Air Conditioning R32 SYSHP MINI 07-16 Mini Heat Pump Monobloc Series Engineering Data Manual 6,3 to 13,8 kW 6,7 to16,2 kW
CONTENTS Part 1 General Information............................................................................... 3 Part 2 Engineering Data...................................................................................19 Part 3 Installation and Field Settings................................................................
2
Part 1 General Information 1 Mini Heat Pump Monobloc System ............................................................. 4 2 Unit Capacities............................................................................................. 6 3 Nomenclature.............................................................................................. 6 4 System and Design Unit Selection ............................................................... 7 5 Typical Applications ........................................
1 Mini Heat Pump Monobloc System 1.1 System Schematic Figure 1-1.1: System schematic Fan Coil Units Floor Heating ‘3Way Valve Mini Heat Pump Monobloc Collector By-pass Valve Distributor Cold Water Inlet DHWTank Mini Heat Pump Monobloc is an integrated air-to-water space heating, space cooling and domestic hot water heat pump system. The outdoor heat pump system extracts heat from the outdoor air and transfers this heat through refrigerant piping to the plate heat exchanger in the hydronic system.
1.2 System Configurations Mini Heat Pump Monobloc can be configured to run with the electric heater either enabled or disabled and can also be used in conjunction with an auxiliary heat source such as a boiler. The chosen configuration affects the size of heat pump that is required. Three typical configurations are described below. Refer to Figure 1-1.2. Configuration 1: Heat pump only The heat pump covers the required capacity and no extra heating capacity is necessary.
Mini Heat Pump Monobloc 2 Unit Capacities Table 1-2.1: Mini Heat Pump Monobloc uni t capacity range and unit appearances Capacity 5kW 7kW Model M.HP05 DCI MONO M.HP07 DCI MONO 9kW 12kW M.HP12 DCI MONO M.HP09 DCI MONO M.HP12 DCI TRI 14kW 16kW M.HP14 DCI MONO M.HP14 DCI TRI M.HP16 DCI MONO M.HP16 DCI TRI Appearance 3 Nomenclature M.
4 System and Design Unit Selection 4.
4.2 Mini Heat Pump Leaving Water Temperature (LWT) Selection The recommended design LTW ranges for different types of heat emitter are: For floor heating: 30 to 35°C For fan coil units: 30 to 45°C For low temperature radiators: 40 to 50°C 4.
5 Typical Applications 5.1 Space Heating Only The room thermostat is used as a switch. When there is a heating request from the room thermostat, the Mini HP unit operates to achieve the target water temperature set on the user interface. When the room temperature reaches the thermostat’s set temperature, the unit stops. Figure 1-5.
5.2 Space Heating and Domestic Hot Water The room thermostats are not connected to the Mini HP unit but to a motorized valve. Each room’s temperature is regulated by the motorized valve on its water circuit. Domestic hot water is supplied from the domestic hot water tank connected to the Mini HP unit. A bypass valve is required. Figure 1-5.
5.3 Space Heating, Space Cooling and Domestic Hot Water Floor heating loops and fan coil units are used for space heating and fan coil units are used for space cooling. Domestic hot water is supplied from the domestic hot water tank connected to the Mini HP unit. The unit switches to heating or cooling mode according to the temperature detected by the room thermostat. In space cooling mode, the 2-way valve is closed to prevent cold water entering the floor heating loops. Figure 1-5.
5.4 Space Heating and Space Cooling Floor heating loops and fan coil units are used for space heating and fan coil units are used for space cooling. The room thermostats are not connected to the Mini HP unit but are connected to the fan coil units. Figure 1-5.
5.5 Space Heating and Domestic Hot Water (Bivalent) 5.5.1 Auxiliary heat source provides space heating only Figure 1-5.
5.5.2 Auxiliary heat source provides space heating and domestic hot water Figure 1-5.
5.5.3 Auxiliary heat source provides additional heating If the Mini HP unit’s outlet temperature is too low, the auxiliary heat source provides additional heating to raise the water temperature to the set temperature. An additional 3-way valve is required. When the Mini HP unit’s outlet temperature is too low, the 3-way valve is open and the water flows through the auxiliary heat source. When the Mini HP unit’s outlet temperature is high enough, the 3-way valve is closed. Figure 1-5.
5.6 Space Heating Through Floor Heating Loops and Fan Coil Units Dual setpoint function application with or without two thermostat connect to the outdoor unit. The floor heating loops and fan coil units require different operating water temperatures. To achieve these two set points, a mixing station is required. Room thermostats for each zone are optional. Figure 1-5.
5.7 Space Heating and Domestic Hot Water Heating with a solar energy kit Space heating application and domestic hot water heating with a solar energy kit connected to the system; space heating provided by heat pump, domestic hot water heating is provided by heat pump and solar energy kit. Figure 1-5.
18
Part 2 Engineering Data 1 Specifications..............................................................................................20 2 Dimensions and Center of Gravity...............................................................26 3 Piping Diagrams..........................................................................................28 4 Wiring Diagrams ........................................................................................29 5 Capacity Tables.......................................
