ELM AQA 01 S 3GB
Table Of Contents
English
2 SYSAQUA
Rated heat output (*) Prated 19 kW
Seasonal space heating energy
efciency
h
s
132 %
Declared capacity for heating for part load at indoor
temperature 20 °C and outdoor temperature T
j
Declared coefcient of performance or primary
energy ratio for part load at indoor temperature 20
°C and outdoor temperature T
j
T
j
=-7 °C Pdh 13.4 kW T
j
=-7 °C COPd 2.60
T
j
=+2 °C Pdh 15.7 kW T
j
=+2 °C COPd 3.17
T
j
=+7 °C Pdh 12.2 kW T
j
=+7 °C COPd 4.66
T
j
=+12 °C Pdh 15.6 kW T
j
=+12 °C COPd 4.73
T
j
= bivalent temperature Pdh 14.3 kW T
j
= bivalent temperature COPd 2.97
T
j
=-15 °C Pdh 11.3 kW T
j
=-15 °C COPd 1.95
Bivalent temperature T
biv
-4.0 °C operation limit temperature TOL -20 °C
Cycling interval capacity for heating Pcych kW Cycling interval efficiency COPcyc
Degradation co-efficient (**) Cdh 0.9 Heating water operating limit temperature WTOL 55 °C
Power consumption in modes other than active
mode
Supplementary heater
Off mode P
OFF
kW Rated heat output Psup kW
Thermostat-off mode P
TO
0.208 kW Type of energy input
Standby mode P
SB
0.068 kW
Crankcase heater mode P
CK
0.068kW
Other items
Capacity control Staged Rated air flow rate, outdoors
9 000
m
3
/h
Sound power level, indoors/
outdoors
L
WA
75 dB Annual energy consumption Q
HE
11 594
kWh
Model(s):
SYSAQUAH 20
Air-to-water heat pump:
yes
Water-to-water heat pump:
no
Brine-to-water heat pump:
no
Low-temperature heat pump:
no
Equipped with a supplementary heater:
no
Heat pump combination heater:
no
Parameters shall be declared for medium-temperature application, except for low-temperature heat
pumps. For low- temperature heat pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Contact details:
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is
equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(T
j
).
(**) If Cdh is not determined by measurement then the default degradation coefcient is Cdh = 0.9.
Systemair AC SAS
Route de Verneuil
27570 Tillières-sur-Avre
FRANCE