Installation and maintenance manual SYSAQUA 140 / 150 / 170 / 190 / 210 Air Cooled Water Chillers and Heat Pumps 143.7 â 217.6kW 125.4 â 208.
English SYSAQUA 1 INSTALLATION INSTRUCTION English NOTICE D’INSTALLATION Français INSTALLATIONSHANDBUCH Deutsch ISTRUZIONI INSTALLAZIONE Italiano INSTRUCCIONES DE INSTALACIÓN Español
English 2 SYSAQUA CONTENTS 1. GENERAL RECOMMENDATIONS......................................................................................................................................................... 3 1.1. SAFETY DIRECTIONS........................................................................................................................................................................................................................ 3 1.2. WARNING................................................
POWER SUPPLY MUST BE SWITCHED OFF BEFORE STARTING WORK IN THE ELECTRIC CONTROL BOX 1. GENERAL RECOMMENDATIONS The purpose of this Manual is to provide users with instructions for installing, commissioning, using and maintaining the units. It also contains instructions on starting up the machine as well as recommendations to avoid bodily injury and risks of damage to the device during its operation.
4 SYSAQUA English 1.3. EQUIPMENT SAFETY DATA Safety Data R410A Toxicity Low In contact with skin Skin contact with the rapidly evaporating liquid may cause tissue chilblains. In case of skin contact with the liquid, warm the frozen tissue with water and call a doctor. Remove contaminated clothing and footwear. Wash the clothing prior to re-use. In contact with eyes Vapours have no effect. Liquid splashes or sprays may cause freeze burns.
2. INSPECTION AND STORAGE At the time of receiving the equipment carefully cross check all the elements against the shipping documents in order to ensure that all the crates and boxes have been received. Inspect all the units for any visible or hidden damage. In the event of shipping damage, write precise details of the damage on the shipper’s delivery note and send immediately a registered letter to the shipper within 48 hours, clearly stating the damage caused.
English 6 SYSAQUA 5. CONTENTS OF PACKAGE 1 SYSAQUA 1 Water filter 1 Bag with the documentation 5.1. OPTIONALS ACCESSORIES Anti-vibration rubber pads Spring pads Isolating valve On opening the carton, check that all the accessories required for installation are present. 6. DIMENSIONS SEE APPENDIX 7. HANDLING 7.1.
SYSAQUA 7 The method of handling depends on the model of SYSAQUA and its final destination. ² Take care to avoid any rough handling or impacts when unloading and moving the appliance. ² Before hoisting into position, test lift to insure stability and balance. Avoid twisting or uneven lifting of the units. ² The units shall be carefully inspected before unit installation to make sure this has not happened. ² ll these sections have been inspected before leaving the factory.
8 SYSAQUA English 7.3.2. HANDLING BY SLINGING Lifting is also possible by slinging. A spreader must be used to prevent damage to the machine edges. Caution Slings must never touch the unit casing of SYSAQUA.
8. TECHNICAL SPECIFICATIONS 8.1.
10 SYSAQUA English 8.2. REFRIGERATION SPECIFICATIONS 8.2.1. REFRIGERANT CIRCUIT DIAGRAM 8.2.2. REFRIGERANT CHARGE SEE APPENDIX Caution This equipment contains fluorinated gas with greenhouse gas effects covered by the Kyoto agreement. The type and quantity of refrigerating fluid per circuit are indicated on the product plate.
SYSAQUA 11 SYSAQUA140 SYSAQUA150 SYSAQUA170 SYSAQUA190 SYSAQUA210 Power supply Maximum current Fuse rating aM Without Total starting current (without Soft starter) pump Total starting current (with Soft starter) Maximum current Fuse rating aM With Total starting current Standard (without Soft starter) pump Total starting current (with Soft starter) Maximum current Fuse rating aM With Total starting current High pressure (without Soft starter) pump Total starting current (with Soft starter) A A 400 V /
English 12 SYSAQUA 9. INSTALLATION Caution The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work or constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or a degradation with dangerous consequences for personnel and property. In such an event, the warranty shall be null and void. Caution The unit base shall be arranged as indicated in the manual.
