% m W kg 100 0,6 150 0,7 200 0,8 100 0,8 150 0,9 200 1,1 300 H mm m kg 75 0,5 125 0,7 225 0,9 75 0,7 125 0,9 225 1,2 1,4 325 1,5 100 0,9 75 0,9 150 1,1 125 1,1 200 1,3 225 1,4 300 1,6 325 1,8 400 2,0 425 2,2 100 1,1 75 1,1 150 1,3 125 1,3 200 1,5 225 1,7 300 1,9 325 2,1 400 2,3 425 2,5 500 2,7 525 2,9 100 1,3 75 1,2 150 1,5 125 1,5 200 1,7 225 1,9 3
/30 | NOVA-H Ordering Codes NOVA-H Fixing 1 Screws 2 Spring clips Dimensions 1 W×H Surface finish 2 SW Signal white (RAL9003, gloss 30%) RALXXXX Other RAL colour NOTES: 1. Available dimension combinations are in the dimension table. 2. In case the surface finish is not specified in the ordering code, the product will be delivered powder painted to RAL9003 (signal white) as standard. Example of Ordering Code NOVA-H-2-400x200-SW Perforated panel grille.
/30 | NOVA-H Accessories R1-NOVA Damper for NOVA Description R1-NOVA is a damper for NOVA grilles. The product is intended to balance distribution of air through the entire grille. The product is intended for air supply as well as for air extract. The damper changes the air flow using its regulating wheel. Design R1-NOVA is manufactured from galvanized steel sheet. The product consists of a frame, adjustable blades and a regulating wheel. The regulating wheel is operated by a flap tip screwdriver.
/30 | NOVA-H W H mm 200 300 400 500 600 800 1000 1200 m W kg 100 0,36 150 0,48 200 0,61 100 0,53 150 0,71 200 0,90 300 H mm m kg 75 0,32 125 0,47 225 0,75 75 0,46 125 0,67 225 1,06 1,27 325 1,46 100 0,69 75 0,61 150 0,93 125 0,87 200 1,18 225 1,39 300 1,67 325 1,90 400 2,15 425 2,42 100 0,86 75 0,74 150 1,15 125 1,07 200 1,47 225 1,70 300 2,07 325 2,33 400 2,67 425 2,96 500 3,29 525 3,61 100 1,03 75 0,88 150 1,38 12
/30 | NOVA-H Ordering Codes R1-NOVA Dimensions W×H Example of the Ordering Code R1-NOVA-400x200 Damper for NOVA, dimensions 400 mm × 200 mm.
/30 | NOVA-H UR-NOVA Mounting Frame for NOVA Description UR-NOVA is a mounting frame for NOVA grilles. The product is intended to simplify the installation of a grille. The product is installed into a walls, celings or rectangular ducts. Design The product is manufactured from galvanized steel sheet. Non-standard version of the product manufactured from stainless steel is available upon request. Dimension (H + 23) × (W + 23) 26 max. 3 A - walling concrete, B - plaster board, C - wood max.
/30 | NOVA-H W H mm 200 300 400 500 600 800 1000 1200 m W kg 100 0,19 150 0,22 200 0,26 100 0,26 150 0,29 200 0,33 300 H mm m kg 75 0,19 125 0,22 225 0,29 75 0,26 125 0,29 225 0,36 0,39 325 0,43 100 0,33 75 0,33 150 0,36 125 0,36 200 0,39 225 0,43 300 0,46 325 0,49 400 0,53 425 0,56 100 0,39 75 0,39 150 0,43 125 0,43 200 0,46 225 0,49 300 0,53 325 0,56 400 0,59 425 0,63 500 0,66 525 0,69 100 0,46 75 0,46 150 0,49 1
/30 | NOVA-H Ordering Codes UR-NOVA Dimensions W×H Example of the Ordering Code UR-NOVA-400x200 Mounting frame for NOVA, dimensions 400 mm × 200 mm.
