4.3.2 Connecting wires to terminals
WARNING
Live terminals and connections even with device
switched off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
; Remove the cap from the cable gland.
Only remove caps where cables are fed in.
; Equip the cable glands with the seals provided in the terminal box.
; Route the wire(s) (not included in scope of delivery) into the terminal
box.
; First connect the "PE" (protective earth).
; Connect the wires to the corresponding terminals.
Useascrewdriver to do so.
When connecting, ensure that no wire ends fan out.
Fig. 2: Connecting wires to terminals
; Seal the terminal box.
4.3.3 Cable routing
Water must be prevented from reaching the cable gland along the cable.
Fans installed lying flat
Make sure the cable is routed inaU-shaped loop.
Fig. 3: Fan installed lying flat, cable routed inaU-shaped loop.
Fans installed upright
When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.
Fig. 4: Cable routing for fans installed upright.
4.4 Factory settings
Factory settings made for the device by Systemair.
Mode parameter set 1 PWM control
Mode parameter set 2 PWM control
Fan/device address 01
Max. PWM/% 100
Min. PWM/% 5
Save set value to
EEPROM
Yes
Set value requirement Analog (linear)
Direction of action
parameter set 1
Positive (heating)
Direction of action
parameter set 2
Positive (heating)