technical documentation manuals 308013008

Troubleshooting/maintenance/repair |
25
Activities for fans used for emergency operation. cont'd
Operational readiness of the
emergency system
Allow the "emergency" system to run for
15 minutes
X
Function of the “emergency” control
Test whether the “emergency” control
effectively bridges all the other controls
and switches
X
Function of the standstill heating
Switch the motor off. The standstill heating
must switch on automatically and remain
switched on
X
11.3 Variable-speed fans
Important
The fan may be destroyed due to unpermitted frequencies.
Pay particular attention to damage from vibrations.
After commissioning, start with shorter maintenance intervals.
If no damage occurs, adjust the maintenance intervals up to the those stated in the operating
instructions.
Responsibility for gradual adaptation is with the system operator.
11.4 Overhaul/further maintenance
Pay attention to the safety references and preconditions as in normal maintenance. For the following activities and
functions, contact Systemair:
complete overhaul of motors
replacement of bearings
re-winding of motors
monitoring of condition
vibration analysis
Extension of maintenance intervals
Systemair axial fans withoutVDD need to be maintained after a 20,000/40,000 hours of operation (depending on
the type of motor bearing) or at the latest after 5 years.
The maintenance intervals can be prolonged using VDD, as shown in the table below.
after hours of operation: at the latest after:
without VDD with VDD without VDD with VDD
motor with closed
bearings
40000 hours 60000 hours
5 years 8 years
motor with open
bearings
20000 hours 40000 hours
5 years 8 years
If the fan is operating with VDD, maintenance action is necessary after above specified time or if the limit values for vi-
bration according to ISO 14694:2003 are exceeded.
Steps to maintain a Systemair axial fan:
Check the condition of the shaft sealing rings and shaft bearings and take action if necessary.
If the motor is equipped with a relubrication device, relubricate according to the specifications of the motor
manufacturer.
Work before switching on again
Attach all the safety and protective devices tightly and securely.
Remove all the devices with which you have blocked the rotor.
Remove all assembly residues and foreign bodies from the area around the fan unit.
| 008