1 Specifications M.HP05 DCI MONO / M.HP07 DCI MONO / M.HP09 DCI MONO Table 2-1.1: M.HP05/07/09 DCI MONO specifications1 kW Model name Power supply Heating 2 Heating Heating Cooling Cooling M.HP07 DCI MONO M.HP09 DCI MONO 220-240/1/50 4.65 6.65 8.60 Rated input kW 0.93 1.35 1.87 5.00 4.94 4.60 Capacity kW 4.80 6.70 8.60 Rated input kW 1.33 1.88 2.50 3.60 3.57 3.44 Capacity kW 4.65 6.80 8.60 Rated input kW 1.77 2.42 3.13 2.63 2.81 2.75 Capacity kW 4.60 6.45 8.
Table 2-1.1: M.HP05/07/09 DCI MONO specifications1(continued) kW 5 Model name 7 9 M.HP05 DCI MONO M.HP07 DCI MONO M.HP09 DCI MONO MOP A 20.0 20.0 20.0 MCA A 14.1 14.1 14.1 Water side heat exchanger Plate type Water pump Pump head m Expansion tank Volume L Refrigerant 6.0 6.0 2.0 Type R32 6.0 kWCharge kg 2.
M.HP12 DCI MONO / M.HP14 DCI MONO / M.HP16 DCI MONO Table 2-1.2: M.HP12/14/16 DCI MONO specifications1 kW 12 14 16 Model name M.HP12 DCI MONO M.HP14 DCI MONO M.HP16 DCI MONO Power supply Heating2 V/Ph/Hz 220-240/1/50 Capacity kW 12.30 14.10 16.30 Rated input kW 2.56 3.07 3.66 COP Heating3 4.81 4.60 4.45 Capacity kW 12.40 14.10 16.20 Rated input kW 3.52 4.06 4.72 COP Heating4 3.53 3.47 3.43 Capacity kW 11.90 14.20 16.10 Rated input kW 4.28 5.17 5.
Table 2-1.2: M.HP12/14/16 DCI MONO specifications1(continued) kW Model name 12 14 16 M.HP12 DCI MONO M.HP14 DCI MONO M.HP16 DCI MONO MOP A 30.0 30.0 30.0 MCA A 26.8 26.8 26.8 Water side heat exchanger Plate type Water pump Pump head m 7.5 7.5 7.5 Expansion tank Volume L 5 5 5 Refrigerant Type R32 Charge kg 2.
Table 2-1.3: M.HP12/14/16 DCI TRI specifications kW Model name Power supply kW Model name Power supply Heating2 12.30 14.10 16.30 Rated input kW 2.54 3.05 3.63 4.84 4.63 4.49 Capacity kW 12.40 14.10 16.20 Rated input kW 3.45 3.99 4.70 3.59 3.54 3.45 Capacity kW 11.90 14.20 16.10 Rated input kW 4.24 5.10 5.83 2.81 2.79 2.76 Capacity kW 12.20 14.00 15.50 Rated input kW 2.53 3.11 3.63 4.83 4.50 4.27 EER Cooling6 Capacity kW 10.90 12.90 13.
Table 2-1.3: M.HP12/14/16 DCI TRI specifications kW Model name MOP A MCA A Water side heat exchanger 12 14 16 M.HP12 DCI TRI M.HP14 DCI TRI M.HP16 DCI TRI 15.0 15.0 15.0 11.0 11.0 11.0 Plate type Water pump Pump head m 7.5 7.5 7.5 Expansion tank Volume L 5 5 5 Refrigerant Type R32 kWCharge kg 2.8 Standard internal kW 4.5 4.
2 Dimensions and Center of Gravity M.HP05 DCI MONO / M.HP07 DCI MONO / M.HP09 DCI MONO Figure 2-2.1: M.
M.HP12 DCI MONO / M.HP14 DCI MONO /M.HP16 DCI MONO M.HP12 DCI TRI / M.HP14 DCI TRI / M.HP16 DCI TRI Figure 2-2.2: M.
3 Piping Diagrams M.HP05 DCI MONO / M.HP07 DCI MONO / M.HP09 DCI MONO Figure 2-3.1: M.HP05/07/09 DCI MONO piping diagram Accumulator Liquid Tank 8 Strainer 9 Water Side Heat Exchanger (Plate Heat Exchange) 10 Backup heater (optional) 11 Flow switch 12 Discharge gas sensor 13 Outdoor temperature sensor 14 Evaporation sensor in heating (Condenser sensor in cooling) 15 Refrigerant inlet (liquid pipe) temp. sensor 16 Refrigerant outlet (gas pipe) temp. sensor 17 Water outlet temp.
4 Wiring Diagrams M.HP05 DCI MONO / M.HP07 DCI MONO / M.HP09 DCI MONO Figure 2-4.1: M.
Figure 2-4.1: M.
M.HP12 DCI MONO / M.HP14 DCI MONO / M.HP16 DCI MONO Figure 2-4.2: M.
Figure 2-4.2: M.
