IMO AR 315DV SILEO

Operating instructions
4. CONNECTION AND STARTUP
4.1 Mechanical connection
CAUTION
Cutting and crushing hazard when removing device
from packaging
Blades can bend
Carefully remove the device from its packaging, by the fan
housing. Strictly avoid shocks.
Wear safety shoes and cut-resistant safety gloves.
NOTE
Damage to the device from vibration
Bearing damage, shorter service life
The fan must not be subjected to force or excessive vibration
from sections of the installation. #If the fan is connected to air
ducts, the connection should be isolated from vibration, e.g.
using compensators or similar elements. #Ensure stress-free
attachment of the fan to the substructure.
; Check the device for transport damage. Damaged devices are not to
be installed.
; Install the undamaged device in accordance with your application.
CAUTION
Possible damage to the device
If the device slips during installation, serious damage can result.
Ensure that the device is securely positioned at its place of
installation until all fastening screws have been tightened.
4.2 Electrical connection
DANGER
Voltage on the device
Electric shock
Always connectaprotective earth first.
Check the protective earth.
DANGER
Faulty insulation
Risk of fatal injury from electric shock
Use only cables that meet the specified installation
regulations for voltage, current, insulation material, capacity,
etc.
Route cables so that they cannot be touched by any
rotating parts.
CAUTION
Voltage
The fan isabuilt-in component and has no disconnecting switch.
Only connect the fan to circuits that can be switched off with
an all-pole disconnection switch.
When working on the fan, secure the system/machine in
which the fan is installed so as to prevent it from being
switched back on.
NOTE
Water ingress into wires or cables
Water ingress at the customer end of the cable can damage the
device.
Make sure the end of the cable is connected inadry
environment.
Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.
4.2.1 Requirements
; Check whether the data on the nameplate match the connection data.
; Before connecting the device, make sure the power supply matches
the device voltage.
; Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must haveacross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26/0.13 mm².
Ground conductor contact resistance according to EN 60335
Compliance with the impedance specifications according to EN 60335
for the protective earth connection circuit must be verified in the end
application.
Depending on the circumstances of installation, it may be necessary to
connect an additional protective earth conductor to the extra protective
earth terminal on the device.
4.2.2 Voltage control
With speed control using transformers or electronic voltage
regulators (e.g. phase control), excessive current may occur.
In addition, depending on how the device is installed, noises
can occur with phase control.
4.2.3 Variable frequency drive
Please useavariable frequency drive only after consultation with Systemair
Whenavariable frequency drive is used for speed adjustment, the
maximum safe operating speed (see 3.2 Nominal data) may not be
exceeded.
For operation with variable frequency drives, install sinusoidal
filters that work on all poles (phase-phase and phase-ground)
between the drive and the motor.
During operation with variable frequency drives, an all-pole
sine filter protects the motor against high-voltage transients that
can destroy the coil insulation system, and against harmful
bearing currents.
Heating of the motor due to use ofavariable frequency drive must be
checked in the application by the customer.
4.3 Connection in terminal box
4.3.1 Preparing cables for connection
Only strip the cable as far as necessary, ensuring that the cable gland is
sealed and there is no strain on the connections. For tightening torques,
see Chapter 3.1 Product drawing.
NOTE
Tightness and strain relief are dependent on the cable
used.
This must be checked by the user.