/30 | NOVA-H Quick Selection Air flow volume qv at different A-weighted sound power levels LWA Item 25 dB(A) 30 dB(A) 35 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-200x100-SW 65 18 84 23 106 29 NOVA-H-1-200x100-SW + R1-NOVA-200x100 42 12 55 15 69 19 NOVA-H-1-200x150-SW 103 29 130 36 163 45 NOVA-H-1-200x150-SW + R1-NOVA-200x150 67 19 85 24 106 30 NOVA-H-1-200x200-SW 142 39 179 50 223 62 NOVA-H-1-200x200-SW + R1-NOVA-200x200 92 26 116 32 145 40 NOVA-H-1-22
/30 | NOVA-H Item 25 dB(A) 30 dB(A) 35 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-400x400-SW 656 182 810 225 989 275 NOVA-H-1-400x400-SW + R1-NOVA-400x400 426 118 526 146 643 179 NOVA-H-1-425x75-SW 110 31 140 39 176 49 NOVA-H-1-425x75-SW + R1-NOVA-425x75 72 20 91 25 114 32 NOVA-H-1-425x125-SW 195 54 244 68 302 84 NOVA-H-1-425x125-SW + R1-NOVA-425x125 127 35 159 44 197 55 NOVA-H-1-425x225-SW 370 103 464 129 572 159 NOVA-H-1-425x225-SW + R1-NOVA-425x
/30 | NOVA-H Item 25 dB(A) 30 dB(A) 35 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-600x150-SW + R1-NOVA-600x150 224 62 282 78 348 97 NOVA-H-1-600x200-SW 476 132 595 165 730 203 NOVA-H-1-600x200-SW + R1-NOVA-600x200 309 86 386 107 474 132 NOVA-H-1-600x300-SW 747 208 921 256 1122 312 NOVA-H-1-600x300-SW + R1-NOVA-600x300 486 135 598 166 730 203 NOVA-H-1-600x400-SW 1026 285 1260 350 1530 425 NOVA-H-1-600x400-SW + R1-NOVA-600x400 667 185 819 228 994 276
/30 | NOVA-H Item 25 dB(A) 30 dB(A) 35 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-825x325-SW + R1-NOVA-825x325 752 209 928 258 1126 313 NOVA-H-1-825x425-SW 1556 432 1911 531 2310 642 NOVA-H-1-825x425-SW + R1-NOVA-825x425 1011 281 1242 345 1502 417 NOVA-H-1-825x525-SW 1961 545 2406 668 2903 806 NOVA-H-1-825x525-SW + R1-NOVA-825x525 1275 354 1564 434 1886 524 NOVA-H-1-1000x100-SW 389 108 487 135 600 167 NOVA-H-1-1000x100-SW + R1-NOVA-1000x100 253 70 317
/30 | NOVA-H Item 25 dB(A) 30 dB(A) 35 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-1200x400-SW 2202 612 2696 749 3248 902 NOVA-H-1-1200x400-SW + R1-NOVA-1200x400 1431 398 1753 487 2111 586 NOVA-H-1-1200x500-SW 2963 823 3614 1004 4338 1205 NOVA-H-1-1200x500-SW + R1-NOVA-1200x500 1926 535 2349 653 2820 783 NOVA-H-1-1200x600-SW 3450 958 4179 1161 4999 1389 NOVA-H-1-1200x600-SW + R1-NOVA-1200x600 2242 623 2716 754 3250 903 NOVA-H-1-1225x75-SW 356 99 443 12
/30 | NOVA-H Air flow volume qv at different A-weighted sound pressure levels LpA with 10m2 absorbtion area Item 20 dB(A) 25 dB(A) 30 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-200x100-SW 62 17 80 22 102 28 NOVA-H-1-200x100-SW + R1-NOVA-200x100 40 11 52 15 66 18 NOVA-H-1-200x150-SW 98 27 125 35 156 43 NOVA-H-1-200x150-SW + R1-NOVA-200x150 64 18 81 23 102 28 NOVA-H-1-200x200-SW 135 37 171 48 213 59 NOVA-H-1-200x200-SW + R1-NOVA-200x200 88 24 111 31 139 39
