Air Conditioning SysTemp Close Control Engineering Data Manual Series Series Series Series
| Key points Key points SySmart Control Advanced electronic control system is conceived and designed to provide an energy savings and the optimized management of the entire unit. Thanks to the control via Modbus® Master protocol, all key components of the unit are continuously supervised, with over 50 different variables that ensure the real-time monitoring of all operating cycles.
Unit identification and specifications | Unit identifcation and specifications Unit identification ST O P A 07 General The air conditioners have been specifically designed and manufactured for close control air conditioning where the handling almost exclusively sensible heat loads is a fundaAccessories mental requirement.
| Specifications The structure is riveted monobloc made by hot-galvanized sheet steel of 1mm-thickness painted in anthracite colour RAL 7024. Thermal acoustic insulation system consisting of 23mm thickness for the sides panel and 12 or 20 mm for the back panel according to the unit model. The insulation is high density, A1 class fire-resistance polyurethane sheets as per norm UNI/ISO 3795, self-extinguishing, protected by a plastic film out friction.
Specifications | For the units with monobloc structure the drain tray is made by galvanized steel of 1mm-thickness painted in anthracite colour RAL 7024. Valid for models: ST OPA/UPA 071-141-211-251-321-322 ST OPU/UPU 10-20-30-50 ST HRA 121-201-231-361 ST HRU 20-40.
| Specifications Total run hours Menu displays accumulative components operating hours for major components including compressors, fan motor, humidifier and reheat. Supervision and RS 485 / RJ45 port for remote communication Supervision A daily and weekly graphics charts of the temperature and humidity, (if the humidity sensor is installed), detected every two hours are displayed on the display panel.
Specifications | Available close control accessories Inverter on the compressor DC brushless technology, driven by frequency driver (inverter), mounted on vibration isolators. The system includes a manual high-pressure reset switch; auto reset low-pressure managed by software. Valid for units direct expansion circuit only.
| Specifications Protected line and air condenser regulator Consisting in an electrical line protected from overload and short-circuits and a FSC, single-phase fan speed control, with phase cutting regulation for air condenser fan regulation to maintain a constant condensing temperature, or EC fan speed control by 0-10 signal. Valid for units with direct expansion circuit only.
| SysTemp P SysTemp P The P Series close control air conditioners have constructional and operating characteristics suitable for environments where thermal loads of a sensitive nature prevail.
SysTemp P | 11 Air Conditioners with downflow air supply Standard version with top air intake and downflow air supply, with stand for raised floors. Version with top air intake and front air supply through air distribution plenum with adjustable grilles. Version with top air intake and front air supply through front panel.
| SysTemp P Air Conditioners with upflow air supply Standard version with front air intake and upflow air supply. Version with front air intake and supply, through air distribution plenum with adjustable grilles. Version with air intake from the bottom, stand for raised floor, blind front panel and upflow air supply.
SysTemp P | Available accessories Direct expansion: Brushless DC compressors with inverter regulation and integrated oil separator Power supply line for remote condenser Power supply line with speed regulator for remote condenser Condensing regulation with 0-10V signal for remote condenser with EC fans LAC valve for operation with low temperature outside air with remote condenser Water-cooled condenser Water-cooled condenser with a condensing temperature control valve Chilled water: Three-way control valve
| SysTemp G SysTemp G G series close control air conditioners have constructional and operating characteristics suitable for meeting the design criteria of the latest generation data centers. When designing air conditioning systems for large data centers, the need for electrical cable housing and the enormous air volumes required to cool down the servers have made it essential to increase the height of raised floors up to the current 550/1,000-millimetre level.
SysTemp G | Air Conditioners with downflow air supply Standard version for data center perimetral installation: the height of the raised floor must be at least 550 mm. Standard version for data center perimetral installation with raised floor height less than 550 mm. In this case the stand, having a fixed height of 550 mm provided with side closing panels, must be installed above the floor. However, please make sure that the ceiling height allows good air intake.
| SysTemp G Available accessories Direct expansion: Brushless DC compressors with inverter regulation and integrated oil separator Power supply line for remote condenser Power supply line with speed regulator for remote condenser Condensing regulation with 0-10V signal for remote condenser with EC fans LAC Valve for operation with low temperature outside air with remote condenser Water-cooled condenser Water-cooled condenser with a condensing temperature control valve Chilled water: Three-way control v
| SysTemp R SysTemp R R series close control air conditioners are built and sized in such a way that they can be installed alongside data center racks In air conditioning systems for large data centers, the adoption of the following design concepts has in fact become an established custom: The racks containing servers are increasingly positioned according to the Hot Aisle and Cold Aisle layout.
