IMO AR 315DV SILEO

Operating instructions
Line voltage faulty Check line voltage,
restore power supply.
Faulty connection Isolate from supply,
correct connection;
see connection
diagram.
Thermal overload
protector activated
Allow motor to cool
off, locate and rectify
cause of error,
release restart lockout
if necessary
Impermissible point of
operation
Check point of
operation
Motor
overtemperature
Ambient temperature
too high
Reduce ambient
temperature if possible
Deficient cooling Improve cooling
In the event of further malfunctions, contact Systemair.
5.1 Cleaning
NOTE
Damage to the device during cleaning
Malfunction possible
Do not clean the device usingawater jet or high-pressure
cleaner.
Do not use any acid, alkali or solvent-basedcleaning
agents.
Do not use any pointed or sharp-edged objects for cleaning
5.2 Safety inspection
What to check How to check How often What action?
Contact
protection
cover for
intactness or
damage
Visual inspection At least every
6 months
Repair or
replacement of
device
Device for
damage to
blades and
housing
Visual inspection At least every
6 months
Replacement of
device
Fastening the
cables
Visual inspection At least every
6 months
Fasten
Fastening the
protective earth
terminal
Visual inspection At least every
6 months
Fasten
Insulation of
cables for
damage
Visual inspection At least every
6 months
Replace cables
Tightness of
cable gland
Visual inspection At least every
6 months
Retighten,
replace if
damaged
Condensation
drainage holes
for clogging,
where necessary
Visual inspection At least every
6 months
Open holes
Welds for crack
formation
Visual inspection At least every
6 months
Replace device
Abnormal
bearing noise
acoustic At least every
6 months
Replace device
5.3 Disposal
For Systemair, environmental protection and resource preservation are
top priority corporate goals.
Right from the development stage, ecological design, technical safety
and health protection are fixed criteria.
The following section contains recommendations for ecological disposal
of the product and its components.
5.3.1 Country-specific legal requirements
NOTE
Country-specific legal requirements
Always observe the applicable country-specific legal
regulations with regard to the disposal of products or waste
occurring in the various phases of the life cycle. The
corresponding disposal standards are also to be heeded.
5.3.2 Disassembly
Disassembly of the product must be performed or supervised by
qualified personnel with the appropriate technical knowledge.
The product is to be disassembled into suitable components for disposal
employing standard procedures for motors.
WARNING
Heavy parts of the product may drop off. Some of the
product components are heavy. These components
could drop off during disassembly.
This can result in fatal or serious injury and material damage.
Secure components before unfastening to stop them falling.
5.3.3 Component disposal
The products are mostly made of steel, copper, aluminum and plastic.
Metallic materials are generally considered to be fully recyclable.
Separate the components for recycling into the following categories:
Steel and iron
Aluminum
Non-ferrous metal, e.g. motor windings
Plastics, particularly with brominated flame retardants, in accordance
with marking
Insulating materials
Cables and wires
Electronic scrap, e.g. circuit boards
; Ferrite magnets can be disposed of in the same way as normal iron
and steel.
Electrical insulating materials on the product, in cables and wires are
made of similar materials and are therefore to be treated in the same
manner.
The materials concerned are as follows:
Miscellaneous insulators used in the terminal box
Power cables
Cables for internal wiring
Electrolytic capacitors