M.HP12 DCI TRI / M.HP14 DCI TRI / M.HP16 DCI TRI Figure 2-5.3 M.
Figure 2-4.3 M.
5 Capacity Tables 5.1 Heating Capacity Tables Table 2-5.1: M.HP05 DCI MONO heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 °C DB °C WB COP -25.0 - 2.62 1.46 1.81 2.56 1.60 1.60 -20.0 - 3.45 1.48 2.34 3.49 1.66 2.10 3.48 1.86 1.88 -15.0 - 4.61 1.64 2.81 4.23 1.68 2.52 4.03 1.89 2.13 4.10 2.10 1.95 3.76 2.24 1.68 HC PI 60 COP HC PI COP -10 -11 5.52 1.61 3.43 5.14 1.73 2.97 4.66 1.90 2.45 4.55 2.
Table 2-5.3: M.HP07DCI MONO heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP PI COP HC PI 45 COP HC PI 50 COP HC PI 55 COP HC PI 60 °C DB °C WB -25.0 - 3.49 1.99 1.78 3.37 2.11 1.60 -20.0 - 4.59 2.01 2.29 4.59 2.19 2.10 4.52 2.38 1.91 -15.0 - 6.14 2.23 2.76 5.57 2.21 2.52 5.23 2.42 2.16 5.24 2.63 2.00 4.70 2.73 1.72 -10 -11 7.35 2.19 3.36 6.77 2.28 2.97 6.05 2.43 2.49 5.81 2.55 2.28 5.18 2.66 1.95 3.96 2.68 1.50 2.36 1.97 1.24 -7.0 -8.0 7.76 2.
Table 2-5.5: M.HP09 DCI MONO heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 COP HC PI 60 °C DB °C WB COP HC PI COP -25.0 - 4.01 2.20 1.85 3.91 2.47 1.58 -20.0 - 5.28 2.22 2.38 5.34 2.56 2.08 5.32 2.93 1.83 -15.0 - 7.06 2.46 2.87 6.47 2.58 2.50 6.16 2.98 2.07 6.27 3.38 1.86 5.74 3.65 1.57 -10 -11 8.46 2.42 3.49 7.87 2.67 2.95 7.13 2.99 2.38 6.96 3.28 2.12 6.32 3.55 1.78 4.96 3.72 1.36 2.95 2.73 1.
Table 2-5.7: M.HP12 DCI MONO heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 °C DB °C WB COP -25.0 - -20.0 - 8.43 4.05 2.08 8.54 4.35 1.97 8.55 4.66 1.84 -15.0 - 11.26 4.49 2.51 10.35 4.38 2.36 9.89 4.75 2.08 10.11 5.08 1.99 9.30 5.21 1.79 HC PI 60 COP HC PI COP 6.40 4.01 1.62 6.26 4.19 1.49 -10 -11 13.49 4.41 3.06 12.59 4.52 2.78 11.44 4.76 2.40 11.21 4.93 2.28 10.24 5.08 2.02 8.08 5.07 1.62 4.
Table 2-5.9: M.HP14 DCI MONO heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 °C DB °C WB COP -25.0 - -20.0 - 8.85 4.29 2.06 9.11 4.66 1.96 9.28 5.04 1.85 -15.0 - 11.83 4.76 2.48 11.04 4.70 2.35 10.74 5.14 2.09 11.21 5.55 2.02 10.56 5.74 1.84 HC PI 60 COP HC PI COP 6.72 4.25 1.60 6.68 4.49 1.49 -10 -11 14.17 4.68 3.03 13.43 4.85 2.77 12.43 5.16 2.41 12.43 5.38 2.31 11.63 5.60 2.08 9.44 5.63 1.71 5.
Table 2-5.11: M.HP16 DCI MONO heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 °C DB °C WB COP -25.0 - -20.0 - 9.31 4.54 2.05 9.61 4.97 1.93 9.82 5.42 1.82 -15.0 - 12.44 5.04 2.47 11.65 5.02 2.32 11.36 5.53 2.06 11.90 6.01 1.98 11.25 6.26 1.80 HC PI 60 COP HC PI COP 7.07 4.50 1.59 7.05 4.80 1.47 -10 -11 14.90 4.96 3.01 14.16 5.17 2.74 13.14 5.54 2.37 13.19 5.83 2.26 12.39 6.10 2.03 10.10 6.18 1.
Table 2-5.13: M.HP12 DCI TRI heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 °C DB °C WB COP -25.0 - -20.0 - 8.43 3.96 2.13 8.54 4.27 2.00 8.55 4.60 1.86 -15.0 - 11.26 4.39 2.56 10.35 4.31 2.40 9.89 4.69 2.11 10.11 5.04 2.01 9.30 5.19 1.79 HC PI 60 COP HC PI COP 6.40 3.93 1.65 6.26 4.12 1.52 -10 -11 13.49 4.32 3.12 12.59 4.45 2.83 11.44 4.70 2.43 11.21 4.89 2.29 10.24 5.06 2.03 8.08 5.07 1.62 4.
