OPERATION INSTRUCTIONS DANFOSS ENG
Relay outputs
Programmable relay outputs 2
Relay 01 Terminal number 1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load) 60 V DC, 1 A
Max. terminal load (DC-13)
1)
(Inductive load) 24 V DC, 0.1 A
Relay 02 (FC 302 only) Terminal number 4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
2)3)
Overvoltage cat. II 400 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load) 80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load) 24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load) 50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load) 24 V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2A
Control card, 10 V DC output
Terminal number 50
Output voltage 10.5 V ±0.5 V
Max. load 15 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0–590 Hz ± 0.003 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19) ≤± 0.1 ms
System response time (terminals 18, 19, 27, 29, 32, 33) ≤ 2 ms
Speed control range (open-loop) 1:100 of synchronous speed
Speed control range (closed-loop) 1:1000 of synchronous speed
Speed accuracy (open-loop) 30–4000 rpm: error ±8 rpm
Speed accuracy (closed-loop), depending on resolution of feedback device 0–6000 rpm: error ±0.15 rpm
All control characteristics are based on a 4-pole asynchronous motor
Control card performance
Scan interval 1 ms
Control card, USB serial communication
USB standard 1.1 (full speed)
USB plug USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection ground. Use only an isolated laptop as PC connection to
the USB connector on the adjustable frequency drive.
Specifications
Instruction Manual
62 Danfoss A/S © Rev. 11/06/2014 All rights reserved. MG11AK22