technical documentation manuals 308013008

Installation |
15
Lifting and positioning
The weight of the fan units varies depending on the motor size and accessories. As a result, the fan unit can also be
very bulky and heavy. You can find precise information on the name plate or the data sheet.
Caution
Risk of parts falling down
When fitting the fan, pay attention to its weight and the weight of the components.
Lifting
Lift the fan unit slowly and carefully.
Use hoisting gear permitted for the weight of the fan.
Attach the hoisting equipment to flanges and foot
bores or at the marked places.
Use transport equipment (e.g. lifting eyes) if available.
Please observe the marking “oben/top” on the fan.
Positioning
Observe the arrows on the name plate or the housing
of the fan. They show the direction of rotation and air
flow.
Position the fan unit so that it is standing in the
planned direction of flow.
Provide enough free space for inspection and
maintenance work on the fan unit.
Anchor
Use suitable fittings.
If you are not sure, contact Systemair.
7.2 Installation positions
AXC, AXR, AXS
Consider below guideline for installation positions.
Note:
Order process (Systemair configurator): If the type of installation is e.g. "SO" (vertical installation, >= IEC
160), a suitable motor is automatically used (in this case with different bearings).
Please contact Systemair if a position marked with a “red-cross” is required for an existing fan.
Fans equipped with
B3 <160 and B30 (Pad)
The installation is possible in any mounting position.
B3 >160
AXCBF
Important
Overheating motor
The motor opening must be faced upwards to avoid trapped heat.
| 008