Table 2-5.15: M.HP14 DCI TRI heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 °C DB °C WB COP -25.0 - -20.0 - 8.85 4.23 2.09 9.11 4.61 1.98 9.28 5.00 1.86 -15.0 - 11.83 4.70 2.52 11.04 4.65 2.38 10.74 5.10 2.11 11.21 5.52 2.03 10.56 5.73 1.84 HC PI 60 COP HC PI COP 6.72 4.19 1.62 6.68 4.45 1.50 -10 -11 14.17 4.62 3.07 13.43 4.79 2.80 12.43 5.11 2.43 12.43 5.36 2.32 11.63 5.58 2.08 9.44 5.63 1.71 5.
Table 2-5.15: M.HP16 DCI TRI heating capacity - peak values1 LWT (°C) Outdoor air temp. 30 HC PI 35 COP HC PI 40 COP HC PI 45 COP HC PI 50 COP HC PI 55 °C DB °C WB COP -25.0 - -20.0 - 9.31 4.47 2.08 9.61 4.91 1.96 9.82 5.37 1.83 -15.0 - 12.44 4.96 2.51 11.65 4.95 2.35 11.36 5.48 2.07 11.90 5.97 1.99 11.25 6.24 1.80 HC PI 60 COP HC PI COP 7.07 4.43 1.62 7.05 4.74 1.49 -10 -11 14.90 4.88 3.06 14.16 5.11 2.77 13.14 5.50 2.39 13.19 5.80 2.28 12.39 6.08 2.04 10.10 6.18 1.
5.2 Cooling Capacity Tables Table 2-5.21: M.HP05 DCI MONO cooling capacity Outdoor air temp. LWT (°C) 25 PI 0.8 0.8 0.7 0.6 0.6 0.5 0.5 0.4 0.4 0.3 0.3 °C DB CC EER CC 45 3.7 4.59 3.6 40 4.7 6.27 4.6 35 5.3 7.57 5.2 30 5.4 8.51 5.4 25 5.4 9.16 5.3 20 5.1 9.59 5.0 15 4.7 9.92 4.6 10 4.3 10.31 4.3 5 4.0 11.05 4.0 0 3.9 12.60 3.8 -5 4.0 11.86 4.0 Abbreviations: LWT: Leaving water temperature (°C ) CC: Total cooling capacity (kW) PI: Power input (kW) 22 PI EER CC 1.0 3.70 3.6 0.9 5.06 4.6 0.9 6.10 5.1 0.
Table 2-5.24: M.HP12 DCI MONO cooling capacity Outdoor air temp. LWT (°C) 25 PI EER CC 2.1 4.40 8.9 1.9 6.01 11.3 1.8 7.25 12.7 1.7 8.16 13.1 1.5 8.78 12.9 1.4 9.19 12.2 1.2 9.51 11.3 1.1 9.88 10.4 0.9 10.59 9.7 0.8 12.08 9.4 0.9 11.64 9.7 °C DB CC 45 9.2 40 11.7 35 13.0 30 13.5 25 13.3 20 12.6 15 11.7 10 10.7 5 10.0 0 9.7 -5 10.0 Abbreviations: LWT: Leaving water temperature (°C ) CC: Total cooling capacity (kW) PI: Power input (kW) 22 PI EER 2.5 3.63 2.3 4.96 2.1 5.98 2.0 6.72 1.8 7.24 1.6 7.58 1.4 7.
Table 2-5.27: M.HP12 DCI TRI cooling capacity Outdoor air temp. LWT (°C) 25 PI EER CC 2.1 4.40 8.9 1.9 6.01 11.3 1.8 7.25 12.7 1.7 8.16 13.1 1.5 8.78 12.9 1.4 9.19 12.2 1.2 9.51 11.3 1.1 9.88 10.4 0.9 10.59 9.7 0.8 12.08 9.4 0.9 11.64 9.7 °C DB CC 45 9.2 40 11.7 35 13.0 30 13.5 25 13.3 20 12.6 15 11.7 10 10.7 5 10.0 0 9.7 -5 10.0 Abbreviations: Tamb: Outdoor air temperature (°C) LWT: Leaving water temperature (°C ) CC: Total cooling capacity (kW) PI: Power input (kW) 22 PI EER 2.5 3.63 2.3 4.96 2.1 5.
6 Operating Limits Figure 2-6.1: Heating operating limits1 Abbreviations: T4: Outdoor temperature (°C) T1: Leaving water temperature (°C) Notes: 1. Shaded areas indicate no heat pump operation (backup electric heater or auxiliary heat source only) Figure 2-6.2: Cooling operating limits Abbreviations: T4: Outdoor temperature(°C) T1: Leaving water temperature (°C) Notes: 1. The maximum operating temperature of the 5/7/9kW model is 43°C. Figure 2-6.