SysTemp R | Air Conditioners with horizontal air supply Version for "in row" Iinstallation with front and side air supply ST HRA: Direct expansion air conditioners with horizontal supply ST HRA 121 201 231 361 Performance ST HRU: Chilled water air conditioners with horizontal supply ST HRU 20 40 37,8 Performance Total cooling capacity (1) kW 9,6 19,3 20,8 32,5 Total cooling capacity (1) kW 24,9 Sensible cooling capacity kW 9,6 15,1 17,2 26,3 Sensible cooling capacity kW 22,2
| SysTemp R Available accessories Direct expansion: Power supply line for remote condenser Power supply line with speed regulator for remote condenser Condensing regulation with 0-10V signal for remote condenser with EC fans LAC valve for operation with low temperature outside air with remote condenser Water-cooled condenser Water-cooled condenser with a condensing temperature control valve Chilled water: Three-way control valves Inlet and outlet water temperature sensors Heating: Low thermal inertia e
SysTemp R | TMC Remote condensers and dry coolers for Close Control units. Technical features Versions for horizontal and vertical installation and with V-shaped structure.
| Technical data Main technical data Operating range Air Conditioners Type Direct Expansion Chilled Water Maximum Temperature (Air infeed) °C 38 40 Minimum Temperature (Air infeed) °C 20 18 Minimum Humidity (Air infeed) % 60 60 Maximum Humidity (Air infeed) % 25 25 Storage Conditions °C Temperature from -20°C to + 45°C - Humidity 10%Ur to 90 %Ur non condensing – Store in a room that is closed and protected from external atmospheric agents.
Technical data | Water circuit connections 3-way valve A B A B C D E F G H C 2-way valve H F G Water connections E Armaflex insulation Mechanical filter Thermometer Shut-off valves Pressure gauge Balance valve Drain Supports D Water supply line Cooled water coil connection Water connections Standard models Fitting diameter Ø Inches DN Threading Water circuit volume ISO 7/1 dm3 P Series 10 3/4” 20 3,5 20 30 50 60 70 80 110 160 220 1” 25 1-1/4” 32 7 10 16 19 28 22 38,5 56 76,5
| Technical data Chilled water coil connection-two sources design (accesory) Water connections Fitting diameter Ø Inches DN P Series 3/4” 20 1” 25 Standard models 50 211 321 70 110 461 - 512 662 – 852 932 160 1-1/4” Water circuit volume dm3 Female 5 5.5 18 16 22 22.5 27.5 34,8 28.5 Female 15.5 22.
Technical data | G A A B C D E F G H I J K H I F J E K D C Plate condenser Condenser water inlet Water discharge Shut-off valve Inlet fitting Outlet fitting Liquid line Hot gas line Thermometers and pressure gauges Balancing valve Condenser water outlet B Non-regulated water-cooled condensers water circuit supply line H A I J F K E L G D C B H A I J F K E L A B C D E F G H I J K L Plate condenser Condenser water inlet Water discharge Shut-off valve Inlet fitting Condensation pressure
| Technical data Water condenser connection of the submerged electrode humidifier Water connections Flexible hose adaptor Threaded fitting Connection diameter Ø (mm) External Internal 8 6 Connection diameter Ø Inches DN 3/4 20 Threading ISO 7/1 Male Humidifier cylinder A A E E B B F A B C D E F F C D C D Internal humidifier components Load-bearing structure Cylinder Solenoid valve/drainage pump Drainage fitting Filling tank + conductivity meter Supply solenoid valve
Technical data | Chilled water circuit The following image represents the water circuit of chilled water units.
| Technical data Cooling circuit with single compressor and remote condenser The following image represents the cooling circuit in units with single compressor and remote condenser.
Technical data | Cooling circuit with single compressor and water-cooled condenser The following image represents the cooling circuit in units with single compressor and air-cooled condenser.
| Technical data Cooling circuit with double compressor and remote condenser The following image represents the cooling circuit in units with double compressor and remote condenser.
Technical data | Cooling circuit with double compressor and water-cooled condenser The following image represents the cooling circuit in units with double compressor and water-cooling condenser.
| Technical data Two sources water circuit with chilled water circuits The following image represents the water circuit of chilled water two sources units.
Technical data | Two sources cooling circuit with single compressor and remote condenser The following image represents the cooling circuit in two sources units with single compressor and remote condenser.
| Technical data Two sources cooling circuit with single compressor and water-cooled condenser The following image represents the cooling circuit in two sources units with single compressor and water-cooling condenser.
