Installation, Operation and Maintenance instruction KBR Thermo box fan AC KBR Thermo box fan EC KBR/F Smoke extraction fan
Table of content 1 Introduction .......................................................... 1 1.1 Product description ...................................... 1 1.2 Intended use .............................................. 1 1.3 Document description................................... 1 1.4 Product overview......................................... 1 1.5 Name plate ................................................ 2 1.5.1 Type designation ............................. 2 1.6 Product liability...................
1 Introduction 1.1 Product description constant airflow temperature of 400 °C for 2 hours one time. If KBR/F has a maximum constant airflow temperature of 400 °C for 2 hours, it must be replaced. The product is not applicable for transportation of air that contains explosive, flammable or aggressive media. The product is not applicable for locations where there is a risk of explosion. The product is a centrifugal thermo box fan with a casing made from galvanized steel and mineral wool as insulation.
1.5 Name plate 1 2 3 4 5 6 7 8 10 9 11 12 13 1. Type designation: Product name, dimension and motor type. Refer to 1.5.1 Type designation page 2. 2. Current, A 3. Input power, W 4. Frequency, Hz 5. Certifications 6. Scannable code 1 7. Voltage, V 8. IP class, enclosure class 9. Insulation class 10. Serial number: part number/production number/production date 11. Nominal fan speed 12. Weight, kg 13.
3 Note: Information that is necessary in a given situation. Transportation and storage Warning 2.2 Safety instructions Warning Read the warning instructions that follow before you do work on the product. • Read this manual and make sure that you understand the instructions before you do work on the product. • Obey local conditions and laws. • The ventilation contractor and the operator are responsible for correct installation and intended use. • Keep this manual at the location of the product.
4 Installation 4.1 To do before the installation of the product 4.2 1 To install the product Install the product on the mounting feet. Make sure that the weight of the product is equal on the mounting feet. Make sure the drain plug is always put at the lowest point of the product to drain the condensation. • Make sure that you have the necessary installation accessories: Caution – Refer to 13 Accessory overview page 17 for an overview of the accessories.
4.2.1 1 To connect the ducts to the product Put the ducts on the duct connections of the product. Note: Systemair recommends to use flexible connections or FK fast clamps to attach the duct to the product. Flexible connections and FK fast clamps are available as accessories. 5 Electrical connection 5.1 To do before the electrical connection • Make sure that the electrical connection agrees with the product specification on the motor name plate.
5.6 To install motor protection for AC motors 6 Commissioning Caution • If the product has an built in motor protection, reset by disconnecting the product from power for 60 seconds. • If strong vibrations occur during commissioning, immediately increase or decrease the fan speed until the vibrations are decreased. Continuous strong vibrations can cause damage to components.
7 Operation Caution EC motors must be set to ON/OFF via the control input. To stop the product via mains supply decreases the life time of the motor. Systemair recommends to install external speed controller for easy access to control the input signal. 7.1 To start a product with an EC motor 1 Make sure that the 0–10 V signal is set to “0” with the speed controller. 2 Set the installed safety switch in the ON position and wait 5 seconds.
Maintenance task Usual operation conditions Each 6 months Each 3 months Each 6 months Visually examine the product and its components for damage, corrosion and dirt. X X Examine the fan impeller for damage and imbalance. X X Clean the product and the ventilation system. X Do a check of all fasteners and make sure that they are fully tightened. Make sure that the product and its components are correctly operated.
9 Troubleshooting Note: If you cannot find a solution to your problem in this section, speak to Systemair technical support. Problem Cause Solution The fan impeller is not correctly balanced. Speak to Systemair technical support. There is dirt on the fan impeller. Clean the fan impeller carefully. Refer to 8.2 To clean the product page 8. The fan impeller has damages or deformations because the transported air contains aggressive media. Speak to Systemair technical support.
Problem Cause Solution The fan impeller does not turn in the correct direction. Make sure that the electrical connection is correctly done. A phase loss occurred. If the motor is a 3-phase motor, make sure that no phase is missing. Note: This is not applicable for EC motors. The motor is overheated. Thermal contacts, PTC or resistors are released. • Do a check of the motor cooling impeller. • If it is possible, measure the resistance to do a check of the motor winding.