SYSAQUA 13 When choosing the location for the SYSAQUA, take care to leave sufficient free clearance on all sides to ensure easy access for maintenance work. English 9.2. CLEARANCE 5 000 1 500 WITH BUFFER TANK 1 500 1 500 1 500 5 000 2 000 WITHOUT BUFFER TANK 1 500 1 500 1 500 The minimum free clearance dimensions indicated must be observed to ensure both proper system operation and allow access for maintenance and cleaning.
English 14 SYSAQUA 10. HYDRAULIC LINKS Caution When choosing and installing water pipes, you must consult and observe all current local standards, regulations and instructions. 10.1. MAIN HYDRAULIC CIRCUIT Caution The mains hydraulic circuit will provide a constant water flow on the refrigerating fluid/water plate exchanger and in case of load variation. You must design the pipe network with the minimum number of bends and keep the number of changes in height to the strict minimum.
SYSAQUA 15 To ensure that the system operates correctly you must use suitably sized and properly routed pipes for the hydraulic links between the SYSAQUA and the mains network. Proper operation of the regulation and safety devices is ensured only when the water volume is sufficient. For refrigeration only units, the total volume on the level of the primary water circuit must never below: ² application air conditioning 3.
16 SYSAQUA English 10.6. FROST PROTECTION 10.6.1. WATER LOOP GLYCOLING Caution THE USE OF A GLYCOL-BASED SOLUTION IS THE ONLY EFFECTIVE FROST-PROTECTION MEANS The glycol-based water solution must be sufficiently concentrated to ensure appropriate protection and prevent ice from forming. Take precautions when using non inert MEG antifreeze solutions (Mono Ethylene Glycol) or MPG (Mono Propylene Glycol). With this type of antifreeze solution, corrosion may occur in the presence of oxygen.
SYSAQUA 17 In case of low temperature setpoint or reduced water flow, the water loop must be protected against icing during the operation of the unit. Concentration must comply with the minimum water temperature of the installation. The choice of the type of glycol shall take in consideration the increase of pressure drops. For instance, we recommend to protect a -10°C setpoint down to -18°C. Using MPG, that protection is achieved with a 35% concentration. 10.7.
18 SYSAQUA English 10.8. HEAT INSULATION To guarantee proper energy efficiency and compliance with current standards, water pipes passing through uninhabited zones should be properly lagged to retain heat. To achieve correct insulation with conductivity of 0.04 W/mK, lag the pipes with insulating material with a radial thickness between 25mm and 30 mm. 10.9.
SYSAQUA 19 English 11. WIRING DIAGRAM AND LEGEND 11.1. WIRING DIAGRAM SEE APPENDIX 11.2.
English 20 SYSAQUA 11.2.3.
12. ELECTRICAL CONNECTIONS WARNING Before carrying out any work on the equipment, make sure that the electrical power supply is disconnected and that there is no possibility of the unit being started inadvertently. Non-compliance with the above instructions can lead to injury or death by electrocution. The electrical installation must be performed by a fully qualified electrician, and in accordance with local electrical standards and the wiring diagram corresponding to the unit model.
22 SYSAQUA English Caution Supplying the unit with a line with an unbalance exceeding the acceptable value results in cancelling the warranty. Caution Correction of the excessive centralized power factor (>0.95) may generate transient phenomena dangerous for the motors and contactors of the unit during the start and stop phases. Check instant voltages during these phases. These units are equipped with a local switch used as general terminal board.
13. REGULATION SYSAQUA units are fitted with an electronic control system. It provides the command, control and alarm functions. 13.1. ORDER OF PRIORITY FOR CONTROL SYSTEMS The integrated regulator in the SYSAQUA can be controlled by various interfaces and systems. The order of priority for each drive system is as follows: 1. Timing programming: this scheduling is integrated in the regulator 2. The BMS : the remote supervision transmits it commands according to the communication protocols 3.
