User Manual

Table Of Contents
20
| Technical data
GB
Table 4 Heating and cooling power GEO 300
m³/h
Supply air temperature (winter °C) Supply air temperature (summer °C)
100
4,26 13,5
200
1,6 16,1
300
-0,99 18,1
Table 5 Heating and cooling power GEO 500
m³/h
Supply air temperature (winter °C) Supply air temperature (summer °C)
100
5,4 12,5
150
4,7 13,3
250
3,08
15
350
1,25 16,5
450
-0,35 17,8
12.2 Wiring diagrams