Technical data | Two sources cooling circuit with double compressor and remote condenser The following image represents the cooling circuit in two sources units with double compressor and remote con- denser.
| Technical data Two sources cooling circuit with double compressor and water-cooled condenser The following image represents the cooling circuit in two sources units with double compressor and water-cooling condenser.
Technical data | Cooling circuit with free cooling and single compressor The following image represents the cooling circuit of the free cooling units with single compressor.
| Technical data Cooling circuit with free cooling and double compressor The following image represents the cooling circuit of the free cooling units with double compressor.
Weights, Dimensions and clearances | Weights Standard models Weight +/-5% [kg] Standard models Weight +/-5% [kg] Standard models Weight +/-5% [kg] 10 20 30 50 60 70 80 110 160 220 125 150 245 250 270 280 375 410 690 810 50 70 110 160 260 300 435 760 230 XH 300 1250 1630 20 145 40 210 40 260 P Series 071 141 211 251 321 361 461 170 225 280 305 385 460 470 322 422 512 662 852 932 211 310 321 420 461 520 461 612 932 1342 620 690 910 1240 121 220 201 235 430 535 540 685 705 745
| Dimensions and clearances Dimensions and clearances Plan dimensions Dimensions (mm) Standard models 071 – 141 Over 10 – 20 Under 211 – 251 Over 30 – 50 Under 321 – 322 Over 60 - 70 Under 361 – 461 422 – 512 Over 80 – 110 Under Over 160 Under Upper Lower Front Left A B H a b 1 2 750 600 750 600 1990 300 300 880 2300 860 - 2640 3190 Under Over 220 Height 1750 Over 932 TS Depth 1410 Under 932 Length 860 Over 662 – 852 Routine Maintenance (mm) Cle
Dimensions and clearances | Dimensions and clearances Plan dimensions Standard models Dimensions (mm) Depth Height Upper Lower Front A B H a b 1 921 1990 1050 2350 921 1990 300 550* 860 1050 2350 921 1990 1320 461 - 612 1490 150 XH 932 230 230 XH Routine maintenance (mm) Length 70 150 Clearances (mm) 1840 2390 2740 1342 3120 300 4020 * Minimum height of ventilating plinth. Check definitive height when placing the order.
| Dimensions and clearances Plenum and base frame (accessory) Various types of air distribution plenum and base frame are available as accessories for both the Under (U) and Over (O) versions of the unit. When installing plenums and base frame, it is advisable to place a gasket (rubber or similar material) of an adequate thickness and length, between them and the machine to avoid transmitting vibrations to the structure.
Dimensions and clearances | Dimensions and clearances plenum and plinth Plan dimensions - standard model dimensions (mm) P series - Plenum and soundproofed duct section Length Depth Height 071 – 141 – 10 – 20 750 580 450/550 (lower plenum) 850 550 211 – 251 – 30 – 50 860 321 – 322 – 60 – 70 1410 361 – 461 – 422 – 512 – 80 – 110 1750 662 – 852 2300 932 – 160 2640 220 3495 P series - Free-cooling plenum * Length Depth Height 071 – 141 – 10 – 20 750 580 580 211 – 251 – 30 – 50
| Dimensions and clearances Sizing the hole for the installation of the base frame in the finished floor surface P series Plinth plan dimensions - Dimensions (mm) 071- 141 – 10 – 20 Length Depth Tolerance A B C 750 580 211 – 251 – 30 – 50 860 321 – 322 – 60 – 70 1410 361 – 461 – 422 – 512 – 80 – 110 1750 662 – 852 2300 932 – 160 2640 850 10 220 3495 G series ventilated base frame plan dimensions Dimensions (mm) Length Depth Tolerance A B C 900 10 70 1320 461 - 612 149
Dimensions and clearances | TMC Dimensions Vertical Installation (V) Length (A) Standard models Horizontal Installation (H) Depth (B) V mm 11 882 19 1582 31 Height (C) H V mm 480 H mm 550 510 818 Fixing holes Ø Weight mm kg 10 44 67 1225 35 27 71 40 104 49 2225 55 570 900 830 1050 13 63 112 112 120 84 157 3225 92 170 TMC Clearances Vertical Installation (V) Horizontal Installation (H) 45
| Notes Notes
Notes | Notes 47
Systemair AC SAS Route de Verneuil 27570 Tillières-sur-Avre France Tel. +39 0362 680 1 Fax +39 0362 680 693 Tel. +33 02 32 60 61 00 Fax +33 02 32 32 55 13 Systemair · November 2021 · EDM SysTemp-S.7GB/11.21 E34020 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.