24 SYSAQUA English 13.2.2. HOME PAGE The home page is used to quickly display the state of the machine by displaying the following information: Main overview ² Operating mode ² Water return temperature ² Water flow temperature 1/3 Current mode Red. H Entering water T. 42.3°C Leaving water T. 45.2°C 13.2.3. MAIN MENU Pressing the "Info" button displays this screen directly.
SYSAQUA 25 Open the electrical box and check that all circuit breakers are open except for FTC. Before starting up the SYSAQUA for the first time, the "Installation" menu must be configured. 13.3.1. TIME SETTINGS Caution If the date and time are not set, the unit will function in degraded mode or may not even be able to start. Start by configuring the date and time. To do so, switch to the "Installer" or "Maintenance" profile in the "Installation" section.
26 SYSAQUA Define the type and glycol content present in the installation water circuit. Main Menu Status 1/4 Commissioning Services Access Commissioning 1/12 03.02.2016 10:40:05 Language selection Communications Glycol protection Auto change over Water Law Reduced mode Limited capacity Cold OAT protection Small volume protection Calendar Versions Glycol protection 1/2 Type No Glycolconcentr. 0% 1/4 No MEG MPG ethanol Open then reset the FTC circuit breaker to reboot the controller.
EWT 2xBK OAT 1 Configuration The input can be configured with the function values defined below: Control on Commissioning EEV T2 M B3 B2 M T1 B1 M EEV 1/8 Fan Pump Circuit control Contacts D1 D2 dT ret./sup.
28 SYSAQUA English 13.4.4. SELECTING THE OPERATING MODE To launch the unit, the user must select the desired mode in the menu: ² Delegate : the current mode is determined by the BMS or by default by the calendar (refer to the user manual) Main Menu Status 1/4 Status HMI state HMI state HMI mode HMI mode State State from from Mode from Mode from Cooling setp. Cooling setp. Current setp. cool Current Heating setp. setp. cool Heating setp. setp. heat Current Current setp.
13.4.6. WATER LAW The configuration of the different water law settings dynamically matches the setpoint according to the outside temperature. The different parameters below for the water law can be set in the installation menu and by a GTC. Main Menu Status 1/4 Commissioning 1/12 03.02.
English 30 SYSAQUA 13.4.6.2. HEAT MODE The water law replaces the heat mode setpoint with the f function of the OAT outside temperature: ² water law setpoint = f(OAT) Function f is restricted between 20 and 50°C. It is defined by points A, B and C in the graph below. The values indicated are factory values.
SYSAQUA 31 Main Menu Status English 13.4.7. "VARIABLE PRIMARY FLOW” OPTION 1/4 Commissioning Service Configuration Manual control Deice Operation hours Lock out Inputs-Outputs Parameters Archives Services Access 1/8 The "Variable Primary Flow" option is used to modulate the power of the hydraulic pump This modulation is obtained by powering the pump through a frequency inverter. Configuration 1/8 Fan Pump Circuit control Contacts D1 D2 dT ret./sup.
English 32 SYSAQUA 13.4.7.2. CONSTANT SPEED MODE VS CAPACITY The speed of the pump depends on the capacity of the unit. This speed range is determined during commissioning to adjust the power of the pump to the load drops of the installation. Speed set-point 100% Mod. pump max speed Pump configuration 1/13 Pump Single Continuous pump Off Modulation 2 stages Acceleration delay 10 s ----------------------------------------Anti seizing act.
1. Set all units in demand to open all the valves (load = 100%). 2. Set the water pressure setting to a high value (example: 8.0 bar) 3. Check that the output is in line with SYSAQUA requirements. 4. Read the pressure value in the system (example: 3.5 bar). 5. Set the water pressure setting to the read value. When the pressure setting is set, check that the system is operational in the following conditions: ² when in partial load, the pressure is constant.
