CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 4 Input Register 13
Chapter 4 Input Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentActual.Cor_Outdoor temp(0)
R
30001
Actual/Setpoint
Outdoor temperature (read-only)
VentActual.Cor_Efficiency
R
30002
Actual/Setpoint
Efficiency in % for exchanger
VentActual.Cor_RunMode
X
30003
Actual/Setpoint
Modbus:
0=Stopped
1=Starting up
2=Starting reduced speed
3=Starting full speed
4=Starting normal run
5=Normal run
6=Support control heating
7=Support control cooling
8=CO
2
run
9=Night cooling
10=Full speed stop
11=Stopping fan
BACnet:
1=Stopped
2=Starting up
3=Starting reduced speed
4=Starting full speed
5=Starting normal run
6=Normal run
7=Support control heating
8=Support control cooling
9=CO
2
run
10=Night cooling
11=Full speed stop
12=Stopping fan
VentActual.Cor_SAFRunTime
R
30004
Actual/Setpoint
Running time (hour) supply air fan
VentActual.Cor_EAFRunTime
R
30005
Actual/Setpoint
Running time (hour) extract air fan
VentActual.Cor_ExtendedRunMin
I
30006
Actual/Setpoint
Number of minutes extended
operation
VentActual.Cor_SupplyAirTemp
R
30007
Supply, Extract
and Room
temperatures
Supply air temperature
VentActual.Cor_SupplyPID_SetP
R
30008
Supply, Extract
and Room
temperatures
Calculated setpoint supply air
temperature when outdoor
compensated control function or
cascade control is active
VentActual.Cor_ExhaustAirTemp:
(NB: This is actually the variable for
the extract air temp!)
R
30009
Supply, Extract
and Room
temperatures
Extract air temperature