ELM AQA 01 S 3GB
Table Of Contents
English
13SYSAQUA
Rated heat output (*) Prated 118 kW
Seasonal space heating energy
efciency
h
s
131 %
Declared capacity for heating for part load at indoor
temperature 20 °C and outdoor temperature T
j
Declared coefcient of performance or primary
energy ratio for part load at indoor temperature 20
°C and outdoor temperature T
j
T
j
=-7 °C Pdh 84.09 kW T
j
=-7 °C COPd 2.76
T
j
=+2 °C Pdh 96.78 kW T
j
=+2 °C COPd 3.33
T
j
=+7 °C Pdh 50.82 kW T
j
=+7 °C COPd 4.54
T
j
=+12 °C Pdh 57.62 kW T
j
=+12 °C COPd 5.28
T
j
= bivalent temperature Pdh 89.02 kW T
j
= bivalent temperature COPd 3.05
T
j
=-15 °C Pdh 72.81 kW T
j
=-15 °C COPd 2.26
Bivalent temperature T
biv
-3.5 °C operation limit temperature TOL -20 °C
Cycling interval capacity for heating Pcych kW Cycling interval efficiency COPcyc
Degradation co-efficient (**) Cdh 0.9 Heating water operating limit temperature WTOL 55 °C
Power consumption in modes other than active
mode
Supplementary heater
Off mode P
OFF
kW Rated heat output Psup kW
Thermostat-off mode P
TO
0.789 kW Type of energy input
Standby mode P
SB
0.173 kW
Crankcase heater mode P
CK
0.173 kW
Other items
Capacity control Staged Rated air flow rate, outdoors
42 000
m
3
/h
Sound power level, indoors/
outdoors
L
WA
Annual energy consumption Q
HE
72 485
kWh
Model(s):
SYSAQUAH 125
Air-to-water heat pump:
yes
Water-to-water heat pump:
no
Brine-to-water heat pump:
no
Low-temperature heat pump:
no
Equipped with a supplementary heater:
no
Heat pump combination heater:
no
Parameters shall be declared for medium-temperature application, except for low-temperature heat
pumps. For low- temperature heat pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Contact details:
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is
equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(T
j
).
(**) If Cdh is not determined by measurement then the default degradation coefcient is Cdh = 0.9.
Systemair AC SAS
Route de Verneuil
27570 Tillières-sur-Avre
FRANCE