7 Hydronic Performance M.HP05 DCI MONO / M.HP07 DCI MONO / M.HP09 DCI MONO Figure 2-7.1: M.HP05/07/09 DCI MONO hydronic performance1 70 III 240V 220V 60 50 ESP (kPa) 40 II 30 20 I 10 0 0 0.5 1 1.5 Water flow rate (m3/h) Abbreviations: ESP: External static pressure Notes: 1. I, II and III indicate water pump speed: I: Low; II: Medium; III: High. 48 48 2 2.
M.HP12 DCI MONO / M.HP14 DCI MONO / M.HP16 DCI MONO M.HP12 DCI TRI / M.HP14 DCI TRI / M.HP16 DCI TRI Figure 2-7.2: M.HP12/14/16 DCI MONO/TRI hydronic performance1 90 220V III 80 240V 70 60 ESP (kPa) 50 II 40 30 I 20 10 0 0 0.5 1 1.5 2 2.5 3 3.5 Water flow rate (m3/h) Abbreviations: ESP: External static pressure Notes: 1. I, II and III indicate water pump speed: I: Low; II: Medium; III: High.
8 Sound Levels 8.1 Overall Table 2-8.1: Sound pressure levels1 Model name dB(A)2 M.HP05 DCI MONO 48.8 M. HP07 DCI MONO 52.3 M.HP09 DCI MONO 54.5 M.HP12 DCI MONO 57.6 M.HP14 DCI MONO 58.0 M.HP16 DCI MONO 58.1 M.HP12 DCI TRI 57.2 M.HP14 DCI TRI 58.1 M.HP16 DCI TRI 59.0 Notes: 1. Sound pressure level is measured at a position 1m in front of the unit and (1+H)/2m (where H is the height of the unit) above the floor in a semi-anechoic chamber.
8.2 Octave Band Levels Figure 2-8.2: M.HP05 DCI MONO octave band levels 120 120 110 Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 12°C, LWT 7°C Octave band sound pressure level (dB(A) 110 100 100 90 NR-90 90 80 80 70 NR-90 NR-80 NR-80 NR-70 70 60 60 50 NR-70 NR-60 50 40 40 30 30 20 20 10 10 0 0 -10 -10 31.5 31.5 Heating in rated frequency Outdoor air temperature 7°C DB, 85% R.H.; EWT 30°C, LWT 35°C .
Octave band sound pressure level (dB(A) Figure 2-8.4: M.HP09 DCI MONO octave band levels 120 Cooling in rated frequency Outdoor 110 120 100 110 90 100 80 90 70 80 60 70 50 60 40 50 30 40 20 30 10 20 0 10 -10 0 31.5 air temperature 35°C DB; EWT -10 31.
Figure 2-8.6: M.HP14 DCI MONO octave band levels Cooling in rated frequency Octave band sound pressure level (dB(A) 120 Outdoor air temperature 110 120 100 110 90 100 80 90 70 80 60 70 50 60 40 50 30 40 20 30 10 20 0 10 -10 0 31.5 -10 31.
Figure 2-8.8: M.HP12 DCI TRI octave band levels Cooling in rated frequency 120 Outdoor air temperature 110 35°C DB; EWT 12°C, LWT 7°C Octave band sound pressure level (dB(A) 100 90 NR-90 NR-90 80 NR-80 NR-80 70 NR-70 NR-70 60 NR-60 NR-60 50 NR-50 NR-50 40 NR-40 NR-40 30 Heating in rated frequency Outdoor air temperature 7°C DB, 85% R.H.; EWT 30°C, LWT 35°C . Heating in rated frequency Outdoor air temperature 7°C 20 NR-30 NR-30 DB, 85% R.H.; EWT 10 NR-20 NR-20 47°C, LWT 55°C.
Figure 2-8.10: M.HP16 DCI TRI octave band levels Cooling in rated frequency 120 Outdoor air temperature Octave band sound pressure level (dB(A) 110 35°C DB; EWT 12°C, LWT 7°C 100 90 NR-90 80 70 60 50 Outdoor air temperature NR-70 7°C DB, 85% R.H.; EWT 30°C, NR-60 LWT 35°C . NR-50 40 Heating in rated frequency NR-80 Heating in rated frequency NR-40 Outdoor air temperature 7°C 20 NR-30 DB, 85% R.H.; EWT 10 NR-20 47°C, LWT 55°C. 0 NR-10 30 -10 31.
9 Accessories 9.1 Standard accessories Table 2-9.1: Standard accessories Quantity M.HP12 DCI MONO Name Shape M.HP05 DCI MONO M.HP07 DCI MONO M.HP09 DCI MONO M.HP14 DCI MONO M.HP16 DCI MONO M.HP12 DCI TRI M.HP14 DCI TRI M.
Part 3 Installation and Field Settings 1 Preface to Part 3 ........................................................................................58 2 Installation .................................................................................................59 3 Water Pipework .........................................................................................64 4 Electrical Wiring .........................................................................................68 5 DIP Switch Settings ....
1 Preface to Part 3 1.1 Notes for Installers Boxes The information contained in this Engineering Data Book may primarily be of use during the system design stage of a Mini Heat Pump Monobloc project. Additional important information which may primarily be of use during field installation has been placed in boxes, such as the example below, titled “Notes for installers”.
