SYSCOIL COMFORT Engineering Data Manual (EDM SCC 01 S 2GB)

SYSCOIL COMFORT
17
Technical Data
Electrical heater
Models
with electric heating
BE1 BE2
heating capacity Minimum air ow heating capacity Minimum air ow
W m
3
/h W m
3
/h
SCC10
500 108 / /
SCC20
500 98 / /
SCC30
500 145
1000
(500 + 500)
206
SCC40
1 250 276 / /
SCC50
1 250 250
2500
(1250 + 1250)
484
SCC60
1 250 300
2500
(1250 + 1250)
475
SCC70
1 250 350
2500
(1250 + 1250)
522
SCC80
1 250 380
2500
(1250 + 1250)
812
Operating range with EC motor : Voltage setpoint
Models
Speeds - Voltage setpoint (V)
S1 S2 S3 S4 S5
SCC10 2 3 5 7 10
SCC20 2 4 5 7 10
SCC30 2 5 6 7 10
SCC40 2 4 5 8 10
SCC50 2 5 7 8 10
SCC60 2 5 7 8 10
SCC70 4 7 8 9 10
SCC80 3 3.4 4.1 4.85 6.4
Water volume (liters)
Models SCC10 SCC20 SCC30 SCC40 SCC50 SCC60 SCC70 SCC80
2 pipes L 0.41 0.61 0.89 1.17 1.45 1.73 2.19 2.6
4 pipes
Cooling L 0.41 0.61 0.89 1.17 1.45 1.73 2.19 2.6
Heating L 0.2 0.2 0.3 0.39 0.48 0.58 0.73 0.92
Operating limits
Environmental conditions
Minimum premise air temperature / new air intake / around the apparatus 5°C / 15% HR
Maximale premise air temperature / new air intake / around the apparatus 32°C / 70% HR
Water circuit
Max. operating pressure 16 bars
Min. entering water temperature (without glycol) +5°C
Max. entering water temperature +90°C