DataSheet DKIR1 DKIS1201711

6 / 6 | Fire Safety Products
Technical parameters
Utilisation in SHEVS in single re compartment
Test temperature 600 °C
Durability test 10 000 + 100 + 100 cycles without a change to the required attributes
Testing pressure -500 Pa / -1500 Pa (see Tab. 1)
Safe position closed / open according to situation in the re compartment
Airow direction given by SHEVS design
Allowed air velocity max. 12 m/s
Closure/opening servomotor driven
Closed/open indication microswitches included in servo
Environment suitability only indoor environment (3K5 according to EN 60721-3-3)
Ambient temperature -20 °C up to +50 °C
Inspection possibility after opening of the inspection lid
Maintenence not needed
Damper installation
The dampers’ installation is always designated by the
particular ventilation project, which must comply with valid
standards. Damper distances from building constructions,
technological distributors and ventilation devices must be
such that the authorized mounting people will be able to
do the installation, functional tests, revisions and services.
There must be at least 200 mm space between two
dampers or between the damper and the wall or ceiling.
Usage and operation
The DKIR1 / DKIS1 is a part of a heat exhaust ventilation
system (SHEVS). The system helps to keep the exits
smoke-free, facilitates the job for re brigades, slows
down the spread of re. This system is created in larger
buildings, where the size and shape of the building do
not enable natural smoke exhaust when re occurs. The
damper is controlled by a servo-drive which, triggered
by an electric impulse from a smoke alarm or remote-
controlled by electric re signalization center, opens or
closes the damper blade according to the needs of the
SHEVS and according to the situation in relevant re
compartment. Servomotor closes or opens the damper
within 60 seconds.
Transportation, storage
and operation conditions
It is essential to transport the dampers by such means of
transport that provide a cover and secured on pallets. If
manipulation occurs during the transportation or storage,
dampers must be protected against damage and weather
conditions. Damper blades must be in the closed position.
It is recommended to store these products in a closed and
dry area with a temperature range from -10°C to 50°C.
Materials used and disposal
This product contains iron, brass, zinc, calciumsilicate
non-asbestos boards, passive and active anti-re sealing.
They are disposed of according to valid legal regulations.
The product does not contain any dangerous materials.
Warranty conditions
The producer provides a 24-month warranty starting
on the date of expedition.
Appendix
Any demands regarding deviations from the above
mentioned technical specications and conditions shall
be discussed with the manufacturer. The manufacturer
reserves the right to perform any technical modications
of the product without prior notice, provided that such
changes have no effect on the quality and performance
of the product.
IMOS-Systemair · November 2017 · DataSheet_DKIR1_DKIS1