34 SYSAQUA English 13.5. ALARMS Main overview Trigger all circuit breakers. Silence the alarm. If at least one alarm or warning is in progress, the alarm button flashes. Press the 'Alarm' button to access the latest current alarm. The screen displays the latest alarm activated with a description, the date and time at which it occurred. Alarm list 1/4 Acknowledge 3 + Fault supp.pump: Alarm + Condensing P. circuit 1: Com. fault + Suction T. circuit 1: Com. fault Current mode Red. H Entering water T.
SYSAQUA 35 English 13.6. SCHEDULE The first line displayed shows the current mode at the level of time programming. Main Menu Status 1/4 Commissioning 1/12 03.02.2016 10:40:05 Language selection Communications Glycol protection Auto change over Water Law Reduced mode Limited capacity Cold OAT protection Small volume protection Calendar Versions Commissioning Services Access In the Monday submenu, 6 operating intervals can be selected.
English 36 SYSAQUA 14. COMMISSIONING Caution When performing startup and service, thorough safety precautions shall always be taken. Only qualified individuals should perform these functions. 14.1. PRE-START CHECK LIST Before commissioning the system, you must carry out a certain number of installation checks to ensure that the appliance will operate in the best possible conditions. The following list of checks is not exhaustive and only serves as a minimum reference guide. 1.
SYSAQUA 37 14.2.1. GENERAL Cheek for any unusual noises or vibration in the running components. 14.2.2. PHASE ROTATION PROTECTION If the phase of the power supply are not correct, the phase rotation protection device will prevent the machine from starting. 14.2.3. ELECTRICAL 14.2.3.1. SET POINTS 1. Compressors circuit breaker settings. 2. Pump Circuit Breaker and Fan Circuit breaker settings. NOTE : The outdoor fan motor is equiped with an internal safety device with automatic reset. 14.2.3.2.
38 SYSAQUA English 14.2.5.1. PUMP MANAGEMENT The pump operates as long as the SYSAQUA is not in Off mode. For the double pump option, the pumps never operate simultaneously. The operating priority is given to the first pump motor. The second pump motor backs up the first in the event that it becomes faulty.
17. MAINTENANCE Caution The user is responsible for ensuring that the unit is in perfect working order and that the technical installation and minimum maintenance operations have been performed by a qualified technician in accordance with the procedures described in the present manual. Depending on actual operational constraints and regulatory changes, the installer might recommend increased maintenance operations and more frequent inspections.
40 SYSAQUA English 17.2. PERIODIC TABLE OF SERVICE AND MAINTENANCE TASKS PER COMPONENTS ACTIONS 3 6 12 24 1 month months months months months Recommended inspection and maintenance interval 1 - Casing 1.3 1.4 1.5 Control possible contaminations, damage and/or corrosion. Check the possible presence of water (condensates, leakages,...). Verify thermal insulation aspect Check the state of the anti-vibration pads Check the condition of door gasket. 2.
1 3 6 12 24 month months months months months Recommended inspection and maintenance interval TASKS PER COMPONENTS ACTIONS 3.10 Check filter cleanliness. Clean 3.11 Check that the hydraulic circuit is filled properly 3.12 Check the condition of the expansion tank (presence of excess corrosion, or gas pressure loss) Replace if required. Check the water pump If the unit has not been used for a long time, manually rotate the pump shaft and check that it turns freely.
42 SYSAQUA English 17.3. MAINTENANCE PROCEDURES 17.3.1. REFRIGERANT CIRCUIT This equipment must be submitted to sealing checks minimum once per year, by a professional authorized to perform such an operation. Refer to national requirements for the frequency of these checks. Caution Never use the compressor as a vacuum pump to drain the installation. 17.3.1.1.
SYSAQUA 43 Caution Fin edges are sharp and can cause injury hazard. Avoid contact with them. Condenser coils are composed of copper tubes and aluminium fins. In case of leaks due to damage or shock, the coils must be repaired by one of the authorized Support Centres. To guarantee the best possible operation of the condenser bank, the condenser surface must be maintained as clean as possible, and it must be void of foreign materials (leaves, wires, insects, slag, etc.).
