OPERATION INSTRUCTIONS DANFOSS ENG
ALARM 94, End of curve
Feedback is lower than the setpoint. This may indicate
leakage in the system. 22-50 End of Curve Function is set for
alarm. Troubleshoot the system and reset the adjustable
frequency drive after the fault has been cleared.
ALARM 95, Broken belt
Torque is below the torque level set for no load, indicating
a broken belt. 22-60 Broken Belt Function is set for alarm.
Troubleshoot the system and reset the adjustable
frequency drive after the fault has been cleared.
ALARM 96, Start delayed
Motor start has been delayed due to short-cycle
protection. 22-76 Interval between Starts is enabled.
Troubleshoot the system and reset the adjustable
frequency drive after the fault has been cleared.
WARNING 97, Stop delayed
Stopping the motor has been delayed due to short cycle
protection. 22-76 Interval between Starts is enabled.
Troubleshoot the system and reset the adjustable
frequency drive after the fault has been cleared.
WARNING 98, Clock fault
Time is not set or the RTC clock has failed. Reset the clock
in 0-70 Date and Time.
WARNING 200, Fire mode
This warning indicates the adjustable frequency drive is
operating in Fire mode. The warning clears when fire
mode is removed. See the fire mode data in the alarm log.
WARNING 201, Fire Mode was Active
This indicates the adjustable frequency drive had entered
fire mode. Cycle power to the unit to remove the warning.
See the fire mode data in the alarm log.
WARNING 202, Fire mode limits exceeded
While operating in fire mode one or more alarm conditions
have been ignored which would normally trip the unit.
Operating in this condition voids unit warranty. Cycle
power to the unit to remove the warning. See the fire
mode data in the alarm log.
WARNING 203, Missing motor
With an adjustable frequency drive operating multi-motors,
an underload condition was detected. This could indicate a
missing motor. Inspect the system for proper operation.
WARNING 204, Locked rotor
With an adjustable frequency drive operating multi-motors,
an overload condition was detected. This could indicate a
locked rotor. Inspect the motor for proper operation.
WARNING 250, New spare part
A component in the adjustable frequency drive has been
replaced. Reset the adjustable frequency drive for normal
operation.
WARNING 251, New type code
The power card or other components have been replaced
and the type code changed. Reset to remove the warning
and resume normal operation.
Diagnostics and Troubleshoo... Instruction Manual
44 Danfoss A/S © Rev. 11/06/2014 All rights reserved. MG11AK22
77