10 Disposal The product follows the WEEE directive. This symbol on the product or the packaging of the product shows that this product is not domestic waste. The product must be recycled at an approved disposal location for electrical and electronic equipment. 10.1 To disassemble and discard the parts of the product 1 Disconnect and disassemble the product in the opposite sequence of electrical connection and installation.
11 Warranty For warranty claims, send a written maintenance plan and the commissioning report to Systemair. The warranty is only applicable for these conditions: • The product is correctly installed and operated. • Motor protection is used. • The instructions in the data sheets are obeyed. • Maintenance instructions are obeyed. • A product that is not operated continuously is operated for a minimum of 1 hour each month. 12 Technical data 12.
12.2 Product dimensions Note: If the unit of measure is not specified, the dimensions are given in millimetres. H A I B J C D K G E L F M N F J O P A B C D E F G H I ØJ K L M N O P KBR 280 AC 171 125 537 295 360 625 29 291 115 280 50 50 620 38 234 55 KBR/F 280 AC 171 60 537 295 360 625 29 291 50 280 50 50 620 38 234 55 KBR 280 EC 171 125 537 295 360 625 29 291 115 280 50 50 620 38 234 55 KBR 315 AC 187.
12.3 Wiring diagrams Refer to the wiring diagram documents that are included in the supply of the product. The wires in the motor cables have these colours: Wire Colour +10V Red 0...10V/PWM Yellow GND Blue 12.3.1 Wiring diagrams for speed controllers for EC motors Note: An internal potentiometer is installed on the terminal block from the factory. Remove the internal potentiometer when you use an external speed controller for the EC fan. MTP 10 MTP 10 1 2 3/Us +10V 4/+ 0...
MTV–1/10 MTV 1/010 1/IN Vac 230V AC 2/IN Vac +10V 4/Out+ 0...10V 5/Out- GND S-5EC/FRQ MTP 10 10V +10V GND 0...10V A GND EC-Vent EC-Vent IN/RPM optional IN/10V OUT/PWN GND TACH +10V PWM 0...
12.3.2 Wiring diagrams for ON/OFF controls for EC motors CO2RT-R(-D) CO2RT-R-D Supply +10V Neutral 0...10V Common GND 24V AC Relay NO Relay NC Din1 IR24–P IR24-P 24V +10V Neutral 0...
13 Accessory overview 1 2 3 4 5 8 6 7 1. 2. 3. 4. RSA: Silencer EVH: Flexible connection, applicable for KBR/F fans LRK: Airflow shutter UGF: Transition flange 5. 6. 7. 8. ASF: Flexible connection, applicable for KBR fans WBK: Wall bracket ALS: Drain plug WSD: Motor weather protection Note: For more information about accessories, refer to www.systemair.com or speak to Systemair technical support.
14 EU Declaration of Conformity We, the manufacturer Company Systemair GmbH Address Seehöfer Straße 45 97944 Boxberg Germany declare under our sole responsibility that the product Product designation Thermo fans — KBR Smoke extract fans — KBR/F Type/Model KBR 280–355; KBR 280–355EC; KBR/F 280–355; KBR/F 280–355EC Identification Serial numbers dating from 2021 and onwards fulfils all relevant provisions of the Machinery directive 2006/42/EC DIN EN ISO 12100:2013 Safety of machinery - General pri
15 UKCA Declaration of Conformity We, the manufacturer Company Systemair GmbH Address Seehöfer Straße 45 97944 Boxberg Germany declare under our sole responsibility that the product Product designation Thermo fans — KBR Smoke extract fans — KBR/F Type/Model KBR 280D2, KBR 280D2–4, KBR 280DV, KBR 315D2, KBR 315D2, KBR 315DV, KBR 315E4, KBR 355D2, KBR 355D2–K, KBR 280EC, KBR 315EC, KBR 315EC-L, KBR 355EC-K, KBR 355EC-L KBR/F 280D2, KBR/F 280D2–4, KBR/F 280DV, KBR/F 315D2, KBR/F 315DV, KBR/F 355D2, KB
last page Systemair GmbH Seehöfer Str. 45 97944 Boxberg Germany Tel.: +49 (0)7930/9272-0 Fax: +49 (0)7930/9273-92 info@systemair.de www.systemair.de © Copyright Systemair AB All rights reserved EOE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.