English 44 SYSAQUA 18. TROUBLE SHOOTING Problem Probable cause Solution Unit operates continuously but without generating cooling Insufficient refrigerant fluid charge. Top up the refrigerant fluid charge. Clogged dehumidification filter. Replace the dehumidification filter. Reduced output from one or both circuits Check the compressor valves and change them if necessary. Frozen intake line The overheating setting on the thermostatic pressure relief valve is too low. Increase the setting.
Problem Probable cause Solution Circuit stoppage further to the low pressure thermostat being activated. Presence of a leak. Identify and repair the leak. Insufficient refrigerant fluid charge. Top up the refrigerant fluid charge. Pressostat operating fault. Replace the pressostat. Incorrect operation of the high pressure pressostat. Check the operation of the pressostat. Replace it if required. Outlet valve partially closed. Open the valve. Replace it if required.
English 46 SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO APPENDIX SYSAQUA 190 - 210......................................................................................................XV DIMENSIONS................................................................................................III SYSAQUA WITHOUT PUMP....................................................................................................III SYSAQUA WITH 1 PUMP................................................................................
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO DIMENSIONS DIMENSIONS ABMESSUNGEN DIMENSIONI DIMENSIONES SYSAQUA WITHOUT PUMP 1249 1145 Ø17 2148 152 1249 1145 559 171 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 2804 Ø2"1/2 1100 2210 48 INTLET 2856 WATER OUTLET SYSAQUA III
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO SYSAQUA WITH 1 PUMP 1249 1145 Ø17 2148 152 1249 1145 2804 171 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 700 1100 2210 48 INTLET 2856 IV SYSAQUA WATER OUTLET Ø2"1/2
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO SYSAQUA WITH 2 PUMPS 1249 1145 Ø17 2148 152 1249 1145 171 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 700 2804 Ø2"1/2 1100 2210 48 INTLET 2856 WATER OUTLET SYSAQUA V
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO SYSAQUA WITH 1 PUMP AND BUFFER TANK 1249 1145 Ø17 2148 152 1249 1145 480 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 2804 700 Ø2"1/2 1740 48 2210 864 3666 VI SYSAQUA INTLET OUTLET WATER
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO SYSAQUA WITH 2 PUMPS AND BUFFER TANK 1249 1145 Ø17 2148 152 1249 1145 480 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 2804 700 Ø2"1/2 1740 48 2210 864 3666 INTLET OUTLET WATER SYSAQUA VII
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO REFRIGERANT CIRCUIT DIAGRAM SCHEMA DU CIRCUIT FRIGORIFIQUE KÄLTEKREISLAUFDIAGRAMM SCHEMA DEL CIRCUITO REFRIGERANTE ESQUEMA DEL CIRCUITO FRIGORIFÍCO English M1-1 M1-2 M2-1 M2-2 RV1 RV2 OFA/B OFC/D 3-1 3-2 4-1 4-2 5-1 5-2 6-1 6-2 7-1 7-2 8 circuit 1 circuit 1 circuit 2 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 Compressors 1 Compressors 2 Compressors 1 Comp
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO COOLING ONLY VERSION - SYSAQUA.L 140 TO SYSAQUA.L 150 HP1 FPC1 CDT1 CDT2 OFA OFB FPC2 HP2 OFC OFD OAT M2-1 M2-2 M1-1 M1-2 3-1 CST1 OCT1 4-1 FPE1 WATER FPE2 8 6-1 5-1 3-2 CST2 6-2 5-2 4-2 OCT2 COOLING ONLY VERSION - SYSAQUA.L 170 HP1 FPC1 CDT1 CDT2 OFA OFB FPC2 HP2 OFC OFD OAT M2-1 M2-2 M1-1 M1-2 3-1 CST1 OCT1 4-1 FPE1 WATER FPE2 8 6-1 5-1 3-2 CST2 6-2 5-2 4-2 OCT2 COOLING ONLY VERSION - SYSAQUA.