2 Installation 2.1 Acceptance and Unpacking Notes for installers When units are delivered check whether any damage occurred during shipment. If there is damage to the surface or outside of a unit, submit a written report to the shipping company. Check that the model, specifications and quantity of the units delivered are as ordered. Check that all accessories ordered have been included. Retain the Owner’s Manual for future reference. 2.
2.3 Placement Considerations Placement of the outdoor unit should take account of the following considerations: Outdoor units should not be exposed to direct radiation from a high-temperature heat source. Outdoor units should not be installed in positions where dust or dirt may affect heat exchangers. Outdoor units should not be installed in locations where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.
2.5 Cold Climate Installation In cold climate locations installation should take account of the following considerations: Never install the unit at a site where the suction side may be exposed directly to wind. To prevent exposure to wind, install a baffle plate on the air discharge side of the unit. To prevent exposure to wind, install the unit with its suction side facing the wall. In areas of heavy snowfall, a canopy should be installed to prevent snow entering the unit.
2.8 Drainage Drainage ditch should be provided to allow drainage of condensate that may form on the air side heat exchanger when the unit is running in heating mode or domestic hot water mode. The drainage should ensure that condensate is directed away from roadways and footpaths, especially in locations where the climate is such that condensate may freeze. Figure 3-2.6: 5/7/9kW models drainage hole Drain hole Thisdrain holeiscovered by rubber plug.
Figure 3-2.9: Installation with obstacles behind the unit ≥500mm ≥20mm ≥300mm 2.9.2 Installation in rows Table 3-2.3: Single row installation spacing requirements Figure 3-2.10: Single row installation <1/2 H B2 H A C B1 Figure 3-2.11: Multi-row installation Model name A (mm) B1 (mm) B2 (mm) C (mm) M.HP05 DCI MONO M.HP07 DCI MONO M.HP09 DCI MONO ≥1500 ≥500 ≥150 ≥300 M.HP12 DCI MONO M.HP14 DCI MONO M.HP16 DCI MONO M.HP12 DCI TRI M. HP14 DCI TRI M.
3 Water Pipework 3.1 Water Circuit Checks Mini Heat Pump Monobloc units are equipped with a water inl et and outlet for connection to a water circuit. Mini Heat Pump Monobloc units should only be connected to closed water circuits. Connection to an open water circuit would lead to excessive corrosion of the water piping. Only materials complying with all applicable legislation should be used. Before continuing installation of the unit, check the following: The maximum water pressure ≤ 3 bar.
To determine the maximum allowed water volume in the entire circuit, proceed as follows: Determine the calculated pre-pressure (Pg) for the corresponding maximum water volume using the Figure 3-3.1. Figure 3-3.1: Maximum water volume 2.8 A1: S ystem without glycol for 1-phase 12~16kW and 3-phase 12~16kW unit A2: System without glycol for the 5/7/9kW unit Pressure (bar) 2.3 1.8 1.3 A1 A2 0.8 0.
When using non-copper metallic piping, be sure to insulate the two kind of materials from each other to prevent galvanic corrosion. For copper is a soft material, use appropriate tools for connecting the water circuit. Inappropriate tools will cause damage to the pipes 3.4 Water Circuit Anti-freeze Protection Ice formation can cause damage to the hydronic system. As the outdoor unit may be exposed to sub-zero temperatures, care must be taken to prevent freezing of the system.
That in case of an installation with a domestic hot water tank, only the use of propylene glycol is allowed. In other installations the use of ethylene glycol is fine.
4 Electrical Wiring 4.1 General Notes for installers Caution All installation and wiring must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation. Electrical systems should be grounded in accordance with all applicable legislation. Overcurrent circuit breakers and residual-current circuit breakers (ground fault circuit interrupters) should be used in accordance with all applicable legislation.
Make sure no external pressure is applied to the terminal connectors. When installing the ground fault circuit interrupter make sure that it is compatible with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the ground fault circuit interrupter This unit is equipped with an inverter. Installing a phase advancing capacitor not only reduce the power factor improvement effect, but also may cause abnormal heating of the capacitor due to high frequency waves.
Figure 3-4.
Table 3-4.1: Wiring requirements 1 Solar energy kit signal wire AC Required number of conductors 2 2 User interface wire AC 5 200mA 0.75-1.25mm2 3 Room thermostat wire AC 2 or 3 200mA 0.75mm2 4 Auxiliary heating source control wire - 2 200mA 0.75mm2 5 Temperature sensor wire2 DC 2 9 DHW pump control wire AC 2 200mA 0.75mm2 10 Motorized 2-way valve control wire AC 2 200mA 0.75mm2 11 Motorized 3-way valve control wire AC 2 or 3 200mA 0.
5 DIP Switch Settings DIP switches S1 and S2 on the hydronic system main PCB should be used to specify refrigerant piping length and to specify whether certain components have or have not been installed. Refer to Table 3-5.1 and to the Mini Heat Pump Monobloc units Service Manual, Part 4, 2.2 “Main PCB for Hydronic System”. Table 3-5.
