SYSCOIL COMFORT Engineering Data Manual (EDM SCC 01 S 2GB)
SYSCOIL COMFORT
12
Main Controls (Optional)
SysLogic communicating electronic control
(supplied tted)
SysLogic communicating electronic control
System networking
3 4 5
CTRL
GND
SIG
3 4 5
CTRL
+ - G+ - G
MB2
Mode
12 VGND SIG
Main Board
Main Board
Zone HMI
Max 1 wihtin a zone
Optional supervisor connected
to the optional MB2 card
Max 1 wihtin a zone
Max number of main boards
connected : 15
Q SysLogic controller can be congured in 2-pipes heating only or cooling
only, 2-pipes/2-wires, reversible 2-pipes with or without extra electric
heating or 4-pipe system.
Q Other pre-programmed functionalities included : master/slaves up to
15 units controlled from one remote control only; NC window contact;
automatic or manual selection of unoccupied mode.
Q The regulation SysLogic allows to pilot up to 15 ventilo-convectors in
master / slaves with a remote control WRC / MRC.
MB2 communication bus system allows to pilot up to 255 addresses via
a GTC.
Max. length of bus = 100 meters, shielded twisted pair cable.
WRC/MRC wire remote control with digital display
(supplied loose or tted)
BRC local terminal
(supplied loose or tted)
Q Wire remote control for wall mounting or for mounting on fan coil units.
Q ON/OFF; fan operation (auto or manual); operation mode (cooling,
heating, auto or fan operation only); temperature setpoint adjustment
in different modes.
Q ON/OFF; fan operation (auto or manual); temperature adjustement
(± 5°C)
VC
VN
HC