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO HEAT PUMP VERSION - SYSAQUA.H 140 TO SYSAQUA.H 150 HP1 FPC1 CDT1 CDT2 RV1 OFA OFB CST1 OCT1 HP2 RV2 OAT 4-1 FPE1 WATER 6-1 5-1 OFC OFD M2-1 M2-2 M1-1 M1-2 3-1 FPC2 FPE2 3-2 CST2 8 7-1 7-2 6-2 5-2 4-2 OCT2 HEAT PUMP VERSION - SYSAQUA.
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO HYDRAULIC CIRCUIT DIAGRAM SCHEMA DU CIRCUIT HYDRAULIQUE HYDRAULISCHER SCHALTPLAN SCHEMA CIRCUITALE IDRAULICO ESQUEMA CIRCULAR HIDRÁULICO English Deutsch Français RECOMMENDED INSTALLATION INSTALLATION RECOMMANDEE EMPFOHLENE INSTALLATION CF Connexion flexible CF Connexion flexible CF Schlauchverbindung VV Drain valve VV Vanne de vidange VV Ablassventil VA Globe valve VA Vanne d'arrêt VA Absperrhahn VR Water charging valve VR Vanne de rem
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO WITHOUT PUMP PA EWT CL EWC FT PHE RAG RAG FS CL LWC VD LWT WITH 1 PUMP Installation recommandée VERSION SIMPLE POMPE AQA 1-2 VE MN VR CF VA WPS FT WP PA SS PHE PA RAG RAG MN CF EWT CL EWC WT WPT VA FS CL LWC VD VD LWT VV WITH 2 PUMPS VE MN VR CF WP VA PA WPS FT SS WP VA WPT WT XII SYSAQUA PHE VD RAG RAG FS LWC VD VV EWT PA MN CF CL EWC CL LWT
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO PRESSURE LOSSES PERTE DE CHARGE DE L'ECHANGEUR A PLAQUES DRUCKVERLUST PERDITA DI CARICO PÉRDIDA DE CARGA 1000 900 800 700 600 500 400 300 SYSAQUA 140-150 100 90 80 70 60 50 40 SYSAQUA 170-190-210 30 20 10 9 2 190 240 3 170 8 7 6 5 4 140 150 Pressure loss (kPa) 200 1 1 2 3 4 5 6 7 8 9 10 20 Water flow (m /h) 3 30 40 50 60 70 80 90 100 SYSAQUA XIII
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO HYDRAULIC PUMPS CURVES COURBES DES POMPES HYDRAULIQUES KURVEN VON HYDRAULIKPUMPEN CURVE DELLE POMPE IDRAULICHE CURVAS BOMBAS HIDRÁULICAS STANDARD PUMP SYSAQUA 140 - 150 - 170 200 50 Hz Available pressure (kPa) 180 160 45 Hz 140 120 40 Hz 100 80 35 Hz 60 30 Hz 40 20 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 3 Power Input (kW) 2.5 2 50 Hz 1.5 45 Hz 40 Hz 1 35 Hz 30 Hz 0.
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO SYSAQUA 190 - 210 200 Available pressure (kPa) 180 160 50 Hz 140 45 Hz 120 100 40 Hz 80 35 Hz 60 30 Hz 40 20 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 20 25 Water flow (m3/h) 30 35 40 3.5 Power Input (kW) 3 2.5 50 Hz 2 45 Hz 1.5 40 Hz 1 35 Hz 30 Hz 0.
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO HIGHT PRESSURE PUMP SYSAQUA 140 - 150 - 170 - 190 350 50 Hz Available pressure (kPa) 300 250 45 Hz 200 40 Hz 150 35 Hz 100 30 Hz 50 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 20 25 Water flow (m3/h) 30 35 40 5 4.5 Power Input (kW) 4 3.5 50 Hz 3 2.5 45 Hz 2 40 Hz 1.5 35 Hz 30 Hz 1 0.