7 User Interface Field Settings 7.1 Introduction During installation, the Mini Heat Pump Monobloc units’ settings and parameters should be configured by the installer to suit the installation configuration, climate conditions and end-user preferences. The relevant settings are accessible and programmable through the FOR SERVICEMAN menu on the Mini Heat Pump Monobloc units’ user interface.
7.2 Menu Structure 1 DHW MODE SETTING 2 COOL MODE SETTING 3 HEAT MODE SETTING 4 AUTO MODE SETTING 5 TEMP. TUPE SETTING 6 ROOM THERMOSTAT 7 OTHER HEATING SOURECE 8 HOLIDAY AWAY MODE SETTING 9 SERVICE CALL SETTING 10 RESTORE FACTORY SETTINGS 11 TEST RUN 12 SPECIAL FUNCTION 13 AUTO RESTART 1.1 1.2 1.3 1.4 1.
7.3 FOR SERVICEMAN Menu FOR SERVICEMAN allows installers to input the system configuration and set the system parameters. To enter FOR SERVICEMAN, go to MENU > FOR SERVICEMAN. Figure 3-7.2: FOR SERVICEMAN password screen Enter the password, using ◄ ► to navigate between digits and using ▼ ▲ to adjust the numerical values, and then press OK. The password is 234. Refer to Figure 3-7.2. Figure 3-7.2: FOR SERVICEMAN password screen 7.4 DHW MODE SETTING Menu 7.4.1 DHW MODE SETTING menu overview Figure 3-7.
Figure 3-7.5 illustrates the operation of the heat pump and immersion heater in DHW mode. If the DHW tank water temperature (T5) is less than the minimum of the DHW set temperature (T5S) and the heat pump leaving water temperature operating limit (T5stop) (refer to Figure 2-6.3 in Part 2, 6 “Operating Limits”) less dT5_ON (refer to Part 3, 7.4.2 “DHW MODE Menu”), the heat pump starts providing heated water to the DHW tank. After t_TBH_delay (refer to Part 3, 7.4.
T4DHWMAX sets the ambient temperature above which the heat pump Figure 3-7.8: T4DHWMAX and T4DHWMIN will not operate in DHW mode. The highest value that T4DHWMAX can take is 43°C, which is the DHW mode upper ambient temperature Heat by TBH or AHS Heat by heat pump operating limit of the heat pump. T4DHWMIN sets the ambient temperature below which the heat pump will not operate in DHW mode.
To enter the DHW PRIORITY menu, navigate to the DHW MODE SETTING menu, scroll to YES on the DHW PRIORITY line and press OK. t_DHWHP_MAX sets the maximum length of time that the heat pump will run in DWH Figure 3-7.12: DHW PRIORITY menu mode before switching to space heating mode or space cooling mode if a requirement for space heating/cooling modes exists.
DISINFECT sets whether or not the DHW pump operates during the DHW tank disinfection operation. PUMP RUNNING TIME sets the length of time the pump runs for at each of the user-specified start times on the DHW PUMP tab on the DOMESTIC HOT WATER (DHW) menu, if TIMER RUNNING is enabled. 7.5 COOL MODE SETTING Menu MENU > FOR SERVICEMAN > COOL MODE SETTING In COOL MODE SETTING the following parameters should be set. Figure 3-7.15: COOL MODE SETTING menu COOL MODE enables or disables cooling mode.
t_INTERVAL_C sets the cooling mode compressor re-start delay. When the compressor stops running, it will not re-start until at least t_INTERVAL_C minutes have elapsed. 7.6 HEAT MODE SETTING Menu MENU > FOR SERVICEMAN > HEAT MODE SETTING Figure 3-7.19: HEAT MODE SETTING menu In HEAT MODE SETTING the following parameters should be set. HEAT MODE enables or disables heating mode.
dTSH sets the temperature difference between the actual room temperature (Ta) Figure 3-7.23: dTSH and set room temperature (TS) above which the heat pump provides heated water to the space heating terminals. When TS – Ta ≥ dTSH the heat pump provides heated HEAT water to the space heating terminals and when Ta ≥ TS the heat pump does not provide heated water to the space heating terminals. Refer to Figure 3-7.23. dTSH is Note: only relevant if YES is selected for ROOM TEMP in the TEMP. TYPE SETTING menu.
ROOM TEMP. sets whether space heating/cooling modes are controlled according to the room temperature detected by the temperature sensor in the Mini Heat Pump Monobloc user interface. If YES is selected, the user is able to set the room temperature set temperature on the user interface’s main screen. If YES is selected for both WATER FLOW TEMP. and ROOM TEMP.
AHS sets whether or not the system has an additional heating source and, if it does, whether or not it should be used. If the system does not have an additional heating source, select NON. If the system has an additional heating source and the Mini Heat Pump Monobloc unit should be able to control it, select YES. If the system has an additional heating source but the Mini Heat Pump Monobloc unit should not be able to control it, select NON. SOLAR ENERGY sets whether or not a solar energy kit is installed.
