IMO AW 1000D EC SILEO DE,EN

Operating instructions
4.5 Connection diagram
No. Conn. Designation Function/assignment
KL 1 1 L1 Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz
KL 1 2 L2 Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz
KL 1 3 L3 Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz
PE PE Ground connection, PE connection
KL 2 1 NO Status relay, floating status contact; make for failure
KL2 2 COM Status relay, floating status contact; changeover contact; common connection; contact rating 250 VAC/max.
2A(AC1)/min. 10 mA
KL2 3 NC Status relay, floating status contact; break for failure
KL 3 1 RSA Bus connection RS485, RSA, MODBUS-RTU; SELV
KL 3 2 RSB Bus connection RS485, RSB, MODBUS-RTU; SELV
KL 3 3/10 GND Reference ground for control interface; SELV
KL 3 4 Ain1 U Analog input 1, set value: 0-10 V, Ri = 100 , adjustable curve, only usable as alternative to input Ain1 I;
SELV
KL 3 5 + 10 V Fixed voltage output 10 VDC, +10V±3%, max. 10 mA, short-circuit-proof power supply for external devices
(e.g. pot); SELV
KL 3 6 Ain1 I Analog input 1, set value: 4-20 mA, Ri=100 Ω, adjustable curve, only usable as alternative to input Ain1U;
SELV
KL 3 7 Din1 Digital input 1: enable electronics,
enable: pin open or applied voltage 5-50 VDC
disable: bridge to GND or applied voltage<1VDC
reset function: triggers software reset afteralevel change to<1VDC; SELV
KL 3 8 Din2 Digital input 2: Switching parameter sets 1/2, according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2.
Parameter set 1: pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage<1VDC; SELV
KL 3 9 Din3 Digital input 3: according to EEPROM setting, the integrated controller's direction of action can be selected as
normal/inverse via bus or digital input
normal: pin open or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage<1VDC; SELV
KL 3 11 Ain2 U Analog input 2, measured value: 0-10 V, Ri=100 , adjustable curve, only usable as alternative to input
Ain2I; SELV
KL 3 12 + 20 V Fixed voltage output 20 VDC, +20V+25/-10%, max. 50 mA, short-circuit-proof power supply for external
devices (e.g. sensors); SELV
KL 3 13 Ain2 I Analog input 2, measured value: 4-20 mA, Ri=100 Ω, adjustable curve, only usable as alternative to input
Ain2U; SELV
KL 3 14 Aout Analog output 0-10 VDC, max.5mA, output of current motor modulation level/motor speed
adjustable curve; SELV