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO SYSAQUA 210 400 50 Hz Available pressure (kPa) 350 300 45 Hz 250 40 Hz 200 150 35 Hz 100 30 Hz 50 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 20 25 Water flow (m3/h) 30 35 40 6 Power Input (kW) 5 4 50 Hz 3 45 Hz 40 Hz 2 35 Hz 30 Hz 1 0 0 5 10 15 SYSAQUA XVII
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO WIRING DIAGRAM SCHEMAS ELECTRIQUES STROMLAUFPLANS SCHEMA ELETRICO ESQUEMA ELECTRICO TAKE CARE! These wiring diagrams are correct at the time of publication. Manufacturing changes can lead to modifications. Always refer to the diagram supplied with the product. ATTENTION Ces schémas sont corrects au moment de la publication. Les variantes en fabrication peuvent entraîner des modifications. Reportez-vous toujours au schéma livré avec le produit.
KOF2-H KOF2-L KOF2 KOF1-H KOF1-L KOF1 FTOF2-H FTOF2-L FTOF1-H FTOF1-L FTC R3/4 R1/2 C1-1/1-2 C2-1/2-2 K3/4 K1/2 FT3/4 FT1/2 KA1 QG compresseurs 1 et 2 du circuit 1 compresseurs 1 et 2 du circuit 2 Résistances de carter des compresseurs du circuit 1 Résistances de carter des compresseurs du circuit 2 disjoncteur magnétothermique du circuit de commande disjoncteur magnétothermique de la ventilation extérieure du circuit 1 disjoncteur magnétothermique de la ventilation extérieure du circuit
XX SYSAQUA sécurité interne du moteur de la ventilation extérieure du circuit 1 sécurité interne du moteur de la ventilation extérieure du circuit 2 fuse carrier secondary circuit of T1 additional magneto-thermal circuit breaker of compressors of circuit 1 additional magneto-thermal circuit breaker of compressors of circuit 2 additional magneto-thermal circuit breaker of outdoor fans of circuit 1 additional magneto-thermal circuit breaker of outdoor fans of circuit 1 additional magneto-thermal circuit
CDT2 CDT1 OCT2 OCT1 FPC2 FPC1 FPE2 FPE1 KA1 RV2 RV1 RAG K3/4 K1/2 EEV2 EEV1 HP2 HP1 WPS FS résistance anti-gel vannes d’inversion de cycle du circuit 1(option) vannes d’inversion de cycle du circuit 2(option) contact du module de contrôle d’ordre et de coupure de phases transducteur basse pression du low pressure transducer of circuit 1 circuit 1 transducteur basse pression du low pressure transducer of circuit 2 circuit 2 transducteur haute pression du high pressure transducer of circu
XXII SYSAQUA Français OPTIONS DESIGNATION OPTION POMPE English OPTIONS DESCRIPTION OPTION PUMP OPZIONE POMPA Italiano OPZIONI DENOMINAZIONE WPT Hydraulikdrucksensor hydraulic pressure sensor FDWP1/2 Wasserpumpe circulateur d’eau variateur de fréquence triphasé des Drehstrom-Frequenzumrichter des moteurs des circulateur d’eau Wasserpumpenmotors three phase frequency variator of water pump motor sensore di pressione idraulica variatore di frequenza trifase dei motori del circolatore dell’acqua
fan thermostat of electric panel fan of electric panel EBF OPTION FAN OF ELECTRIC PANEL antifreeze electric heater of drain pan of circuit 1 antifreeze electric heater of drain pan of circuit 2 ventilateur boîtier électrique OPTION VENTILATION DU COFFRET ELECTRIQUE thermostat ventilateur boîtier électrique résistance bac condensats circuit 2 résistance bac condensats circuit 1 thermostat résistances bacs condensats thermostat electric heater of drain pan TEBF RBC2 RBC1 TBC OPTION PACK NORDIQU
2 N K1 FT1 L2 2 2 1 8 L3 7 C1.1 T2 T1 4 6 5 6 5 3 4 3 L1 6 5 1 4 3 BK 1 BU L1 L2 L3 BN BK BK N X T3 GY P-E K2 FT2 SE 4611 SOFT STARTER OPTION QG L2 2 2 1 T2 C1.