7.10.3 ADDITIONAL HEATING SOURCE MENU MENU > FOR SERVICEMAN > OTHER HEATING SOURCE > ADDITIONAL HEATING SOURCE Figure 3-7.32: ADDITIONAL HEATING SORUCE menu To enter the ADDITIONAL HEATING SOURCE menu, navigate to the OTHER HEATING SOURCE menu, scroll to YES on the ADDITIONAL HEATING SOURCE line and press OK. T4_AHS_ON sets the ambient temperature below which the additional heating source is used. If the ambient temperature is above T4_ASH_ON, the additional heating source is not used.
7.11 HOLIDAY AWAY SETTING Menu MENU > FOR SERVICEMAN > HOLIDAY AWAY SETTING The HOLIDAY AWAY SETTING menu settings are used to set the outlet water Figure 3-7.35: HOLIDAY AWAY SETTING menu temperature to prevent water pipes freezing when away from home in cold weather seasons. In HOLIDAY AWAY SETTING the following parameters should be set. T1S_H.A._H sets the heat pump’s leaving water set temperature for space heating mode when in holiday away mode. T5S_H.
Figure 3-7.38: TEST RUN start screen and TEST RUN menu 7.14.2 POINT CHECK MENU MENU > FOR SERVICEMAN > TEST RUN > POINT CHECK The POINT CHECK menu is used to check the operation of individual components. Use ▼▲ to scroll to the components you want to check and press ON/OFF to toggle the on/off state of the component. If a valve does not turn on/off when its on/off state is toggled or if a pump/heater does not operate when turned on, check the component’s connection to the hydronic system main PCB.
7.14.4 CIRCULATION PUMP RUNNING OPERATION MENU > FOR SERVICEMAN > TEST RUN > CIRCULATION PUMP RUNNING Figure 3-7.42: CIRCULATION PUMP RUNNING display The CIRCULATION PUMP RUNNING operation is used to check the operation of the circulation pump. When the circulation pump running operation starts, all running components stop. 60 secs later, the 3-way valve opens and the 2-way valve closes. After a further 60 secs PUMPI starts.
On systems with no auxiliary heat source and no backup electric heater, the heat pump will then operate until the water temperature rises to the set temperature or the heat mode running operation is exited by pressing OK. If any error code is displayed during the cool mode running operation, the cause should be investigated. Refer to Part 3, 9 “Error Code table”. 7.14.7 DHW MODE RUNNING operation Figure 3-7.
7.15.3 PREHEATING FOR FLOOR Figure 3-7.48: Preheating for floor menu MENU > FOR SERVICEMAN > SPECIAL FUNCTION > PREHEATING FOR FLOOR During initial start-up and when water temperature is low, it is important that the water is heated gradually. Or it may result in concrete floors cracking due to rapid temperature change. T1S sets the heat pump’s leaving water set temperature in preheating for floor mode.
7.15.4 FLOOR DRYING UP MENU > FOR SERVICEMAN > SPECIAL FUNCTION > FLOOR DRYING UP For newly-installed under-floor heating systems, floor drying up mode can be used to remove moisture from the floor slab and subfloor to prevent warping or rupture of the floor during floor heating operation. There are three phases to the floor drying up operation: Figure 3-7.51: FLOOR DRYING UP menu Phase 1: gradual temperature increase from a starting point of 25°C to the peak temperature.
8 Climate Related Curves Figure 3-8.1: WEATHER TEMP. SET menu The climate related curves can be selected in the user interface, MENU > PRESET TEMPERATURE > WEATHER TEMP. SET. The curves for heating mode and ECO heating mode are the same but the default curve is curve 4 in heating mode, while in ECO mode, the default curve is curve 6. The curves for cooling mode and ECO cooling mode are the same but the default curve is curve 4 in cooling mode, while in ECO mode, the default curve is curve 6.
Figure 3-8.3: High temperature curves for heating mode1 Leaving water set temperature (°C ) 58 58 T1s(°C) T1s(°C) 53 53 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 48 48 43 43 38 38 -25 -25 33 -5 33 -5 -15 -15 5 5 15 15 25 25 35 35 T4(℃) T4(℃) Outdoor ambient temperature (°C ) Notes: 1. It only has the curves of the low temperature setting for heating, if the high temperature is set for heating. 2. Curve 4 is default in high temperature heating mode and curve 6 is default in ECO mode. Figure 3-8.
Figure 3-8.5: High temperature curves for cooling mode1 27 T1s(°C) Leaving water set temperature (°C ) 25 1 23 2 3 4 21 5 6 19 7 8 17 -5 15 5 15 25 35 45 T4(℃) Outdoor ambient temperature (°C ) Notes: 1. It only has the curves of the low temperature setting for cooling, if the high temperature is set for cooling. 2. Curve 4 is default in high temperature cooling mode and curve 6 is default in ECO mode.
9 Error Code Table Table 3-9.
Table 3-9.
Tel. +39 0362 680 1 Fax +39 0362 680 693 www.systemair.com As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Systemair · EDM SYSHP MINI - S-2GB/03.