/30 | NOVA-H Item 20 dB(A) 25 dB(A) 30 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-425x75-SW 105 29 134 37 168 47 NOVA-H-1-425x75-SW + R1-NOVA-425x75 68 19 87 24 109 30 NOVA-H-1-425x125-SW 186 52 234 65 290 81 NOVA-H-1-425x125-SW + R1-NOVA-425x125 121 34 152 42 189 52 NOVA-H-1-425x225-SW 352 98 444 123 549 153 NOVA-H-1-425x225-SW + R1-NOVA-425x225 228 63 288 80 357 99 NOVA-H-1-425x325-SW 532 148 662 184 812 226 NOVA-H-1-425x325-SW + R1-NOVA-425x325
/30 | NOVA-H Item 20 dB(A) 25 dB(A) 30 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-600x200-SW + R1-NOVA-600x200 295 82 371 103 456 127 NOVA-H-1-600x300-SW 716 199 884 245 1080 300 NOVA-H-1-600x300-SW + R1-NOVA-600x300 465 129 575 160 701 195 NOVA-H-1-600x400-SW 983 273 1210 336 1473 409 NOVA-H-1-600x400-SW + R1-NOVA-600x400 639 178 787 219 958 266 NOVA-H-1-600x500-SW 1256 349 1546 429 1876 521 NOVA-H-1-600x500-SW + R1-NOVA-600x500 817 227 1005 279 121
/30 | NOVA-H Item 20 dB(A) 25 dB(A) 30 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-825x425-SW + R1-NOVA-825x425 968 269 1194 332 1447 402 NOVA-H-1-825x525-SW 1877 521 2313 643 2798 777 NOVA-H-1-825x525-SW + R1-NOVA-825x525 1220 339 1504 418 1819 505 NOVA-H-1-1000x100-SW 371 103 467 130 576 160 NOVA-H-1-1000x100-SW + R1-NOVA-1000x100 241 67 303 84 375 104 NOVA-H-1-1000x150-SW 582 162 728 202 893 248 NOVA-H-1-1000x150-SW + R1-NOVA-1000x150 378 105 473 13
/30 | NOVA-H Item 20 dB(A) 25 dB(A) 30 dB(A) m³/h l/s m³/h l/s m³/h l/s NOVA-H-1-1200x500-SW 2840 789 3478 966 4187 1163 NOVA-H-1-1200x500-SW + R1-NOVA-1200x500 1846 513 2261 628 2721 756 NOVA-H-1-1200x600-SW 3313 920 4026 1118 4827 1341 NOVA-H-1-1200x600-SW + R1-NOVA-1200x600 2153 598 2617 727 3138 872 NOVA-H-1-1225x75-SW 339 94 425 118 524 146 NOVA-H-1-1225x75-SW + R1-NOVA-1225x75 220 61 277 77 340 95 NOVA-H-1-1225x125-SW 594 165 744 207 914 254
/30 | NOVA-H Technical Parameters Diagrams and technical parameters are available at design.systemair.
/30 | NOVA-H Installation "NOVA-H " 1. "UR-NOVA" 2a) "e.g.
/30 | NOVA-H B1 2b) B2 "CLICK" 3. 4.
/30 | NOVA-H i "NOVA-H " "R1-NOVA" 1. 2. "CLICK" 1. 2.
/30 | NOVA-H Transport, Storage and Operation
/30 | NOVA-H Supplement Any deviations from the technical specifications contained herein and the terms should be discussed with the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these changes do not affect the quality of the product and the required parameters. Current information on all products is available on design.systemair.com.
Systemair DESIGN • 2022-08-03 • Handbook_NOVA_H_en-GB • Original instructions