FT3 RD BN BK 2 C2.1 T2 T1 4 6 T3 SE 4611 SOFT STARTER OPTION 2 1 K3 5 3 FT4 1 1 5 2 4 3 6 2 1 BK BK BK BU BN BN T2 C2.
SE 4596 SE 4596 L N 230V 2 1 24V L BU 2xBK 24V B1 T8 2xBK OAT P 24...230V POL687 SIEMENS 28 29 ALARM 3A/250V max R1 P FPC1 BK 21 CST1 2xBK LWT 2xBK M T9 M 24V 1 B3 Q12 B2 G0 2 T2 WH X1 Q11 28 Q14 29 WH M T10 GN X2 Q22 GN 5V L Q21 BK 24V Q24 21 24...230V X3 Q33 R2 24 EWT CDT1 A2 K1 A1 BU OCT1 T3 A2 K2 A1 FT1 44 43 M1 S1 24...
SE 4596 L N 230V L BU X1 Q13 27 M Q14 A2 K3 A1 OG BU T1 T4 BK 24...230V X2 A2 K4 A1 CDT2 2xBK POL96 SIEMENS 5V WPT Q33 L Q23 27 GN 24V WH X3 R3 Q34 25 26 X4 R4 T5 M Q44 26 24...230V T2 C L FDWP1/2.53 RD X5 DO1 SE 4596 RD 44 43 FT3 M1 S3 115...230V FT4 M2 190/210 AQA 44 43 FTOF2-L L N 25 27 43 44 8 44 43 VT FTOF2-H VT FDWP1/2.
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO POWER - CIRCUIT 1 TTS XXVIII SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO POWER - CIRCUIT 2 TTS SYSAQUA XXIX
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO CONTROL - CIRCUIT 1 TTS XXX SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO CONTROL - CIRCUIT 2 TTS SYSAQUA XXXI
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO POWER - CIRCUIT 1 - WITHOUT NEUTRAL XXXII SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO POWER - CIRCUIT 2 - WITHOUT NEUTRAL SYSAQUA XXXIII
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO CONTROL - CIRCUIT 1 - WITHOUT NEUTRAL XXXIV SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO CONTROL - CIRCUIT 2 - WITHOUT NEUTRAL SYSAQUA XXXV
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO POWER - CIRCUIT 1 TTS - WITHOUT NEUTRAL XXXVI SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO POWER - CIRCUIT 2 TTS - WITHOUT NEUTRAL SYSAQUA XXXVII
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO CONTROL - CIRCUIT 1 TTS - WITHOUT NEUTRAL XXXVIII SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO CONTROL - CIRCUIT 2 TTS - WITHOUT NEUTRAL SYSAQUA XXXIX
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO XL SYSAQUA
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO START UP FORM / FICHE DE MISE EN SERVICE CUSTOMER INFORMATION: Order number: ..................................................................... Job name: .......................................................................... Contractor: ............................................................................ Installation address: ........................................................ ..................................................................
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO INSTALLATION MEASUREMENTS: Ambient temperature: ....................................................... Ambient humidity: .......................................................... ................................................................................................ ELECTRICAL MEASUREMENTS: Voltage L1-N: ....................................................................... Voltage L1-L2:: .............................................................
IOM AQA 02-N-5GB Systemair AC SAS Route de Verneuil 27570 Tillières-sur-Avre FRANCE & : +33 (0)2 32 60 61 00 6 : +33 (0)2 32 32 55 13 Part number : J38358GB Supersedes : IOM AQA 02-N-4GB As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.