RDR CAV Controller
/16 | RDR Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ordering Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Technical Parameters Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
/16 | RDR Description RDR is a constant air volume flow controller with mechanical type of operation (no need for auxiliary energy or actuation). It is intended to control the constant air flow independently of the duct air pressure in the range of 50 Pa to 250 Pa. The constant air flow value can be set by a shifting dial within a range dependent on the size and configuration of the product. The cartridge type casing fits into the circular ducts of 80 mm up to 250 mm in diameter.
/16 | RDR Product Parts Components of RDR Legend 1 Sleeve with lip seal 2 Shim (according to the airflow) 3 Regulator casing 4 Piece of regulation 5 Air flow setting and fixing screw
/16 | RDR Dimensions
/16 | RDR Ordering Codes RDR - Size øD - Air flow range Vmin - Vmax Example of the Ordering Code RDR-125/50-100 Constant air volume controller with øD size 125 and air flow range adjustable from 50 m³/h to 100 m³/h
/16 | RDR Technical Parameters Legends Ps Pa qv 3 Pressure drop m /h, l/s Air flow volume LWA dB(A) A-weighted total radiated sound power level LpA dB(A) A-weighted total sound pressure level expressed for 10 m2 room absorption area LW dB Non weighted total sound power level A-weighted total sound power level LWA and non-weighted octave band sound power level LW dependent on air flow q v and pressure drop Ps RDR-80/15-50 RDR-100/15-50 Pressure drop & sound power level (A-weighted) Pre
/16 | RDR RDR-100/50-100 RDR-125/15-50 Pressure drop & sound power level (A-weighted) Pressure drop & sound power level (A-weighted) 15 Pa 20 25 l/s 6 Pa 40 dB(A) 240 45 dB(A) 240 200 200 35 dB(A) 160 40 dB(A) 160 120 120 35 dB(A) 80 8 10 12 l/s 45 dB(A) 30 dB(A) 80 30 dB(A) 25 dB(A) 50 60 70 80 90 100 m³/h 20 30 40 RDR-125/50-100 RDR-125/100-180 Pressure drop & sound power level (A-weighted) Pressure drop & sound power level (A-weighted) 15 Pa 240 20 25 l/s Pa
/16 | RDR RDR-150/180-300 RDR-160/50-100 Pressure drop & sound power level (A-weighted) Pressure drop & sound power level (A-weighted) Pa 50 60 70 80 l/s 52.
/16 | RDR RDR-200/300-500 RDR-250/180-300 Pressure drop & sound power level (A-weighted) Pressure drop & sound power level (A-weighted) 90 Pa 100 110 52.
/16 | RDR Installation
/16 | RDR
/16 | RDR Maintenance No maintenance is required for the product.
/16 | RDR Transport, Storage and Operation
/16 | RDR Supplement Any deviations from the technical specifications contained herein and the terms should be discussed with the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these changes do not affect the quality of the product and the required parameters. Current information on all products is available on design.systemair.com.
Systemair DESIGN • 2021-02-09 • HandBook_RDR_en-GB • 42CE3F56-638D-4D82-B230-110EEBBE79C6